Surge protection device-TT-ST-M-EX(I)-24DC-2859424
Technical data
General
Housing material PA 6.6
Inflammability class according to UL 94 V-2
Color blue
Standards for air and creepage distances EN 60079-11
Mounting type DIN rail: 35 mm
Type Double-level terminal block with disconnect knife
Direction of action Line-Line & Line-Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous operating voltage UC30 V DC
Maximum continuous voltage UC (wire-ground) 30 V DC
Nominal current IN200 mA (TA < 40 °C)
Operating effective current IC at UC≤ 10 µA
Residual current IPE ≤ 2 µA
Nominal discharge current In (8/20) µs (Core-Core) 5 kA
Nominal discharge current In (8/20) µs (Core-Earth) 5 kA
Total surge current (8/20) µs 10 kA
Total surge current (10/350) µs 2 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth) 5 kA
5 kA
Nominal pulse current Ian (10/1000) µs (Core-Core) 100 A
Nominal pulse current Ian (10/1000) µs (Core-Earth) 100 A
Impulse discharge current (10/350)˽µs, peak value limp 1 kA
Output voltage limitation at 1 kV/µs (Core-Core) spike ≤ 40 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 1.5 kV
Output voltage limitation at 1 kV/µs (Core-Core) static ≤ 40 V
Output voltage limitation at 1 kV/µs (Core-Earth) static ≤ 1.5 kV
Residual voltage at In, (conductor-conductor) ≤ 40 V
Residual voltage with Ian (10/1000)µs (conductor-conductor) ≤ 45 V
Voltage protection level UP (Core-Core) ≤ 60 V (C2 -5 kA)
Voltage protection level UP (Core-Earth) ≤ 1.5 kV (C2 -5 kA)
Response time tA (Core-Core) ≤ 1 ns