2
Connections - terminals Control circuit: screw clamp terminals 1 cable 0.75...1.5 mm² - cable stiffness:
flexible - without cable end
Control circuit: screw clamp terminals 2 cable 0.34...1.5 mm² - cable stiffness:
flexible - with cable end
Power circuit: screw clamp terminals 1 cable 1...6 mm² - cable stiffness: flexible -
with cable end
Control circuit: screw clamp terminals 1 cable 0.34...1.5 mm² - cable stiffness:
flexible - with cable end
Power circuit: screw clamp terminals 1 cable 2.5...10 mm² - cable stiffness: flexi-
ble - without cable end
Power circuit: screw clamp terminals 2 cable 1...6 mm² - cable stiffness: flexible -
with cable end
Power circuit: screw clamp terminals 2 cable 1.5...6 mm² - cable stiffness: flexible
- without cable end
Power circuit: screw clamp terminals 2 cable 1...6 mm² - cable stiffness: rigid -
without cable end
Control circuit: screw clamp terminals 1 cable 0.75...1.5 mm² - cable stiffness:
rigid - without cable end
Power circuit: screw clamp terminals 1 cable 1...10 mm² - cable stiffness: rigid -
without cable end
Control circuit: screw clamp terminals 2 cable 0.75...1.5 mm² - cable stiffness:
flexible - without cable end
Control circuit: screw clamp terminals 2 cable 0.75...1.5 mm² - cable stiffness:
rigid - without cable end
Tightening torque Power circuit: 1.9...2.5 N.m - with screwdriver 6 mm flat
Control circuit: 0.8...1.2 N.m - with screwdriver 5 mm Philips no 1
Control circuit: 0.8...1.2 N.m - with screwdriver 5 mm flat
Power circuit: 1.9...2.5 N.m - with screwdriver 6 mm Philips No 2
Width 45 mm
Height 224 mm
Depth 126 mm
Product weight 1.27 kg
Environment
Heat dissipation 1.7 W for control circuit with LUCM
2 W for control circuit with LUCA, LUCB, LUCC, LUCD
Immunity to microbreaks 3 ms
Immunity to voltage dips 70 % 500 ms conforming to IEC 61000-4-11
Product certifications ABS
GL
ATEX
DNV (Det Norske Veritas)
BV
CCC
ASEFA
GOST
LROS (Lloyds register of shipping)
CSA
UL
Standards IEC 60947-6-2
UL 508 type E with phase barrier
EN 60947-6-2
CSA C22-2 No 14 type E
IP degree of protection IP20 front panel and wired terminals conforming to IEC 60947-1
IP40 front panel outside connection zone conforming to IEC 60947-1
IP20 other faces conforming to IEC 60947-1
Protective treatment TH conforming to IEC 60068
Ambient air temperature for operation -25...70 °C with LUCA, LUCB, LUCC, LUCD
-25...60 °C with LUCM
Ambient air temperature for storage -40...85 °C
Fire resistance 960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
Operating altitude 2000 m
Shock resistance 10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance 4 gn 5...300 Hz power poles closed conforming to IEC 60068-2-27
2 gn 5...300 Hz power poles open conforming to IEC 60068-2-27
Resistance to electrostatic discharge 8 kV level 4 on contact conforming to IEC 61000-4-2
8 kV level 3 in open air conforming to IEC 61000-4-2
Resistance to radiated fields 10 V/m 3 conforming to IEC 61000-4-3