I11
www.sti.com/info
I
Mini Contactor Relays 4-Pole
• ACandDCoperated
• 4-,6-and8-poleversionsindifferentcongurations
• Mirroredcontacts
• Screwxingandsnaptting(35mmDINrail)
• Ratedcurrent=10A(Ith)
• Suitableforelectronicdevices(DIN19240)
• Fingerproof(VBG4)
• ARapidDeliveryProduct:Selectmodelsareavailablefor
shipmenttodayorwithin3to5days
Accessories
• 2-and4-poleadditionalauxiliarycontactsindifferent
congurations
Force-Guided Relays & Power Contactors
J7KNA-AR J7KNA
Specifications
Electrical
OperatingCoil
SupplyPower: 24VDC,110VACor230VAC
Inrush: 25VAforACversions
3WforDCversions
PowerUsage: 4.5VAforACversions
2.5WforDCversions
RatedCarryCurrent: 10A@40C
SwitchingCapabilityInductive
Loads(AC-15,DC-13)
AC: Break120V-6A,240V-3A(continuous10A)
DC: 24V-3A
Max.SwitchingFrequency: 10,000perhour
Min.SwitchingCurrent: 5mA
Max.Drop-OutTime*: 8-25msforACversions
8-25msforDCversions
Mechanical
MechanicalLife: 1x107operationsmin.
Mounting: 35mmDINrailor4screwholesforpanelmounting
WireSize: Screwterminalsaccepttwo14AWGsolidorstrandedwires
Weight: ACversions:160g(5oz.)
DCversions:190g(6oz.)
Vibration: 5to300Hz
Environmental
VibrationResistance: 2gwithcontrolrelayopen;4gwithcontrolrelayclosed
OperatingTemperature: -40to60°C(-40to140·F)
Approvals: IEC947-5-1,VDE0660,EN60947-5-1,UL508
*TheDrop-OutTimeisthetimeittakesfortheN/OcontactstoopenafterthecoilvoltageisturnedOFF.
Specicationsaresubjecttochangewithoutnotice.
Approved Standards
Standard Guide No. (US,C)
UL NKCR,NKCR7
ICE947-5-1
VDE0660
EN60947-5-1
R
For full product information, visit www.sti.com. Use the SpeedSpec Code or scan the QR Code for quick access to the specific web page.
Select models are available for Rapid Delivery.
Visit this product on www.sti.com for details..