Specifications are subject to change without notice 1
Current and Voltage Contr ols
Voltage metering relay with absolute scale
Measuring ranges:
SJ 135: 12 mV - 500 VDC divided into 10 ranges
SJ 185: 20 mV - 500 VAC divided into 8 ranges
Knob-adjustable set point
Latching at set level possible
Output: 10 A SPDT relay
Plug-in type module
S-housing
LED-indication for output ON
AC or DC power supply
Product Description
1-phase AC or DC plug-in vo l -
tage metering relays. Often
used in e.g. electrical heat
Ordering Key
Housing
Function
Output
Type
Power supply
Measuring range
Type Selection
Plug Output Measuring range Supply: 24 VAC Supply: 115 VAC Supply: 230 VAC Supply: 24 VDC
DC-voltage metering
Circular SPDT 12 - 60 mVDC SJ 135 024 60mV SJ 135 115 60mV SJ 135 230 60mV SJ 135 724 60mV
30 - 150 mVDC SJ 135 024 150mV SJ 135 115 150mV SJ 135 230 150mV SJ 135 724 150mV
0.2 - 1 VDC SJ 135 024 1V SJ 135 115 1V SJ 135 230 1V SJ 135 724 1V
1 - 5 VDC SJ 135 024 5V SJ 135 115 5V SJ 135 230 5V SJ 135 724 5V
2 - 10 VDC SJ 135 024 10V SJ 135 115 10V SJ 135 230 10V SJ 135 724 10V
4 - 20 VDC SJ 135 024 20V SJ 135 115 20V SJ 135 230 20V SJ 135 724 20V
10 - 50 VDC SJ 135 024 50V SJ 135 115 50V SJ 135 230 50V SJ 135 724 50V
30 - 150 VDC SJ 135 024 150V SJ 135 115 150V SJ 135 230 150V SJ 135 724 150V
60 - 300 VDC SJ 135 024 300V SJ 135 115 300V SJ 135 230 300V SJ 135 724 300V
100 - 500 VDC SJ 135 024 500V SJ 135 115 500V SJ 135 230 500V SJ 135 724 500V
AC-voltage metering
Circular SPDT 20 - 100 mVAC SJ 185 024 100mV SJ 185 115 100mV SJ 185 230 100mV SJ 185 724 100mV
0.2 - 1 VAC SJ 185 024 1V SJ 185 115 1V SJ 185 230 1V SJ 185 724 1V
2 -10 VAC SJ 185 024 10V SJ 185 115 10V SJ 185 230 10V SJ 185 724 10V
4 - 20 VAC SJ 185 024 20V SJ 185 115 20V SJ 185 230 20V SJ 185 724 20V
10 - 50 VAC SJ 185 024 50V SJ 185 115 50V SJ 185 230 50V SJ 185 724 50V
30 - 150 VAC SJ 185 024 150V SJ 185 115 150V SJ 185 230 150V SJ 185 724 150V
60 - 300 VAC SJ 185 024 300V SJ 185 115 300V SJ 185 230 300V SJ 185 724 300V
100 - 500 VAC SJ 185 024 500V SJ 185 115 500V SJ 185 230 500V SJ 185 724 500V
Input Specifications
controls where a specific re-
action is desired when a cer-
tain voltage level is exceeded.
Input
Through pins 5 & 7
AC/DC voltage, pin 5 pos. at DC
Measuring ranges (SJ 135) Internal resist. Max. volt.
12 - 60 mVDC 100 1 V
30 - 150 mVDC 100 2 V
0.2 - 1 VDC 1 k10 V
1 - 5 VDC 3 k30 V
2 - 10 VDC 10 k50 V
4 - 20 VDC 20 k100 V
10 - 50 VDC 51 k150 V
30 - 150 VDC 150 k350 V
60 - 300 VDC 300 k500 V
100 - 500 VDC 510 k600 V
Measuring ranges (SJ 185) Internal resist. Max. volt.
20 - 100 mVAC 100 1 V
0.2 - 1 VAC 1 k10 V
2 - 10 VAC 10 k50 V
4 - 20 VAC 20 k100 V
10 - 50 VAC 51 k150 V
30 - 150 VAC 150 k350 V
60 - 300 VAC 300 k500 V
100 - 500 VAC 510 k600 V
ranges equal rms-value of
a sinusoidal voltage
Max. line voltage 277/480 AC/DC
Latching Interconnect pins 8 & 9
latching at set level possible
1-Phase AC/DC Voltage Contr ol
Types SJ 135, SJ 185
SJ 135 024 500V
2Specifications are subject to change without notice
SJ 135, SJ 185
Output SPDT relay
Rated insulation voltage 250 VAC (rms)
(cont./elect.)
