https://www.phoenixcontact.com/us/products/2700973
09/03/2014Page1/6
Controller-ILC 131 ETH-2700973
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
The controller enables integration of I/O signals from MODBUS periphery devices into the control program via
MODBUS/TCP. Programming takes place with PC Worx Express or PC Worx (IEC 61131-3).
Product description
With the ILC 131 ETH, the highly modular Inline controller range from Phoenix Contact has been extended to include a powerful high-performance
controller. This controller can be used to extend the possible field of application of Inline controllers right down to smaller applications. With direct
integration into the Inline automation system, the high-performance controller is highly modular and can be adapted to the relevant application
requirements. Its integrated Ethernet interface enables parameterization and programming using PC Worx automation software according to IEC 61131,
and it can also exchange data with OPC servers simultaneously and communicate with TCP/IP-compatible devices.
The Inline controller range covers a wide performance range. From entry-level versions to high-end controllers, users can find the right controller for
their application. Within the product portfolio, users can choose between controllers with different computing capacities, with or without PROFINET
controllers, and with or without GL approval. 
Product Features
Numerous protocols supported such as: HTTP, FTP, SNTP, SNMP, SMTP, SQL, MySQL, etc.
Free engineering with PC Worx Express (IEC 61131-3)
Complete fieldbus master (4096 I/O points)
Integrated web server for visualization with WebVisit
FTP server
Flash file system
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 370.0 GRM
Custom tariff number 85371091
Country of origin Germany
Technical data
Note
https://www.phoenixcontact.com/us/products/2700973
09/03/2014Page2/6
Controller-ILC 131 ETH-2700973
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 80 mm
Height 119.8 mm
Depth 71.5 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above mean sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above mean sea level)
Shock 25g, Criterion 1, according to IEC 60068-2-27
Vibration (operation) 5g
Control system
Programming tool PC Worx/PC Worx Express
Diagnostics tool DIAG+
Configuration tool Config+ Version 1.01 or later
Mechanical design
Weight 285 g
Data interfaces
Interface INTERBUS local bus (master)
Connection method Inline data jumper
Transmission speed 500 kBaud / 2 MBaud umschaltbar
Interface Parameterization/operation/diagnostics
Connection method RS-232-C, 6-pos. MINI-DIN socket (PS/2), Ethernet 10/100 (RJ45)
Transmission speed max. 115,2 kBit/s
Interface Ethernet 10Base-T/100Base-TX
Connection method RJ45 socket
Transmission speed 10/100 MBit/s
PROFINET IO
Device function PROFINET device
Power supply
https://www.phoenixcontact.com/us/products/2700973
09/03/2014Page3/6
Controller-ILC 131 ETH-2700973
Technical data
Power supply
Typical current consumption 210 mA
Max. current consumption 870 mA (370 mA communications power + 500 mA analog voltage supply)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC
Residual ripple ± 5 %
Fieldbus function
Amount of process data max. 2048 Bit (INTERBUS)
max. 8192 Bit (internal Modbus Client)
Number of supported devices max. 63
Number of local bus devices that can be connected max. 63 (observe current consumption)
Number of devices with parameter channel max. 8
Module classification INTERBUS master
Direct I/Os
Output name Digital outputs
Number of outputs 4
Connection method 2, 3, 4-wire
Maximum output current per channel 500 mA
Input name Digital inputs
Number of inputs 8
Connection method Inline potential distributor
Description of the input EN 61131-2 type 1 NPN/PNP
IEC61131 runtime system
Programming tool PC Worx/PC Worx Express
Processing speed 1.7 ms (1 K mix instructions)
90 µs (1 K bit instructions)
Program memory 192 kByte (16 K instructions (IL))
Mass storage 192 kByte
Retentive mass storage 8 kByte (NVRAM)
Number of data blocks depends on mass storage
Number of timers, counters depends on mass storage
Number of control tasks 8
Realtime clock Yes
https://www.phoenixcontact.com/us/products/2700973
09/03/2014Page4/6
Controller-ILC 131 ETH-2700973
Classifications
eCl@ss
eCl@ss 4.0 27250203
eCl@ss 4.1 27240601
eCl@ss 5.0 27242215
eCl@ss 5.1 27242207
eCl@ss 6.0 27242207
eCl@ss 7.0 27242207
eCl@ss 8.0 27242207
ETIM
ETIM 3.0 EC000236
ETIM 4.0 EC000236
ETIM 5.0 EC000236
UNSPSC
UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 43172018
UNSPSC 12.01 43201404
UNSPSC 13.2 43201404
Approvals
Approvals
Approvals
UL Listed / cUL Listed / UL Listed / cUL Listed / DNV / RINA / GL / GL-SW / BSH / LR / GL / DNV / RINA / GL-SW / BSH / BV / cULus Listed / GL
Ex Approvals
ATEX / ATEX / UL Listed / cUL Listed / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
https://www.phoenixcontact.com/us/products/2700973
09/03/2014Page5/6
Controller-ILC 131 ETH-2700973
Approvals
UL Listed
cUL Listed
UL Listed
cUL Listed
DNV
RINA
GL
GL-SW
BSH
LR
GL
DNV
RINA
GL-SW
https://www.phoenixcontact.com/us/products/2700973
09/03/2014Page6/6
Controller-ILC 131 ETH-2700973
Approvals
BSH
BV
cULus Listed
GL
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com