Du line Master Channel Generator Types G 3800 0016, G 3800 1016 (R) Fieldbus Installationbus * Programmable channel generator * Automatic data exchange between multiple networked Master Generators, allowing systems with up to 4096 I/O points * Option for built-in GSM Modem for monitoring and control via SMS * User-friendly configuration via Windows 98/2000/NT/XP software * Real-time, timer and logic functions * Analog set-point control and monitoring * Light and Rollerblind control functions * Alarm Monitoring * Option for Radio controlled clock for high real time accuracy * 2 x RS232 ports for configuration and Dupline data read/write * 1 x RS485 port for networking of up to 32 Master Generators * Modbus-RTU protocol * Built-in software driver for external radio modem * 4 digital inputs / 4 digital outputs on-board * H8-housing for DIN-rail mounting (EN50022) * AC or DC power supply Product Description Programmable channel generator with built-in dedicated intelligent functions for light and roller blind control, alarm monitoring and analog setpoint control. In addition to that, there is realtime-, timerand logic- functions. Programming is easily performed through Windows-based configuration software. An optional built-in GSM modem can be used for monitoring and control of Dupline signals via SMS. Up to 32 Master generators can be networked Ordering Key as slaves in a RS485 network using the Modbus protocol. The unit has 4 digital inputs and 4 digital outputs onboard, and it is possible to create links to other Dupline networks via external Radio Modem. The G3800X016 is different from the G3800X015 in that it has the capability to perform automatic data exchange with up to 32 other G3800X016's in a RS485 network, enabling up to 4096 I/O-points in one system. G 3800 1016 230 Type: Dupline(R) H8-housing GSM phone Master channel generator Supply Type Selection Supply Ordering no. Ordering no. w. GSM telephone 115/230 VAC 10-30 VDC G 3800 0016 230 G 3800 0016 800 G 3800 1016 230 G 3800 1016 800 Input/Output Specifications Serial Port COM 1 COM 2 Data format COM 1, COM 2 Pin assignment TxD RxD GND Dielectric voltage Com.port - Dupline(R) Protocol RS 485 Termination Fs-B Fs-A + (B) - (A) GND V+ Protocol Dupline(R) Output Output voltage Current Short-circuit protection RS 232 115 kBaud 9600 Baud, adjustable 8 bit No parity, 1 stop bit 9-pole female SUB-D Pin 2 Pin 3 Pin 5 2 kVAC (rms) Modbus-RTU Pin 27 When in use, connect to pin 31 Pin 28 When in use, connect to pin 30 Pin 29 When in use, connect to pin 31 Pin 30 Pin 31 Pin 32 Pin 33*) Modbus-RTU Dupline(R) carrier 8.2 V < 130 mA Yes Sequence time 32 channels / 128 channels Digital outputs Function Output voltage VDD Output current Output voltage drop Off-state leakage current Short-circuit protection Built-in protective diodes Dielectric voltage Output - Dupline(R) Output - Input Inductive loads Inputs Digital Voltage Current Dielectric voltage Input - Dupline (R) GSM Modem Siemens cellular engine Dual Band Output power Antenna connector *) 38.6 ms / 132.3 ms 4 PNP transistors Programmable 35 VDC 100 mA 2V 100 A None None 4 kVAC (rms) 200 V External noise suppression required 6 - 30 VDC ON > 5.5 V; OFF < 1.5 V 6 mA 4 kVAC TC35 EGSM900 and GSM1800 Class 4 (2 W) EGSM900 Class 1 (1 W) GSM1800 FME V+ and GND may be used as supply for digital I/O's, if RS 485 is not used. Specifications are subject to change without notice (21.08.2006) Dupline(R) is a registered trademark. A product of the CARLO GAVAZZI Group 1 Du line G 3800 0016, G 3800 1016 (R) Fieldbus Supply Specifications (cont.) Supply Specifications Power supply AC-Types Rated operational voltage through term. 21 & 24 jumper term. 22 & 23 Power on term. 21 & 23 Neutral on term. 22 & 24 Frequency Rated operational power Power dissipation G38000016 G38001016 Rated impulse withstand voltage 230 V 115 V Dielectric voltage Supply - Dupline(R) Supply - Output Supply - Input Supply - Com. ports Heat dissipation Overvoltage cat. III (IEC 60664) Inrush current Rated impulse withstand volt. Dielectric voltage Supply - Dupline(R) Supply - Output 230 VAC 15% (IEC 60038) 115 VAC 15% (IEC 60038) 45 to 65 Hz Typ. 7 VA/3 W 4 kV 2.5 kV 4 kVAC (rms) 4 kVAC (rms) 4 kVAC (rms) 4 kVAC (rms) 4W Overvoltage cat. III (IEC 60664) 10 to 30 VDC - 50 Hz for synchronizing the clock - in case of voltage break (AC) the log will automatically update itself until 10 mSec before the loss of current Yes 6W Reverse polarity protection Rated operational power Power dissipation G38000016 G38001016 1A 800 V 500 V 200 V General Specifications 6W 7W Power supply DC-Types Rated operational voltage through term. 21 & 22 DC supply terminal 24 and 25 Installationbus 6W 7W Real-time clock Accuracy Internal back-up time Power ON delay Indication for Supply ON ON Line COM 1 COM 2 RS 485 GSM Environment Degree of protection Pollution degree Operating temperature Storage temperature Humidity (non-condensing) Mechanical resistance Shock Vibration Dimensions Material (see "Technical Information") Weight Better than 1 minute/month Typ. 48 hours < 2.5 s LED, green LED, yellow