1-, 2- and 3-pole — Class CC, Midget, 10x38mm
Description and specifications ...............2-3
Available fuses ............................. 3
Recommended lockout devices ............... 3
Dimensions ............................... 3
Motor sizing table .......................... 4
1-, 2- and 3-pole — Class CF
Description and specifications ...............5-6
Available fuses ............................. 6
Recommended lockout devices ............... 6
Dimensions ............................... 6
Motor sizing tables ......................... 7
Auxiliary contacts
Description and specifications ................ 8
Dimensions ............................... 8
PLC fuse monitor
Description and specifications. ............... 9
Wiring schematic ...........................10
Connections ...............................10
Dimensions ...............................11
Contents
Description Page Description Page
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse™), midget and IEC 10x38mm
DIN-Rail fused disconnect switches
2011/65/EU
Technical Data 1157 Effective March 2018
Supersedes March 2017
BUSSMANN
SERIES
2
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
1-, 2- and 3-pole — Class CC, midget, 10x38mm
Description:
The revolutionary Bussmann series
Compact Circuit Protector (CCP)
fused disconnect switch is 2/3 the
footprint of a traditional fusible
switch and can provide up to a high 200 kA
SCCR that can help improve assembly
SCCR.
Specications:
Ratings
• Volts
• 600 Vac (Class CC)
• 240 Vac (midget UL®)
• 400 Vac (midget International Electrotechnical Commission
(IEC)
• 80Vdc (DC Class CC/UL, DC midget/IEC)
• Amps
• 30A (UL)
• 32A (IEC)
• SCCR
• 200 kA (Class CC)
• 10 kA (midget UL)
• 120 kA (midget IEC max)
• 20 kA (DC Class CC/UL)
• 10 kA (DC midget/IEC)
Poles
• 1-, 2- and 3-pole versions
Agency information
• CE
• RoHS compliant
• For Class CC fuse versions
• UL 98 Listed, File E302370, Guide WHTY
• cULus to CSA Standard 22.2 No. 4-04, File 302370,
Guide WHTY7
• For UL midget and 10X38 IEC fuse versions
• UL 508 Listed, File E320230, Guide NRNT
• cULus Certified 22.2 No. 14-05
• IEC 60947-3 AC23A
• IEC 60947-3 DC23A
Conductors 75°C Cu or higher
• Single/dual 18-6AWG solid or stranded
• Single 4AWG solid or stranded
Terminals
• Single/dual conductor box lug or fork terminal suitable for
line, load or accessory connection
Torque
• 18-10AWG 20 Lb-In
• 8-4AWG 35 Lb-In
Storage and operating temperature
• -20°C to 75°C*
* For fuse performance under or above 25°C, consult fuse performance
derating charts in the Bussmann Division publication titled Selecting
Protective Devices (SPD), data sheet No. 3002.
Flammability rating
• UL 94V0
Lockout/tagout provisions
• 4mm shank lock or Brady pin-out device part number 90850
Mounting
• 35mm DIN-Rail
Local open fuse indication minimum voltage**
• 90 Vac for AC versions
• 12Vdc for DC versions
** Open fuse indication requires an open fuse to be in the CCP and the
switch in the ON position.
