Embedded Power for Business-Critical Continuity MP Series Rev. 01.01.2012 MP Series 1 of 6 MicroMP 1U Multi Output Up to 1200 Watts Total Power: Up to 1200 Watts Input Voltage: 85 - 264 Vac 120-300 Vdc # of Outputs: Up to 12 Special Features * * * * * * * * * * * * * * * Full Medical EN60601 approval PMBus High efficiency Current limit modification (foldback or constant current) High power density. uMP4: 10.8 W/cu-in uMP1: 15.1 W/cu-in Intelligent fan (speed control/fault status) Downloadable GUI from website uP controlled PFC input with active inrush protection Optional conformal coating Industrial temp range (-40 C to 70 C) No preload required Industrial shock/vibration (> 50G's) Low cost IEC or terminal block input Low profile 1U size Electrical Specifications MP4C shown Input Input range: 85 - 264 Vac, 120 - 350 Vdc (limited to 250 Vac/300 Vdc in medical apps) Frequency: 47 - 440 Hz Inrush current: 40 A peak max. (soft start) Efficiency: Up to 91% @ full case load Power Factor: 0.99 typ. meets EN61000-3-2 (n/a @ 440 Hz) Turn-on time: AC on 2 sec for uMP1 and 1.5 sec for uMP4, inhibit/enable 250 ms typical EMI filter: CISPR 22/EN55022 Level "B" Leakage current: 300 A max. @ 240 Vac for uMP1 and 500 A max for uMP4; 47 - 63 Hz Radiated EMI: CISPR 22/EN55022 Level "B" Holdover storage: 16.7 ms minimum (independent of input Vac, 0 C to 50 C)) AC OK: Signal goes low indicating loss of AC input. Hold up = Full cycle ride thru (50 Hz) Harmonic distortion: Meets EN61000-3-2 Isolation: Meets EN60950 and EN60601 Global Inhibit/Enable: TTL, Logic "1" and Logic "0"; fan off when unit is inhibited Input fuse (internal): uMP1: 16 A/250 V TLAG, uMP4: 10 A / 250 V. (both lines fused) Warranty: 2 years Environmental Specifications Operating temperature: Safety * * * * UL CSA VDE BABT * * * * CB CE CCC BSMI UL60950/UL60601-1 CSA22.2 No. 234 Level 5 EN60950/EN60601-1 Compliance to EN60950/EN60601 BS7002 Certificate and report Mark to LVD Approved Approved -40 to 70 C ambient. Derate each output 2.5% per degree from 50 C to 70 C. ( -20 C start up). Meets full spec after 1/2 load. 10 min warm-up Storage temperature: -40 C to 85 C Electromagnetic susceptibility: Designed to meet EN61000-4; -3, -5, -6, -11 Level 3, Level 4 for -2, -4 Humidity: Operating; non-condensing 10% to 95% RH Vibration: MIL-STD-810E MTBF demonstrated: > 350,000 hours at full load, one uMP4 case + two modules, Telcordia SR-332 calculated MTBF Altitude: Up to 10k feet; derate linear to 50% from 10k-30k feet Embedded Power for Business-Critical Continuity Rev. 01.01.2012 MP Series 2 of 6 Output Factory set point accuracy: 1% Margining: 3 - 7% nominal analog (single output module only) Overall regulation: 0.4% or 30 mV which ever is greater. Ripple: RMS: 0.1% or 10 mV, whichever is greater Pk-Pk: 1.0% or 50 mV, whichever is greater. Bandwidth limited to 20 MHz Dynamic response: < 5% or 250 mV, with 50% step load Recovery time: To within 1% in < 300 sec Reverse voltage protection: 100% of rated output current All outputs disabled when internal temp exceeds safe operating range. Thermal protection: (OTP) Remote sense: Single wire parallel: DC OK: Minimum load: Housekeeping standby: p to 0.5 V total drop (not available on triple output module) U Current share to within 5% of total rated current 5% of nominal. Not required 5 Vdc @ 1.0 A max. present whenever AC