[Ui] rated insulation voltage 600V (pollution degree 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage EN 60947-1 6kV
[Ie] rated operational current 3A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Electrical durability 1000000cycles, AC-15, 2A at 230 V, operating rate <3600cyc/h, load factor: 0.5 conforming to EN/
IEC 60947-5-1 appendix C
1000000cycles, AC-15, 3A at 120 V, operating rate <3600cyc/h, load factor: 0.5 conforming to EN/
IEC 60947-5-1 appendix C
1000000cycles, AC-15, 4A at 24 V, operating rate <3600cyc/h, load factor: 0.5 conforming to EN/
IEC 60947-5-1 appendix C
1000000cycles, DC-13, 0.2A at 110 V, operating rate <3600cyc/h, load factor: 0.5 conforming to
EN/IEC 60947-5-1 appendix C
1000000cycles, DC-13, 0.5A at 24 V, operating rate <3600cyc/h, load factor: 0.5 conforming to EN/
IEC 60947-5-1 appendix C
Electrical reliability Λ < 5 x 10exp(-8), 1mA in clean environment conforming to EN/IEC 60947-5-4
Mounting of block Front mounting
Electrical composition code C1 (quantity <= 9)
C2 (quantity <= 7)
C3 (quantity <= 6)
C4 (quantity <= 4)
C5 (quantity <= 5)
C6 (quantity <= 3)
C7 (quantity <= 4)
C8 (quantity <= 2)
C9 (quantity <= 3)
C12 (quantity <= 6)
M1 (quantity <= 6)
M2 (quantity <= 4)
M3 (quantity <= 4)
M5 (quantity <= 2)
M6 (quantity <= 2)
M7 (quantity <= 6)
M8 (quantity <= 4)
M9 (quantity <= 2)
SF1 (quantity <= 3)
SF2 (quantity <= 2)
MF1 (quantity <= 2)
MF2 (quantity <= 2)
C10 (quantity <= 2)
M4 (quantity <= 2)
C13 (quantity <= 1)
Environment
Protective treatment TH
Ambient air temperature for storage -40…70°C
Ambient air temperature for operation -40…70°C
Standards UL 508
EN/IEC 60947-5-1
CSA C22.2 No 14
EN/IEC 60947-5-4
EN/IEC 60947-1
JIS C8201-5-1
JIS C8201-1
Product certifications CCC
DNV
GL
UL
CSA
LROS (Lloyds register of shipping)
RINA
BV
GOST
Vibration resistance 5 gn (f= 2…500Hz) conforming to IEC 60068-2-6
Shock resistance 30 gn (duration = 18ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11ms) for half sine wave acceleration conforming to IEC 60068-2-27