IPC 16/ 6-STGF-10,16 Order No.: 1975859
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1975859
PHOENIX CONTACT Inc., USA Page 2 / 5
http://www.phoenixcon.com Feb 17, 2010
Tightening torque max 1.8 Nm
Technical data
Insulating material group I
Rated surge voltage (III/3) 8 kV
Rated surge voltage (III/2) 8 kV
Rated surge voltage (II/2) 6 kV
Rated voltage (III/2) 1000 V
Rated voltage (II/2) 1000 V
Connection in acc. with standard EN-VDE
Nominal current IN76 A
Nominal voltage UN1000 V
Nominal cross section 16 mm²
Insulating material PA
Inflammability class acc. to UL 94 V0
Internal cylindrical gage A6
Stripping length 14 mm
Connection data
Conductor cross section solid min. 0.75 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section stranded min. 0.75 mm²
Conductor cross section stranded max. 16 mm²
Conductor cross section stranded, with ferrule
without plastic sleeve min.
0.5 mm²
Conductor cross section stranded, with ferrule
without plastic sleeve max.
16 mm² Only in connection with CRIMPFOX 16 S
Conductor cross section stranded, with ferrule
with plastic sleeve min.
0.5 mm²
Conductor cross section stranded, with ferrule
with plastic sleeve max.
16 mm² Only in connection with CRIMPFOX 16 S
Conductor cross section AWG/kcmil min. 18
Conductor cross section AWG/kcmil max 6
2 conductors with same cross section, solid min. 0.75 mm²
2 conductors with same cross section, solid max. 6 mm²
2 conductors with same cross section, stranded
min.
0.75 mm²
2 conductors with same cross section, stranded
max.
6 mm²