Contact ratings (AgCdO) µ (micro gap)
Resistive loads AC 1 10 A/250 VAC (2500 VA)
DC 1 1 A/250 VDC (250 W)
or 10 A/25 VDC (250 W)
Small inductive loads AC 15 2.5 A/230 VAC
DC 13 5 A/24 VDC
Mechanical life 30 x 106operations
Electrical life AC 1 2.5 x 105operations
(at max. load)
Operating frequency 7200 operations/h
Dielectric strength
Dielectric voltage 2 kVAC (rms) (cont./elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
Power supply AC types Overvoltage cat. III (IEC 60664)
Rated operational voltage (IEC 60038)
Through pins 2 & 10 024 24 VAC ± 15%, 45 to 65 Hz
115 115 VAC ± 15%, 45 to 65 Hz
230 230 VAC ± 15%, 45 to 65 Hz
Voltage interruption 40 ms
Dielectric voltage 2 kV AC (rms) (supply/elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (line/neutral),
no direct connection to electr.
Power supply DC types Overvoltage cat. III (IEC 60664)
Rated operational voltage (IEC 60038)
Through pins 2 & 10 724 24 VDC ± 15%
Dielectric voltage None (supply/elect.)
Rated impulse withstand volt. 800 V (1.2/50 µs)
Rated operational power
AC supply 2.5 VA
DC supply 1.5 W
Reaction time Relay operates: τ= 22 ms
Relay releases: τ= 2.2 s,
worst case reaction time
may be up to 5 x τ
Accuracy
Input 0 to 10% on max.
Min. actual level
min. set level
Indication for
Output ON LED, yellow
Environment (IEC 60947-1)
Degree of protection IP 20 B (IEC 60947-1)
Pollution degree 2 (IEC 60664)
Operating temperature -2 0° to +50 °C (-4° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Weight AC supply 200 g
DC supply 125 g
Approvals UL, CSA
SJ 135
Example 1
DC voltage metering
(AC power supply)
The relay operates when the
actual voltage reaches set
point.
The relay releases when the
voltage drops min. 10% be-
low set point (see hysteresis)
or when power supply is in-
terrupted.
Example 2
DC voltage metering -
latching (AC power supply)
The relay operates and re-
mains in operating position
when the actual voltage
reaches set point.
Provided that the voltage has
dropped min. 10% below the
set point (see hysteresis) the
relay will release when the in-
terconnection between pins 8
and 9 is interrupted. The relay
also releases when power
supply is interrupted.
Example 3
AC or DC metering
(DC power supply)
Please note that pins 7 and
10 are internally connected at
DC power supply. No current
must pass through this inter-
nal connection.
Mode of Operation
SJ 185
The SJ 185 measures the ave-
rage of a sinusoidal voltage
(input). The set point, cali-
brated to rms-value, is set on
built-in potentiometer.
Example 1
AC voltage metering
(AC power supply
The relay operates when the
voltage reaches set point.
The relay releases again when
the voltage has dropped min.
10% below the set point (see
hysteresis), or when power
supply is interrupted.
Example 2
AC voltage metering -
latching
(AC Power supply)
The relay operates and re-
mains in operating position
when the voltage reaches set
point.
Provided that the voltage has
dropped min. 10% below set
point (see hysteresis) the re-
lay releases when the inter-
connection between pins 8
and 9 is interrupted. The relay
also releases when power
supply is interupted.
Example 3
AC or DC metering
(DC power supply)
Please note that pins 7 and
10 are internally connected at
DC power supply. No current
must pass through this inter-
nal connection.
Supply Specifications
Output Specifications
General Specifications
Specifications are subject to change without notice 3
Wiring Diagrams
Range setting
Adjustable set point on abso-
lute scale.
Hysteresis
Approx. 10%.
The hysteresis may be ex-
Range Setting
tended to approx. 75% by
connecting a suitable resis-
tor between pins 8 and 9.
Resistor limits are 470 k/
3k(0.25 W).
The hysteresis increases by
decreasing r esistance.
SocketsS 411
Hold down springHF
Mounting rack SM 13
Socket covers BB 4
Front mounting bezel FRS 2
Potentiometer lock PL 1
For further information refer to "Accessories".
Accessories
Operation Diagrams
Example 1
Power supply
Input voltage - 10%
pins 5 & 7
Relay ON
Example 2
Power supply
Latching
Input voltage - 10%
pins 5 & 7
Relay ON
Example 1 Example 2 Example 3
Power supply
SJ 135/SJ 185 Power supply
SJ 135/SJ 185 Power supply
SJ 135/SJ 185 PE = Pin 7
Latch
Set value Set value