input is applied Module inhibit: Output/Output isolation: Logic - output on with low or open. Different logic options available > 1 Megohm, 500 V Vout Full load (A) OVP trip max (V) OCP trip typ (Iout%) SCP trip max (Iout%) Overshoot (max mV) Peak Deviation (max mV) 40 40 40 TBD 5.96 V 6.32 V 130% 130% 130% 160% 160% 160% 150 250 250 250 250 250 36 36 30 6.8 V 8.8 V 9.2 V 130% 130% 130% 160% 160% 160% 250 250 300 250 250 300 25 20 16 12 V 18 V 20 V 130% 130% 130% 160% 160% 160% 300 600 750 300 600 750 13 10 8 18 V 31 V 38 V 130% 130% 130% 160% 160% 160% 600 1200 1500 600 1200 1500 7 5 4 TBD TBD TBD 130% 130% 130% 200% 160% 200% 1400 2400 3000 1400 2400 3000 3V3 Module 0.9 3.3 3.6 5 V Module 3.2 5 6 12 V Module 6 12 15 24 V Module 12 24 30 48 V Module 28 48 60 Case Line-Up Case Max Output MP4 - 4 Slot 400 W - 600 W MP1 - 6 Slot 1000 W - 1200 W Dimensions 256.90.8 x 88.90.5 x 40.00.7 (10.11" x 3.5" x 1.57") 256.90.8 x 1270.5 x 40.00.5 (10.11" x 5" x 1.57") Connections Max Current Amps IEC/Terminal Block 9.91 IEC/Terminal Block 13.87 Output Module Line-Up Output Range (Vdc) 0.9 - 3.6 3.2 - 6.0 6.0 - 15.0 12.0 - 30.0 28.0 - 54.0 5.0 - 28.0 5.0 - 28.0 Max Current (Amps) Max Power (Watts) 40 36 25 13 7 4 4 144 180 240 240 240 96 96 Module Codes Standard Outputs A, B, C, D - 2, 2.2, 3, 3.3 E, F, G, H - 5, 5, 2, 5.5, 6 I, J, K, L, M, N - 8, 10, 11, 12, 14, 15 O, P, Q, R, S - 18, 20, 24, 28, 30 T, U, V, W, X, Y - 28, 30, 33, 36, 42, 48, 54, 60 Dual Output Module. Each output is rated to 96W (192 Watts total). Wide range is adjustable. Embedded Power for Business-Critical Continuity Rev. 01.01.2012 MP Series 3 of 6 Ordering Info Case Size MPXY - S2E - DER - DLL - Input Type where Y = T = Terminal Block C = IEC Connector, C14 B = IEC Connector, C16 - 00 Case Option Codes First digit 0 - F = Parallel Code Module Codes S2 = 200 W Single O/P (1 slot) D = 96 W/96 W Dual O/P Common Ground (1 slot) I = 96 W/96 W Dual O/P Isolated Ground (1 slot) Case Size Single - Phase Input where X = 4 = 1.57" x 3.5" x 10"; 400 W - 600 W, 4 Slots 1 = 1.57" x 5" x 10"; 1000 W - 1200 W, 6 Slots Software Code Case Option Codes Module/Voltage/Option Codes Hardware Code - A Factory assigned for modified standards ### Factory assigned for modified standards Second digit 0 = No Options 1 = Reverse Air 3 = Global Enable 5 = Opt 1 + Opt 3 Voltage Codes: See Voltage Code Table Parallel Codes Code Slots in Parallel Code Slots in Parallel Code Slots in Parallel Code 1 1&2 6 1,2&3 B 1,2&3; 4&5 0 2 3 4 2&3 3&4 4&5 7 8 9 1,2,3&4 1,2,3,4&5 1,2,3,4,5&6 C D E 1,2,3&4; 5&6 1&2; 3&4; 5&6 1,2&3; 4,5&6 5 5&6 A 1&2; 3&4 F 2&3; 4&5 Slots in Parallel no module in parallel Derating Curves - MP1 Voltage Codes Standard Output Ratings Standard Fan(12 V/24 V/48 V) Module Output Voltage Code Single Output ONE SLOT 240 Watts Max Dual Output ONE SLOT 192 Watts Max Module Identification S2 D = Dual Common Ground I = Dual Isolated Ground 200 VAC 264 VAC 1100 Output Current V1 40.0 40.0 40.0 40.0 36.0 34.0 32.0 30.0 25.0 24.0 22.0 20.0 17.0 16.0 13.0 12.0 10.0 8.6 8.0 7 6.7 5.7 5.0 4.4 4.0 Output Current V1 V2 N/A N/A N/A 4.0* 4.0* 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.4 3.4 N/A N/A N/A N/A N/A N/A N/A Output Power 2.0 V 2.2 V 3.0 V 3.3 V 5.0 V 5.2 V 5.5 V 6.0 V 8.0 V 10.0 V 11.0 V 12.0 V 14.0 V 15.0 V 18.0 V 20.0 V 24.0 V 28.0 V 30.0 V 33.0 V 36.0 V 42.0 V 48.0 