LED, red LED, red LED, red LED, red IP 20 3 (IEC 60664) 0 to +50C (+32 to +122F) -20 to +85C (-4 to +185F) 20 to 80% RH 15 G (11 ms) 2 G (6 to 55 Hz) H8-housing 640 g Wiring Diagrams DUPLINE 1 2 6-30 VDC D+ D- 3 1 4 5 6 2 V+ 3 7 8 9 10 1 2 3 4 V+ VIN 4 11 G 3800 0016 230 V- 12 13 14 15 16 0,1 A 30 V 1 2 3 4 12 VA 33 V+ 34 Inputs 21 P 22 115V 23 N P 24 115V 25 26 27 T 28 Outputs 29 30 Fs-B Fs-A (B) N 31 (A) 32 V- RS 485 Out Supply 6-30 VDC V+ DUPLINE 1 2 + - 21 22 D+ D- 3 4 1 5 6 3 8 9 10 1 2 3 4 IN 11 Radio Contr. Clock G 3800 0016 800 V- 12 13 14 15 16 1 2 3 4 Inputs 23 24 25 26 27 Supply 10-265 VAC 10-30 VDC AC monit. input 36 V+ V- 4 7 T 2 2 35 V+ S-in V - Outputs 28 29 30 Fs-B Fs-A (B) 31 (A) RS 485 32 V- 33 V+ Out 34 35 36 V+ S-in V - Radio Contr. Clock Specifications are subject to change without notice (21.08.2006) Dupline(R) is a registered trademark. A product of the CARLO GAVAZZI Group Du line G 3800 0016, G 3800 1016 (R) Fieldbus Installationbus Mode of Operation Intelligent functions The G3890x016 Master Generator is a programmable channel generator which is particularly well suited for building automation applications due to the dedicated intelligent functions for lighting control, rollerblind control, temperature control and alarm monitoring. In addition to that the unit can be configured to perform real-time, logic and timer functions. The windowsbased configuration software is extremely easy to use due to the pre-programmed functions. Master Generator configuration The Master Generator is as default configured to operate as a standard channel generator without intelligent functions. In order to make use of the intelligent functions the Master Generator must be configured by means of the user-friendly windows-based configuration software. This is included in the package and has to be installed on a Win 95/98/2000/NT/XP PC. When the configuration is completed the configuration is downloaded into the Master Generator via COM1 (RS232 port). The configuration can be saved on a file and it is also possible to upload the configuration from a Master Generator. GSM Modem Option The G38001016 Master Generator has a built-in GSM Modem which enables monitoring and control of Dupline signals via SMS messages to/from mobile GSM telephones. There are 3 different ways to use SMS messaging: * The Master Generator can be programmed to send out eventbased SMS messages. The event can be a channel switching ON or OFF, or it can be an analog signal crossing a setpoint. * Requests for status of digital or analog data can be sent and answered via SMS messages * Status of digital channels can be controlled by sending commands via SMS messages In order to make use of the GSM modem, the following is required: * A SIM-card with the pin-code 9090 needs to be inserted into the slot in the front of G38001016. The SIM-card must be a 3V type. * A GSM antenna needs to be connected to the FME connector on G38001016. If the unit is installed in a metal enclosure, the antenna must be installed outside the enclosure and connected to the Master Generator via a cable (an antenna of this type is available as accessory). An LED in the front of G38001016 indicates the status of the GSM modem. By emitting different blink patterns, the LED indicates "connecting", "SIMcard missing", "No network found", "No response from modem", "SMS sent" and "SMS received". Radio Controlled Clock Option It is possible to equip the G3800x016 with an external antenna for radio-controlled clock in order to achieve high timing accuracy in connection with real-time functions and event time stamps. When the antenna ANT2 is used, the G3800x016 will receive accurate timing signals from the DCF77 transmitter located in Frankfurt a.M., Germany. The antenna outputs the demodulated signals to the Master Generator via an open collector driver. The DCF77 transmitter covers all of Central Europe since the transmission radius is at least 1000 km. For longer distance the use of ANT2 depends on receiver conditions. ANT2 connects to the G3800x016 terminals. RS232 ports The Master Generator is provided with two RS232 ports (COM1 and COM2) which both can be used by PC's/PLC's for read/write of Dupline data using the Modbus-RTU protocol. COM1 is also used for download and upload of configuration files (created by the Master Generator configuration software) and for firmware upgrades. If the option for an external radio modem is desired, it needs to be connected to COM2. COM1 has a fixed baudrate of 115 kBaud, while the baudrate of COM2 is adjustable. RS485 port The RS485 port enables networking of up to 32 Master Generators with or without automatic data exchange. This enables control and monitoring of up to 4096 data points. If desired, it is also possible to use Ethernet instead of RS485. In that case each Master Generator must be equipped with a converter. A Modbus Device Address needs to be assigned to each Master Generator during configuration. In a network with automatic data exchange, one Master Generator is configured as RS485 Master, and will thus synchronize a continual automatic data