Page 1/3
28November2018/version 6 LEM International SA
Chemin des Aulx 8
1228 PLAN-LES-OUATES Switzerland
www.lem.com
LEM reserves the right to carry out modications on its transducers,
in order to improve them, without prior notice
N° 97.09.34.013.0
IP N = 100 A
Features
Closed loop (compensated)
current transducer using the Hall
e󰀨ect
Insulating plastic case recognized
according to UL 94-V0.
Special features
IP M = 0 .. ±160 A
NP/NS = 1 : 1000
TA =−25°C...+70°C.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and
servo motor drives
Static converters for DC motor
drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application domain
Industrial.
Current Transducer LA 100-P/SP13
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic separation between the primary circuit and the secondary
circuit.
Electrical data
IP N Primary nominal RMS current 100 A
IP M Primary current, measuring range 0 ... ±160 A
RM Measuringresistance@70°C
RM min RM max
with ±12 V @ ±100 A max 10 65
@ ±160 A max 10 30
with±15V @±100Amax 40 95
@ ±160 A max 40 50
IS N Secondary nominal RMS current 100 mA
NP/NS Turns ratio 1 : 1000
UC Supplyvoltage(±5%) ±12...15 V
IC Current consumption (±2) 10 (@±15V)+IS mA
ε Error @ IP N, TA=25°C @±15V(±5%) ±0.45 %
Accuracy - Dynamic performance data
@±12...15V(±5%) ±0.70 %
εL Linearityerror <0.15 %
Typ Max
IO O󰀨setcurrent@IP = 0, TA=25°C ±0.2 mA
IO M Magnetico󰀨setcurrent1) @ IP=0andspeciedRM,
after an overload of 3 × IP N ±0.3 mA
IOT Temperature variation of IO −25°C...+70°C ±0.1 ±0.5 mA
tD 10 Delaytime@10%ofIP N <500 ns
tD 90 Delaytimeto90%ofIP N
2) < 1 µs
BW Frequencybandwidth(−1dB) DC...200 kHz
General data
TA Ambientoperatingtemperature −25...+70 °C
TS Ambientstoragetemperature −40...+90 °C
RS Resistance of secondary winding @ TA=70°C 25
m Mass 18 g
Standards EN50178:1997
UL508:2010
Notes: 1)Resultofthecoerciveeldofthemagneticcircuit
2) For a di/dt = 100 A/µs.
UC
IS
IP
UC
RM
dCl dCp
Page 2/3
28November2018/version 6 LEM International SA
Chemin des Aulx 8
1228 PLAN-LES-OUATES Switzerland
www.lem.com
LEM reserves the right to carry out modications on its transducers,
in order to improve them, without prior notice
Current Transducer LA 100-P/SP13
Insulation coordination
Ud RMSvoltageforACinsulationtest,50Hz/1min 2.5 kV
UNi Impulsewithstandvoltage1.2/50µs 4.5 kV
Min
dCp Creepage distance 1) 3.8 mm
dCI Clearance
2) 3.8 mm
CTI Comparativetrackingindex(groupI) 600
Notes: 1) Distance between hole busbar and winding
2) Direct distance between hole busbar and winding.
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
Over voltage category OV 3
Pollution degree PD2
Non-uniformeld
Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturers
operating instructions.
Caution,riskofelectricalshock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
EN 50178 IEC 61010-1
dCp, dCI, UNi
Rated insulation voltage
Nominal voltage
Basic insulation 300 V 300 V
Reinforced insulation 150V 150V
Page 3/3
28November2018/version 6 LEM International SA
Chemin des Aulx 8
1228 PLAN-LES-OUATES Switzerland
www.lem.com
LEM reserves the right to carry out modications on its transducers,
in order to improve them, without prior notice
Dimensions LA 100-P/SP13 (in mm)
Mechanical characteristics
General tolerance ±0.2 mm
Primarythrough-hole 12.7×7mm
Fastening & connection of secondary 3 pins
0.6×0.7mm
Recommended PCB hole 1.2 mm
Remarks
IS is positive when IPowsinthedirectionofthearrow.
Temperature of the primary conductor should not exceed
100°C.
Installation of the transducer must be done unless
otherwisespeciedonthedatasheet,accordingtoLEM
Transducer Generic Mounting Rules. Please refer to
LEMdocumentN°ANE120504availableonourWebsite:
https://www.lem.com/en/le/3137/download/.
Dynamic performances (di/dt and response time) are best
withasinglebarcompletelyllingtheprimaryhole.
In order to achieve the best magnetic coupling, the
primary windings have to be wound over the top edge of
the device.
UC
IS
IP
UC
RM
dCl dCp
Connection