V 54.0 V 60.0 V 110 VAC 1200 900 800 700 600 500 400 0 10 20 30 40 Temperature 50 60 70 Reverse FAN(12 V/24 V/48V) 85 VAC 100 VAC 110 VAC 200 VAC 264 VAC 1200 1100 1000 Output Power A B C D E F G H I J K L M N O P Q R S T U V W X Y * For "I" codes only Volts 100 VAC 1000 Output Module Line-Up Code 85 VAC 900 800 700 600 500 400 0 10 20 30 40 Temperature 50 60 70 Embedded Power for Business-Critical Continuity S2 Module MP4 (AC input on opposite side) S L O T S L O T S L O T S L O T 4 3 2 1 MP4 =4 available slots DC Output Control & Signals (Single output) J2 J1 Input 85-264 Vac 200-264 Vac 400 W max. 600 W max. 240 W MP1 (AC input on opposite side) S L O T 6 S L O T 5 S L O T 4 S L O T 3 S L O T 1 S L O T 2 Rev. 01.01.2012 MP Series 4 of 6 J2 1.00.25 V ADJ 5.30.5 J1 Pin 1 2 3 4 5 6 7 8 9 10 29.80.2 37.50.3 32.50.3 36.50.3 36.50.3 V+ Function No connection No connection Current share Module inhibit return Module ISO inhibit SCOM -RMT sense Margin Remote margin / V prog. +RMT sense V- MP1 = 6 available slots Input 85-264 Vac 1000 W max. CAPS HEIGHT 4.50.3 12.5 MAX 3.0 MAX 200-264 Vac 1200 W max. 0.8 - 1.5 1.60.16 Pin Connectors Figure 1. AC Input AC Input Pin 1 2 3 IEC Connector 9 10 Mates with Landwin 2050S1000 Housing 2053T011V Pin or JST PHDR-10VS Housing JST SPHD-002T-P0.5 (28-24) JST SPHD-001T-P0.5 (26-22) Connector Kit Part No.: 70-841-023 DC Output Control & Signals (Dual output) Function Input AC OK - "emitter" Input AC OK - "collector" Global DC OK - "emitter" Global DC OK - "collector" Spare Global inhibit/optional enable logic "1" Global inhibit/optional enable logic "0" Global inhibit/optional enable return +5 VSB housekeeping V1 ADJ 10 +5 VSB housekeeping return J2 Pin 1 2 3 4 5 6 7 8 9 10 PFC Input Connector (control & signals) Pin 1 2 3 4 5 6 7 8 9 Figure 2. Connector J1 & J2 1 2 J1 Dual Module V2 ADJ I C Bus Output Connector Pin 1 2 3 4 5 6 7 8 9 10 Function 5 Vcc bus Serial data signal (SDA) Secondary return (COM) Serial clock signal (SCL) Address bit 2 (A2) No connection Address bit 1 (A1) No connection Address bit 0 (A0) No connection Function -RMT sense V2 +RMT sense V2 No connection Module inhibit rtn Module ISO inhibit SCOM -RMT sense V1 No connection No connection +RMT sense V1 122.0 0.5 0 ~ 0.1 mm (2X) 2 37.8 0.3 Terminal Block PE N L Function AC neutral AC line (hot) Chassis (earth) ground 9 10 1 2 130.01.5 V1+ COM V2+ COM 130.0 ref 12.5 MAX 1.6 0.15 2.5 MAX Embedded Power for Business-Critical Continuity MP Series MP4 (400/600 Watts Max) Case Size: MP4: 10.11" x 3.5" x 1.57" (256.9mm x 88.9mm x 40.0mm) Weight: MP4 Case: 1.96 lbs * Single O/P: 0.22 lb. * Dual O/P: 0.16 lb. * Blank: 0.06 lb. Rev. 01.01.2012 MP Series 5 of 6 Embedded Power for Business-Critical Continuity MP Series MP1 (1000/1200 Watts Max) Case Size: MP1: 10.11" x 5" x 1.57" (256.9mm x 127mm x 40.0mm) Weight: MP1 Case: 2.78 lbs * Single O/P: 0.22 lb. Americas * Dual O/P: 0.16 lb. * Blank: 0.06 lb. 5810 Van Allen Way Rev. 01.01.2012 MP Series 6 of 6 Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698 Europe (UK) Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355 Asia (HK) 14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888 For global contact, visit: www.Emerson.com/EmbeddedPower techsupport.embeddedpower @emerson.com While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. (c)2011 Emerson Electric Co.