34 PRODUCT CATALOGUE - STEGOCOOLING
Enclosure air-conditioning using a filter fan
and exit filter
TECHNICAL DATA
Axial fan, ball bearing service life 50,000h at +25°C (+77°F), 65% RH
fan body aluminium, rotor plastic
Connection 2 wires with pressure clamps 2.5mm², length 100mm
Casing (filter fan and exit filter) plastic according to UL94 V-0, light grey
Hood (filter fan and exit filter) plastic according to UL94 V-0, light grey;
weather proof and UV light resistant according to UL746C (f1)
Mounting frame with double-sided industrial adhesive band for fixing to the
outside of enclosure; certain operating circumstances can make
the additional use of screws necessary (see drilling template);
a template for the enclosure cut-out is included in the delivery
of the filter fans
Filter mat G4 acc. to DIN EN 779, filtering degree 94%
Filter material synthetic fibre with progressive construction,
temperature resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH,
reusable - cleaning by washing or vacuuming
Operating/Storage temperature -10 to +70°C (+14 to +158°F) / -40 to +70°C (-40 to +158°F)
Operating/Storage humidity max. 90% RH (non-condensing)
Protection type/Protection class IP55 / I (earthed)
Special features
> The self-adhesive seal of the mounting frame prevents dust and water from entering the cabinet.
> Functional design of the intake and exit fan hoods very effectively prevents direct intrusion of falling water and dust.
The advantage is that the filter mat does not get so quickly contaminated with dirt and thus does not need to
be exchanged so often.
> The air channeling makes the filter fan particularly quiet in operation.
> Functional and modern design enables time-saving assembly and maintenance.
> The direction of air flow can easily be switched by reversing the axial fan (sizes 1 to 3).
> EMC versions and other voltages on request.
FILTER FAN
FF 018 | 21m³/h to 102m³/h
Filter fans are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can
be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The
resulting air flow prevents formation of localised hot pockets and protects the electronic components from over-
heating. The plastic used for the hood of this filter fan series is highly weather proof and UV light resistant.
> Very low noise
> Minimal depth in enclosure
> Functional design
> Time-saving installation
> Weather proof and UV resistant
Art. No. Operating
voltage
Air volume,
free flow
Air volume
with exit
filter
Current
consumption
Power
consumption
Average noise
level (DIN EN
ISO 4871)
Depth in
enclosure
Enclosure cut-out
Weight
(approx.)
Approvals
01800.0-00 230VAC, 50Hz
21m³/h 16m³/h 80mA 13W 31db (A) 45mm
97 x 97mm + 0.4
0.6kg
VDE + UL File No. E234324
01801.0-00
230VAC, 50Hz
55m³/h 42m³/h 100mA 15W 40db (A) 58mm
125 x 125mm + 0.4
1.0kg
VDE + UL File No. E234324
01802.0-00
230VAC, 50Hz
102m³/h 68m³/h 100mA 15W 39db (A)
86mm
176 x 176mm + 0.4
1.3kg
VDE + UL File No. E234324
01800.0-01
120VAC, 60Hz
24m³/h 18m³/h 160mA 13W 31db (A) 45mm
97 x 97mm + 0.4
0.6kg
UL File No. E234324
01801.0-01
120VAC, 60Hz
63m³/h 48m³/h 180mA 15W 40db (A) 58mm
125 x 125mm + 0.4
1.0kg
UL File No. E234324
01802.0-01
120VAC, 60Hz
117m³/h 78m³/h 180mA 15W 39db (A)
86mm
176 x 176mm + 0.4
1.3kg UL File No. E234324
FILTER FAN FF 018
TECHNICAL DATASHEET
20.03.2013 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se
35
STEGO - PRODUCT CATALOGUE COOLING
Art. No. Depth in enclosure Enclosure cut-out Weight (approx.) Filter mat Protection type
11800.0-00 16mm 97 x 97mm + 0.4 0.3kg G4 acc. to DIN EN 779, filtering degree 94% IP55
11801.0-00 16mm 125 x 125mm + 0.4 0.4kg G4 acc. to DIN EN 779, filtering degree 94% IP55
11802.0-00 16mm 176 x 176mm + 0.4 0.6kg G4 acc. to DIN EN 779, filtering degree 94% IP55
Time-saving assembly and maintenance
STEGO´s filter fans are easily installed by one person from outside the cabinet.
1.) Make cut-out in the cabinet wall. The cut edge of the cabinet opening should be free of dirt, filings and
grease. A template for the enclosure cut-out is included in the delivery of the filter fan.
2.) Remove protective film from the sealing strips on the mounting frame. Press mounting frame into the
cabinet opening. The frame stays permanently in the cabinet. (For size 176mm and up we recommend
additional screw fixing.)
3.) Electrically connect the axial fan using the clip connectors. Push the unit into the mounting frame.
Fix using screws.
4.) Insert the filter mat in the hood. Clip on. Finished.
Changing the filter mat or fan is quickly done by one person. To change the filter mat simply remove the filter
hood, insert the new mat and snap the hood back again. No tools required. Maintenance of the fan can easily be
done without removing the mounting frame (2).
Filter mat 89 x 89mm 118 x 118mm 168 x 168mm
G4 (1 packaging unit = 3 pcs.) Art. No. 08600.0-00 Art. No. 08601.0-00 Art. No. 08602.0-00
Size 1
TECHNICAL DRAWINGS
EXIT FILTER EF 118
FILTER MAT FM 086
DRILLING TEMPLATE FOR MOUNTING FRAME
Installation sketch
Size 2 Size 3
TECHNICAL DATASHEET
20.03.2013 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se