Accessories
• Auxiliary contacts
• PLC wired remote fuse indication
Shipping weight
• 2.84 lbs (1.29 kg) per carton
Carton quantity
• 12 poles
Features:
• Extremely compact design at 17.5mm wide per pole
• High Short-Circuit Current Ratings (SCCR) up to 200 kA (UL)
and 120 kA (IEC)
• Disconnect rated to provide means for load isolation
• Full voltage rated up to 600 Vac or 80Vdc
• Class CC version is UL 98 Listed and horsepower rated,
and suitable for branch circuit disconnect and branch circuit
protection
• IEC 10x38 version complies with IEC 60947-3 and suitable for
branch circuit disconnect and branch circuit protection
• Suitable for global installations, the units comply with UL,
cULus, and IEC standards accepting UL Class CC, midget or
IEC aM and gG/gL fuses
• Open fuse indication:
• Local fuse indication lights are standard
• Optional wired remote open fuse indication can be utilized
to signal a PLC and open a contactor to de-energize all
phases, if required
• IP20 finger-safe with 10AWG (6mm2) or larger wire
• Built-in switch interlock prohibits removing the fuse under
load
• Padlockable handle for lockout/tagout procedures -
recommend using Brady pin-out device part number 90850
1-Pole DC CCP
3
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
Switch handle
(ganged on 2- and
3-pole versions)
Catalog numbers:
Amp
rating Fuse class
No. of
poles Volts SCCR
Max horsepower rating ( Vac) Wire size/
(torque*)
Wire
type Catalog no. Agency information
120 240 480 600
30 CC 1 600 Vac 200 kA 0.5
Single/Dual
18-6AWG
Sol/Str
Single
4AWG
Sol/Str
Spade
Terminal††
75°C Cu
or
higher
CCP-1-30CC UL 98 Listed, cULus 22.2, No. 4-04
30 CC 2 600 Vac 200 kA 2 CCP-2-30CC UL 98 Listed, cULus 22.2, No. 4-04
30 CC 3 600 Vac 200 kA —357. 5 CCP-3-30CC UL 98 Listed, cULus 22.2, No. 4-04
30 UL Midget
1
240 Vac10 kA
CCP-1-30M
UL 508 Listed, cULus 22.2, No. 14-05
32** 10x38 IEC 400
Vac120 kAIEC 60947-3, AC-23A
30 UL Midget
2
240 Vac10 kA
CCP-2-30M
UL 508 Listed, cULus 22.2, No. 14-05
32** 10x38 IEC 400
Vac120 kAIEC 60947-3, AC-23A
30 UL Midget
3
240 Vac10 kA
CCP-3-30M
UL 508 Listed, cULus 22.2, No. 14-05
32** 10x38 IEC 400
Vac120 kAIEC 60947-3, AC-23A
30 CC 1 80Vdc20 kA CCP-1-DCC UL 98 Listed, CSA 22.2, No. 4-04
30 UL Midget 1 80Vdc10 kA CCP-1-DCM UL 508 Listed, cULus 22.2, No. 14-05
32** 10x38 IEC IEC 60947-3, DC-23A
* 18-10AWG; 20 Lb-In, 8-4AWG; 35 Lb-In.
** 32A Class aM, 25A Class gG.
SCCR May be lower, refer to installed fuse data sheets.
†† Fork terminal with a 4.3mm gap for a #8-32 stud, 30A max, insulated flange, wire size 12-10AWG.
Available Bussmann series fuses:
Fuse
class Type/description Volts
Data
sheet no.
CC LP-CC time-delay, current
limiting 600 Vac/300Vdc 1023
CC FNQ-R time-delay 600 Vac/300Vdc 1014
CC KTK-R fast-acting 600 Vac 1015
MFNM time-delay 250 Vac 2028
MFNQ time-delay 500 Vac 1012
MKTK fast-acting 600 Vac 1011
MBAF fast-acting 250 Vac 2 011
MKLM fast-acting 600 Vac/dc 2020
gG/gL C10G 500V (400V@32A) 720115
aM C10M 500V
(400V@20@25A) 720115
Dimensions – mm (in)
Class CC, UL midget and I0x38 IEC