exchange between all the Master Generators. When programming the individual Controllers it is then possible to make references to signals in other Dupline networks. For example the wind speed value measured by a sensor in one Dupline network, can be used in the roller blind control function in the other Dupline networks. It is also possible to make e.g. "all lights OFF" functions for a big building by activating a single pushbutton. A PC or PLC, connected to one of the COM-ports of the G3800X016 operating as RS485 Master, gets access to all 4096 data points using the Modbus protocol. Also, using the PC makes it possible to change the configuration in any of the Master Generators in the network. In a network without automatic data exchange, a PC or PLC need to be RS485 Master and all the Master Generators will operate as Modbus-RTU slaves. This makes it possible for the PC or PLC to read/write data from any of the 32 Master Generators. See following RS485 networking diagram for both operating modes. Modbus-RTU protocol Using the Modbus-RTU commands 2 and 3 through COM1, COM2 or RS485 makes it possible to read any type of Dupline data (digital, analink, multiplexed analog or counter data). The status of digital and multiplexed analog data and reset of counter can be controlled via the commands 5, 6 and 16. See manual for memory map information. Software The Dupline Data Access software package (type no. DUPDATACC) has been developed specifically for the Master Generator. It contains two software tools that provide easy access from a PC to Dupline digital, analog and counter data via one of the RS232 or RS485 ports. The DDE-driver provides a Dynamic Data Exchange interface, which can be used from Specifications are subject to change without notice (21.08.2006) Dupline(R) is a registered trademark. A product of the CARLO GAVAZZI Group applications that support client side DDE such as Microsoft EXCEL. Getting Dupline data into an EXCEL spreadsheet is a simple copy-and-paste operation. The Dupline ActiveX driver provides an ActiveX interface, which is a Microsoft standard for communication between two products. The Dupline ActiveX driver can be used from any development tool that supports client side ActiveX such as Microsoft Visual Basic, Delphi and Borland C++ builder. The Dupline Data Access package can be used on single Master Generators as well as Master Generator networks. Radio Modem driver The Master Generator has a built-in driver for control of an external Radio Modem, which can be used to create wireless links where no cable is available in parts of an installation. One Master Generator must be defined as the central MGEN and up to 32 Master Generators can be defined as remote MGEN's. The central MGEN is continuously polling and updating the Dupline data from all remote MGEN's via the radio modem network, and in this way it makes the entire system operate as one big Dupline network. Apart from increased reaction time (depending on the number of remote MGEN's), the system will operate as if it was one Master Generator connected to all the I/O-modules with cable. The Master Generator supports the Radio Modem type 2ASxE and all 3AS types from the Finnish manufacturer SATEL (www.satel.fi). Find below an application diagram for the Radio Modem option. Note: Analink modules cannot be used with Radio Modems. On-board I/O The Master Generator has 4 digital inputs and 4 digital outputs on-board. These have been implemented to reduce the cost of remote stations with only a few signals (e.g. in connection with an SMS alarm system or radio modem remote stations). The onboard I/O's are used via the logic functions of the Master Generator, where they can be assigned to specific channel addresses. 3 Du line G 3800 0016, G 3800 1016 (R) Fieldbus Pin Assignment, COM1, COM2 5 1 9 6 Pin Signal 2 3 5 TxD RxD Signal Ground Installationbus RS 232 Cable 9-pin male to controller 2 3 5 9-pin female to PC 2 3 5 9-pin male to controller 2 3 5 15-pin female to radio modem 11 9 7 Master Generator Network Without automatic data exchange PC Interface #1 Dupline #1 Interface #2 Dupline #2 I/O modules * Digital * Analogue * Counter I/O modules * Digital * Analogue * Counter Modbus/RS485 With automatic data exchange PC Modbus/RS232 MGEN Master #32 Dupline #32 MGEN Slave #1 Dupline #1 MGEN Slave #2 Modbus/RS485 Dupline #2 4 Specifications are subject to change without notice (21.08.2006) Dupline(R) is a registered trademark. A product of the CARLO GAVAZZI Group Du line (R) G 3800 0016, G 3800 1016 Fieldbus Installationbus Dimensions (mm) Radio Modem Application H8-housing Central MGEN RS232 Remote MGEN #1 RS232 Remote MGEN #2 RS232 Scope of Supply 1 x Master Channel Generator 1 x User manual 1 x RS 232 cable 1 x Configuration software G 3800 x016 xxx MAN G 3800 0016 ENG RS 232-9 M/9 F SW G 38xx16 Accessories Dupline Data Access Software DUPDATACC GSM Antenna 900 MHz ANT1 Antenna for Radio controlled clock ANT2 ANT1 ANT2 Specifications are subject to change without notice (21.08.2006) Dupline(R) is a registered trademark. A product of the CARLO GAVAZZI Group 5