XVP Illuminated Indicating Banks
Characteristics
© 2001 Schneider Electric All Rights Reserved
2
11/01
CHARACTERISTICS
Environment
Product certifications UL Listed, CSA Certified
File E164353
CCN NKCR
File LR 44087
Class 3211 03
File E164353
CCN NKCR 2
Conforming to standards CE Marked IEC/EN 60947-5-1. UL 508
Protective Treatment “TC”
Ambient Air Temperature (Storage) –40 to + 158 °F
–40 to +70 °C
Operation Illuminated lens unit, steady,
with LED or 7 W incandescent bulb
–13 to +122 °F (–25 to +50 °C)
Flashing Units with LED or
7 W incandescent bulb
Units with Strobe
Audible Sounder Units
Electric Shock Protection
conforming to IEC 536
Tube mounting Class 1
Direct mounting on base unit Class 2
Degree of Protection To IEC 60529 and NF C 20-010
To UL 50 and CSA 22.2 No. 94
IP 65
Type 1, 12, 13
Material Illuminated lens unit Polycarbonate
Base unit and top cover ABS + Polycarbonate
Ring on lens and base Polyamide
Tube mounting Aluminum
Tulip ABS + Polycarbonate
Electrical Characteristics
Rated Insulation Voltage (UL) Conforming to IEC 60947-1 250 Vac
Consumption LED unit 24 Vac/Vdc: <60 mA
120–230 Vac: <20 mA
Steady Incandescent bulb 7W 24 Vac/Vdc: <300 mA; 120–230 Vac: 65–35 mA
Flashing 24 Vac or 24 Vdc <250 mA; 120–230 Vac < 30mA
Unit with strobe (on energization) 24 Vdc: 0.3 Joules, 40 mA; 120 Vac: 0.6 Joules, 20mA;
230 Vac: 0.6 Joules, 11mA
Audible sounder units 24 Vdc, 12 mA; 120 Vac, 15 mA; 230 Vac, 15 mA
Rated Impulse withstand voltage Conforming to IEC 60947-1 U imp = 4 kV
Bulb type Illuminated units, steady or flashing Bayonet type BA 15d; 5 W minimum power; 7 W maximum power
Illuminating Power Strobe Units 0.3 Joules, 24 Vdc, 1.2 cd; 0.6 Joules, 120 Vac, 5.0 cd;
0.6 Joules, 230 Vac, 5.0 cd
Audible sounder units Signal At one meter: 75–85 dB
Terminal marking Common 1 terminal marked –/N
Depending on type of units 1 to 5 terminals marked 1+/L to 5+/L
Ground Marked with grounding symbol
Cable size Maximum wire size 2 x #16 AWG (1.5 mm2) with cable end
Terminals Torque requirement Removable and captive screw terminals: 4.4 lb-in (0.5 Nm)
Ring tongue connectors Burndy YAV14RL33 Wire: 20–14 AWG
Studs: 4–6
Width: 0.25 in.
Frequency of Illuminated units Strobe Units 0.7 Hz–2.0 Hz
Specific Characteristics of Protected LED Bulbs
Voltage limits Nominal voltage 24 V: 19.2 to 30 Vdc; 21.6 to 24.6 Vac
120 V: 100 to 132 Vac
240 V: 200 to 264 Vac
Current consumption Applicable to all colors 24 Vac/Vdc supply: 24 mA
120 Vac supply: 18 mA
240 Vac supply: 18 mA
Service life At nominal voltage and at an ambient temperature of 77 °F (25 °C) 100,000 hours
Surge withstand Conforming to IEC 61000-4-5 1 kV (differential)
Resistance to fast transients Conforming to IEC 61000-4-4 2 kV
Resistance to electromagnetic fields Conforming to IEC 61000-4-3 10 V/m
Resistance to electrostatic discharges Conforming to IEC 61000-4-2 8/6 kV
Electromagnetic emission Conforming to EN 55011 Class B