Recommended lockout device:
CCP version Brady pin-out device P/N
Class CC, midget, IEC 10x38 90850
92.7
(3.7)
17.5
(0.7)
45
(1.8)
35
(1.4)
79.8
(3.1)
52.5
(2.1)
49.2
(1.9)
Fuse access door
Circuit
marking
area
Fork
terminal
Box lug
terminal
Open fuse
indicating light
Lockout/
tagout
provision
4
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
Motor sizing table:
LP-CC time-delay Class CC fuses
Voltage Motor size (Hp) Motor FLA (amps) Min (amps) Code max (amps) Heavy start (amps)
115 Vac, 1-phase
0.167 4.4 9 15 15
0.25 5.8 12 20 20
0.33 7. 2 15 25 25
0.50 9.8 30 30 30
230 Vac, 1-phase
0.17 2.2 4.5 10 10
0.25 2.9 6 10 10
0.33 3.6 7 15 15
0.50 4.9 10 15 15
0.75 6.9 15 25 25
1 8 25 25 30
1.5 10 30 30 30
200 Vac, 3-phase
0.50 2.5 5 10 10
0.75 3.7 7. 5 15 15
1 4.8 10 15 15
1.5 6.9 15 25 25
27. 8 25 25 30
208 Vac, 3-phase
0.50 2.4 5 10 10
0.75 3.5 7 15 15
1 4.6 10 15 15
1.5 6.6 15 20 25
27. 5 15 25 30
230 Vac, 3-phase
0.50 2.2 4.5 10 10
0.75 3.2 7 10 12
1 4.2 9 15 15
1.5 612 20 20
2 6.8 15 25 25
3 9.6 30 30 30
460 Vac, 3-phase
0.50 1.1 2.25 6 6
0.75 1.6 3.2 6 6.25
1 2.1 4.5 10 10
1.5 3 6 10 12
2 3.4 7 15 15
3.00 4.8 10 15 15
5.00 7. 6 25 25 30
575 Vac, 3-phase
0.50 0.9 1.8 3 3.5
0.75 1.3 2.8 6 6
11.7 3.5 6 6.25
1.5 2.4 5 10 10
2 2.7 5.6 10 10
3.00 3.9 8 15 15
5.00 6.1 15 20 20
7.50 9 30 30 30
Note: NEMA motors only (no IEC or design B energy efficient). Minimum size if no more than 1 start/hour. Code max if low to moderate reverse/jog/plug
applications.
Heavy start permitted only if code max does not allow motor start-up. For high reverse/jog/plug applications or larger horsepower motors, Bussmann series
Class CF (Class J electrical performance) fuses are recommended. See CCP_CF with CUBEFuse™.
5
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
1-, 2- and 3-Pole — Class CF
Description:
The revolutionary Bussmann series
Compact Circuit Protector (CCP) fused
disconnect switch with CUBEFuse™is 2/3
the footprint of a traditional fusible switch
and provides a high 200 kA SCCR that can
help increase assembly SCCR.
Specications:
Ratings
Volts
• 600 Vac
• 125Vdc (up to 80A max)
Amps
• 30, 60, 100A
SCCR
• 200 kA AC
• 100 kA DC (up to 80A max)
Poles
• 1-, 2-, 3-pole
Agency information
• UL 98 Listed, File E302370, Guide WHTY
• cULus to CSA Standard 22.2 No. 4-04, File 302370,
Guide WHTY7
• CE
• RoHS compliant
Conductors 75°C Cu or higher
• 30 to 60A CCPs: - Single/dual 18-6AWG solid or stranded
- Single 4AWG solid or stranded
• 100A CCPs - Single 10-8AWG solid
- Single 8-1AWG stranded
- Dual 6AWG stranded
Terminals
• Single/dual conductor box lug or fork terminal suitable for line,
load or accessory connection
• Torque: 0-60A: - 18-10AWG 20 Lb-In
- 8-6AWG 35Lb-In
- 4AWG 35 Lb-In
70-100A: - 18-10AWG single 25 Lb-In
- 8-1AWG single 40 Lb-In
- 6AWG dual 45 Lb-In
Fuses
• Uses finger-safe Class CF Bussmann series CUBEFuse with
Class J performance
• Bussmann series Low-Peak™ dual-element, time-delay*
• Non-indicating 1-100A
• Indicating 6-100A
• Fast-acting, non-indicating 1-100A**
* See data sheet No. 9000.
