48 x 24mm PID temperature controller with autotune and
remote second setpoint selection option
■Multi-sensor thermocouple and Pt100 input model
■4-20mA input model
■Relay, voltage pulse, analogue 4-20mA or 0-10VDC output
■12-function temperature alarm with variable delayed action
■Alarm hysteresis is adjustable from 0.0 to 100.0˚C or ˚F
■Loop break alarm to detect insufficient temperature rise
within a set time
■Alarm output energised/de-energised selection
■Programmable ramp-rate control
■Autotune threshold adjustment
■3 levels of keypad security locking
■Adjustable setpoint limits
■% output power display
■Adjustable PV filter to slow down response if required
■Fully adjustable output power limit
■RS232C or RS485 communications option
■IP54 protection
48 x 24mm 4-Digit Display PID
Temperature Controller FCL
Options and ordering codes
Specifications
FCL-13A R–/
M SM 100-240VAC
48 x 24mm PID temperature
controller with one alarm
Relay output R
Signal voltage for SSR S
Current output A
Analogue voltage 0-10VDC
100-240VAC supply
24VAC/DC supply
Options
With RS232C
T/C+ Pt100 input
V
M
C
Remote 2nd setpoint
SM
With RS485
C5
Without options
–
4-20mA input APlease note: Option SM cannot be
supplied simultaneously with options C or C5
Input type
K-thermocouple J-thermocouple E-thermocouple PL-II thermocouple N-thermocouple DIN Pt100 RTD DIN Pt100 RTD J Pt100 RTD J Pt100 RTD
Rated scale
0 to 1370˚C 0 to 1000˚C 0 to 800˚C 0 to 1390˚C 0 to 1300˚C –199.9 to 850.0˚C –200 to 850˚C –199.9 to 500.0˚C –200 to 500˚C
Sensor resistance 100Ωor less 10Ωper wire or less
Accuracy ±0.3% of full scale ± 1 digit ±0.2% of full scale ±1 digit
Display 4-digit red LED, 8mm high
Control action User-selectable: PID with autotune, PD, On/Off
Proportional band 0 to rated scale maximum value. Factory set to 10˚C (20˚F)
Integral time 1 to 3600 secs (off when set to 0), Factory set to 200 secs
Derivative time 1 to 3600 secs (off when set to 0), Factory set to 50 secs
Anti-reset windup Automatic in PID modes
Reset range in PD action Within the proportional band
Hysteresis in On/Off action 0.1 to 100.0˚C (˚F)
Proportional cycle 1 to 120 seconds, Relay output type: Factory set to 30 secs; Signal voltage type: Factory set to 3 secs
Output: relay types SPNO: 250V, 3A resistive load; 250V, 1A inductive load, cos ø = 0.4
Output: signal voltage types 12VDC +2VDC/–0VDC 40mA, short-circuit protected
Output: analogue types 4 to 20mA DC - max. load resistance 500Ω, 0-10VDC – output impedance 500Ω
Temperature alarm Open collector output 24VDC 0.1A maximum
Loop break alarm time 0 to 200 minutes selectable
Loop break alarm temperature 0 to 100˚C selectable (˚F)
Delayed action alarm time 0 to 9999 secs
Rising/falling rate setting 0 to 9999˚C/minute selectable
Temperature alarms action ON/OFF action, hysteresis 0.1 to 100.0˚C (˚F), Factory set to 1.0˚C (˚F)
High limit alarm (1) Deviation from SV: scale span value to + scale span value
Low limit alarm (1) Deviation from SV: scale span value to + scale span value
High/low limits alarm (1) Deviation from SV: 1 to scale span value
High/low limit range alarm (1) Deviation from SV: 1 to scale span value
Absolute value (process) alarm (1) Input range minimum value to input range maximum value
Absolute (process) reverse alarm (1) Input range minimum value to input range maximum value
Sensor correction (input shift) –100.0 to 100.0˚C (˚F), Factory set to 0.0˚C (˚F)
Sensor break protection Upscale: Control output off
Supply voltage 85 to 264VAC 50/60Hz (100-240 VAC+10%–15%); 20 to 28 VDC/AC 50/60Hz
Power consumption 15VA approx.
Ambient temperature 0 to 50˚C
Ambient humidity 35 to 85% r.h. (non-condensing)
Insulation resistance (2) >10MΩat 500VDC
Mounting Flush
Front panel Membrane sheet keyboard, IP54
Weight 100g approx
Case material Light grey polycarbonate, flame retardant and self-extinguishing
(1) All alarm types can be programmed to operate with or without ‘standby’ function (2) Do not apply voltage between sensor input terminals and control output terminals of FCL-13A-A, FCL-13A-S and FCL-13A-V models
Also available: Heater burnout alarm – cannot be supplied simultaneously with SM, C or C5, or with 4-20mA or 0-10V output models