**See data sheet No. 2147.
Storage and operating temperature
• -20°C to 75°C***
*** For fuse performance under or above 25°C, consult fuse performance
derating charts in the Bussmann Division publication titled Selecting
Protective Devices (SPD) No. 3002.
Flammability rating
• UL 94V0
Lockout/tagout provisions
• 4mm shank lock
Mounting
• 35mm DIN-Rail
Local open fuse indication minimum voltage
• 90V
Open fuse indication requires an open fuse to be in the CCP and the switch
in the ON position.
Accessories
• Auxiliary contacts
• PLC wired remote fuse indication
• Bussmann series CUBEFuse fuse pullers (P/Ns: CFP-30,
CFP-60, CFP-100)
Shipping weight
• 2.03 lbs (0.92kg) per carton
Carton quantity
• Six (6) poles
Features:
• Uses Class CF finger-safe fast-acting and time-delay
CUBEFuse with Class J electrical performance
• Extremely compact design at 25.4mm (1 inch) wide per pole
• Ampacity rejecting disconnects will not accept Bussmann
series CUBEFuse amp ratings greater than switch rating
• High Short-Circuit Current Ratings at 200 kA
• Disconnect rated to provide means for load isolation
• Full voltage rated at 600 Vac
• 125Vdc rated up to 80A max
• UL 98 Listed and suitable for branch circuit disconnect and
branch circuit protection
• 1-, 2- and 3-pole versions are horsepower rated
• Complies with UL and CSA
• Open fuse indication:
• Local fuse indication lights are standard
• Optional wired remote open fuse indication can be utilized
to signal a PLC and open a contactor to de-energize all
phases, if required
• Additional open fuse indication can be provided by the
Bussmann series CUBEFuse
• IP20 finger-safe construction with 10AWG (6mm2) wire or
larger
• Built-in switch interlock capability prohibits removing the fuse
under load
• Padlockable handle for lockout/tagout procedures
6
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
Catalog numbers:
Amp
rating
UL
fuse
class
No. of
poles Volts SCCR
Max horsepower rating ( Vac)*
Wire size/
torque**
Wire
type
Catalog
number Agency information120 240 480 600
30 CF 1 600 Vac 200 kA 1.5 ———
Single/Dual
18-6AWG Sol/Str
Single
4AWG Sol/Str
Spade Terminal
75°C Cu
or higher
CCP-1-30CF UL 98 Listed, cULus 22.2, No. 4-04
125Vdc 100 kA
30 CF 2 600 Vac 200 kA 3 CCP-2-30CF UL 98 Listed, cULus 22.2, No. 4-04
125Vdc 100 kA
30 CF 3 600 Vac 200 kA 5 15 10 CCP-3-30CF UL 98 Listed, cULus 22.2, No. 4-04
60 CF 1 600 Vac 200 kA 3 CCP-1-60CF UL 98 Listed, cULus 22.2, No. 4-04
125Vdc†† 100 kA
60 CF 2 600 Vac 200 kA 7. 5 CCP-2-60CF UL 98 Listed, cULus 22.2, No. 4-04
125Vdc†† 100 kA
60 CF 3 600 Vac 200 kA 7. 5 20 15 CCP-3-60CF UL 98 Listed, cULus 22.2, No. 4-04
100 CF 1 600 Vac 200 kA 5 Single
8-10AWG Sol/Str
8-1AWG Str
Dual 6AWG Str
Spade Terminal
CCP-1-100CF UL 98 Listed, cULus 22.2, No. 4-04
125Vdc††† 100 kA
100 CF 2
600 Vac 200 kA
10 CCP-2-100CF UL 98 Listed, cULus 22.2, No. 4-04
125Vdc††† 100 kA
100 CF 3 600 Vac 200 kA 20 50 40 CCP-3-100CF UL 98 Listed, cULus 22.2, No. 4-04
* With time-delay Bussmann series Low-Peak CUBEFuse.
** 30-60A: 18-10AWG 20 Lb-In, 8-6AWG 35 Lb-In, 4AWG 35 Lb-In, 70-100A: 18-10AWG Single 25 Lb-In, 8-1AWG Single 35 Lb-In, 6AWG Dual 45 Lb-In
Fork terminal with a 4.3mm gap for a #8-32 stud, 30A max, insulated flange, wire size 12-10AWG.
Up to 40A max.
†† Up to 80A max.
Available Bussmann series fuses:
Fuse class Type/description Data sheet No.
CF Low-Peak time-delay, current
limiting 600 Vac/300Vdc 9000
CF UPS/fast-acting 600 Vac/dc 2147
Dimensions – mm (in)
30 and 60A CUBEFuse CCP 100A CUBEFuse CCP
50.4
(2.0)
25.1
(1.0)
75.7
(3.0)
9.1
(0.4)
7.6
(0.3)
60.3 (2.4)
113.9
(4.5)
49.2
(1.9)
75.1
(3.0)
30A CUBEFuse
83.3 (3.3)
60A CUBEFuse
89.1 (3.5)
79.5
(3.0)
147.1
(5.8)
50.5
(2.0)
25.15
(1.0)
91.2
(3.6)
56.6
(2.2)
100.0
(3.9)
67.7
(2.7)
Switch handle (ganged on 2- and 3-pole versions)
Fuse holder
Circuit
marking
area
Fork
terminal
Box lug
terminal
Open fuse
indicating light
Lockout/
tagout
provision
7
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
Motor sizing table:
Bussmann series TCF Low-Peak™ time-delay Class CF fuses
Voltage
Motor
size (Hp)
Motor
FLA (amps)
Optimal
protection
(amps)
Code
max
(amps)
Heavy
start
(amps)
115 Vac, 1-phase
0.167 4.4 10 10 10
0.25 5.8 10 15 15
0.333 7. 2 15 15 15
0.5 9.8 15 20 20
0.75 13.8 25 25 30
116 25 30 35
1.5 20 30 35 45
2 24 40 45 50
3 34 50 60 N/A
5** 56 90 10 0 N/A
230 Vac,1-phase
0.167 2.2 6 6 6
0.25 2.9 6 6 6
0.333 3.6 6 10 10
0.5 4.9 10 10 10
0.75 6.9 15 15 15
1 8 15 15 1 7. 5
1.5 10 15 20 20
212 20 25 25
317 25 30 35
5 28 45 50 60
7. 5 40 60 N/A N/A
10** 50 80 90 N/A
200 Vac, 3-phase
0.5 2.5 6 6 6
0.75 3.7 6 10 10
1 4.8 10 10 10
1.5 6.9 15 15 15
27. 8 15 15 1 7. 5
311 1 7. 5 20 20
51 7. 5 30 35 35
7. 5 25.3 40 45 50
20** 62.1 100 N/A N/A
208 Vac, 3-phase
0.5 2.4 6 6 6
0.75 3.5 6 10 10
1 4.6 10 10 10
1.5 6.6 10 15 15
27. 5 15 15 15
3 10.6 1 7. 5 20 20
5 16.7 25 30 35
7. 5 24.2 40 45 50
20** 59.4 90 N/A N/A
Voltage
Motor
size (Hp)
Motor
FLA (amps)
Optimal
protection
(amps)
Code
max
(amps)
Heavy
start
(amps)
230 Vac, 3-phase
0.5 2.2 6 6 6
0.75 3.2 6 6 6
1 4.2 10 10 10
1.5 610 15 15
2 6.8 15 15 15
3 9.6 15 20 20
5 15.2 25 30 30
7. 5 22 35 40 45
20** 54 90 10 0 N/A
460 Vac, 3-phase
0.5 1.1 3 3 3
0.75 1.6 3 3 3
1 2.1 6 6 6
1.5 3 6 6 6
2 3.4 6 6 6
3 4.8 10 10 10
57. 6 15 15 15
7. 5 11 1 7. 5 20 20
10 14 25 25 30
15 21 35 40 45
20 27 40 50 60
50** 65 100 N/A N/A
575 Vac, 3-phase
0.5 0.9 3 3 3
0.75 1.3 3 3 3
11.7 3 3 3
1.5 2.4 6 6 6
2 2.7 6 6 6
3 3.9 6 10 10
5 6.1 10 15 15
7. 5 915 20 20
10 11 1 7. 5 20 20
40** 41 70 80 80
Note: Use Code Max column for low to moderate reverse/jog/plug
applications.
*Heavy Start permitted only if Code Max does not allow motor start-up.
Based on motor FLA from NEC® tables 430.248 and 430.250.
8
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
1.8
2.6
3.7
1.9
.190
.3
1.8
2.9
2.2
3.7
.190
.3
33 NO
41 NC
34 NO
42 NC
42 NC
34 NO
33 NO
41 NC
STRIP
STRIP
Auxiliary Contacts:
Description:
NO+NC contact output to indicate
the status of the switching
mechanism on the CCP.
Specications:
• Rated ampacity 5 A
• Rated voltage 240 Vac
• NC/NO contacts are closed/open when the CCP switch is in
the ON” position (closed)
• Flammability rating UL 94V0
Agency information
• UL 98 Recognized, File E155130, Guide WHTY2
• cULus to CSA, Standard 22.2 No. 4-04
• IEC 60947-5-1
Wiring
• 20-16AWG (0.5 to 1.5mm2) wire
• Torque 5 Lb-In (0.68N•m)
• For use with only 75°C Cu wire
Packaging
• The CCP-AUX and CCP-AUX-100 are packaged individually
• A single unit is capable of mounting to a 1-, 2-, or 3-pole CCP
Installation technique
• Mounts on the right side ONLY of the CCP, and mechanically
interlocks with the CCP switch handle with hardware provided
IP20 rating — yes
Environmental data
• Storage and operating temperature: -20°C to 75°C
Catalog numbers
• 1-60 A, CCP-AUX
• 70-100 A, CCP-AUX-100
Description Max per CCP
Signal
output
Agency
information Catalog no.
Auxiliary Contacts
NO+NC for
Switch Status
up to 60A
1 per CCP
(1-, 2- or
3-pole)
5A/240
Vac
UL 98
Recognized,
cURus 22.2
No. 4-04,
IEC 60947-5-
1 AC-15
CCP-AUX
Auxiliary Contacts
NO+NC for
Switch Status
70 to 100A
1 per CCP
(1-, 2- or
3-pole)
5A/240
Vac
UL 98
Recognized,
CSA C22.2
No. 4-04
CCP-AUX-100
De-energize all circuits before installing or removing any CCP-AUX devices
and follow all prescribed safety procedures.
Installed on a CCP-3-xx
Up to 60A CCP 70 to 100A CCP
Dimensions – mm (in)
Up to 60A CCP
70 to 100A CCP
9
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
PLC fuse monitor:
Description:
A resettable three-
phase fuse monitor that
integrates with the I/O
card in a Programmable
Logic Controller (PLC).
Specications:
• Signal output to PLC:
• +24Vdc, 10mA max
• Output signals:
• Digital 0Vdc (low), 24Vdc max (high)
• 0Vdc Low – fuse is good
• 24Vdc High – fuse has opened
When the fuse opens, the output signal is sent high and will
remain high until the unit is reset.
Agency information
• UL 98 Recognized, File E155130, Guide WHTY2
• cULus to CSA, Standard 22.2 No. 4-04
Emissions and immunity testing
• Electrostatic discharge, IEC 61000-4-2
• Electrical fast transient/burst, IEC 6100-4-4
• Surge immunity, IEC 61000-4-5
Rated impulse voltage
• 8kV
Local indication
• Two distinct LEDs indicate unit power (green) and open fuse
(red). Open fuse LED is resettable upon the replacement of
the fuse and the actuation of the reset switch
Flammability rating
• UL 94V0
Wiring
• For power, signal and ground connections use shielded
twisted pair 22-24AWG (0.34-0.25mm2) 300V rated wire
Packaging
• The CCP-PLC-IND is packaged individually
• A single unit monitors up to three phases. Package includes
0.110” (2.8mm) quick connects for power, signal and ground
connections
Minimum circuit voltage
• Minimum circuit voltage required across the CCP is 100 Vac/dc
for the remote indication device to operate
Installation technique
• Mounts on the left side ONLY of the CCP and mechanically
interlocks with the CCP switch handle with hardware provided
IP20 rating — yes
Storage and operating temperature
• -20°C to 75°C
PLC programming
• The CCP-PLC-IND signal line is designed to provide a digital
input to a PLC I/O card. In this case, a Programmable Logic
Control program must be written to properly interpret the
input signal to the PLC. The PLC program should check for
consecutive high signals before taking action on a critical
process.
Catalog numbers
• 1-60 A, CCP-PLC-IND
• 70-100 A, CCP-PLC-100
Description
Max
per
CCP
Signal
output
to PLC
Min.
circuit
Volts
Agency
information Catalog no.
Wired remote
fuse
indication for
PLC
applications
up to 60A
1 per
CCP
(1, 2- or
3-pole)
24Vdc/
10mA
100
Vac
UL 98
Recognized,
cURus 22.2
No. 4-04
CCP-PLC-IND
Wired remote
fuse
indication for
PLC
applications
70 to 100A
CCP-PLC-100
De-energize all circuits before installing or removing any CCP-PLC-IND
devices and follow all prescribed safety procedures.
Installed on a CCP-3-xx
Up to 60A CCP 70 to 100A CCP
10
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
PLC wiring schematic:
Connection from CCP-PLC-IND to CCP
Connections for CCP-PLC-IND from a CCP-3-XX
to a remote monitoring device
Connect leads from CCP-PLC-IND to the terminals as shown.
There is a dedicated terminal on the CCP to accept the spade
connectors from the CCP-PLC-IND.
NOTE: When monitoring a 1-or 2-pole CCP, trim unused leads.
PLC power supply CCP-PLC-IND
PLC
input card
+24 Vdc
0 Vdc/Gnd
+24 Vdc
0 Vdc/Gnd
+24 Vdc
0 Vdc/Gnd
Signal
10 mA max.
The CCP-PLC-IND needs
to be powered by the same
+24 Vdc and ground
(0 Vdc/Gnd return)
terminals that feed the
PLC input card.
If it is not, it may
improperly signal.
If feeding multiple
CCP-PLC-INDs from
different power supplies,
there must be multiple
input cards being powered
by those same power
supplies as well.
Circuit monitoring leads
from CCP-PLC-IND to CCP
(100 Vac 600 Vac)
Circuit monitoring
leads from PLC or
remote monitoring
device.
11
Technical Data 1157
Effective March 2018
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Eaton.com/bussmannseries
2.6
1.8
3.7
1.9
.3
2.0
2.9 2.2
3.7
ON
RESET
STATUS
+24vDC
+24vDC
GND
SIG
.3
ON
RESET
STATUS
+24vDC
+24vDC
GND
SIG
5L 33L 21L 1
6T
3
4T
2
2T
1
6T
3
2T
1
4T
2
1L 1
3L 2
5L 3
Dimensions – mm (in)
Up to 60A CCP
70 to 100A CCP
Compact Circuit Protector (CCP)
UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm
fused disconnect switches
Technical Data 1157
Effective March 2018
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction
of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
Eaton, Bussmann, CUBEFuse and Low-Peak
are valuable trademarks of Eaton in the US
and other countries. You are not permitted
to use the Eaton trademarks without prior
written consent of Eaton.
CSA is a registered trademark of the
Canadian Standards Group
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2018 Eaton
All Rights Reserved
Printed in USA
Publication No. 1157 – BU-SB15192
March 2018
For Eatons Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Follow us on social media to get the
latest product and support information.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information: