Ordering information Three phase input type(1-stage filter) FTA series(80,100,125,150A) FTA -80 -683 1 2 3 -O 4 1 Model Name 2 Rated Current 3 Line to ground capacitor code:See table 1.1. R table1.1 Line to ground capacitor code Code 223 Line to ground Leakage Current (Input 250/500V 60Hz) capacitor (155,335only 250/400V 60Hz) (nominal value) 1.0mA/2.0mA max 22,000pF 683 2.5mA/5.0mA max 68,000pF 104 3.5mA/7.0mA max 100,000pF 155 160mA/250mA max 1.5 F 335 320mA/500mA max 3.3 F * When the line to ground capacitor code is Features of FTA series Book type (Space-saving type) - 1-stage filter General-purpose High-attenuation (150kHz - 1MHz) - Selectable leakage current value, Ultra high attenuation type "155","335" for EU (Wye type with neutral earth system), With switch of line to ground capacitor "-G" Specifications No. 1 2 3 4 5 6 7 8 9 10 11 12 13 Items Rated Voltage[V] Rated Current[A] Test Voltage (Terminal-Mounting Plate) Isolation Resistance (Terminal-Mounting Plate) Leakage current 250/500V 60Hz DC resistance Safety agency approval temperatures Operating temperature Operating humidity Storage temperature/humidity Vibration Impact Safety agency approvals 14 Case size (without projection) 15 Weight *1 *2 *3 *4 different, the attenuation characteristic is different. 4 Option H:Ultra high attenuation type "155","335" is not applied. S:Hexagon socket head cap screw (Standard type is Hexagon head screw) U:Improve differential mode attenuation (Rated voltage 250V) G:With switch of line to ground capacitor Only "155","335" is applied. "155" is Leakage current 160mA/250mA max * when the switch state is ON (switched to " "). 50A/80A max when the switch state is OFF (switched to " "). " 335" is Leakage current 320mA/500mA max when the switch state is ON (switched to " "). 50A/80A max when the switch state is OFF (switched to " "). FTA-80-683 FTA-100-683 FTA-125-683 FTA-150-683 AC Three phase 500 (voltage range:528 max) 50/60Hz *1 *2 80 100 125 150 2,500 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity *3 500 VDC 100MW min at room temperature and humidity *4 2.5mA/5.0mA max 5mW max 4mW max 3mW max 3mW max -25 to +85C (Refer to Derating Curve) -40 to +85C (Refer to Derating Curve) 20 to 95%RH (Non condensing) -40 to +85C/20 to 95%RH (Non condensing) 10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1hour each X, Y and Z axis 196.1m/s2 (20G), 11ms Once each X, Y and Z axis UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC 100X130X210 mm (WXHXD) 100X170X260 mm(WXHXD) (Option: -G refer to external view) (Option: -G refer to external view) [3.94X5.12X8.27 inches] [3.94X6.69X10.24 inches] 3.1kg max 4.2kg max Only capacitor code and option "155","335", Three Phase D-connection:400 (440 max), Wye-connection:500(528 max) Only option "U", Three Phase 250(275 max) Only capacitor code and option "155","335", 2,800VDC (Cutoff Current = 10mA), 1minute at room temperature and humidity. Only capacitor code and option "155","335", Isolation resistance specification is deleted. Circuit Diagram (1) Line to ground capacitor code : 223, 683, 104 LINE Case (2) Line to ground capacitor code : 155, 335 LOAD LINE Case LOAD LINE Case LOAD 1 4 1 4 1 4 2 5 2 5 2 5 3 6 3 6 3 6 CY CY CY : Line to ground capacitor : Mounting Plate Case CY : Line to ground capacitor : Mounting Plate (5) Line to ground capacitor code : 155, 335 Option : G LOAD LINE Case Derating Curve LOAD 1 4 1 4 2 5 2 5 3 6 3 6 CY CY CY : Line to ground capacitor : Mounting Plate SW CY CY SW : Switch CY : Line to ground capacitor (The switch state is OFF) : Mounting Plate 100 Load Factor [%] (4) Line to ground capacitor code : 155, 335 Option : U LINE CY CY CY CY CY : Line to ground capacitor : Mounting Plate FTA-7 (3) Line to ground capacitor code : 223, 683, 104 Option : U 80 60 40 20 0 -40 -30 -20 40 50 60 70 80 Ambient Temperature [C] *Keep free ventilation holes for cooling. 90 FTA series (80,100,125,150A) External view FTA-80 / FTA-100 / FTA-125 210 [8.27] 3-M8 (Option-S: Hexagon socket head cap screws) Output Terminal 169 28 [1.1] Name Plate M6 (Option-S: Hexagon socket head cap screws) Protection Earth Terminal Cover Terminal Cover 20 130 [0.79] [0.79] 20 103 [4.06] 103 [4.06] [5.12] 100 [3.94] 26 M6 (Option-S: Hexagon socket head cap screws) Protection Earth 3-M8 (Option-S: Hexagon socket head cap screws) Input Terminal [1.02] [6.65] The air hole for heat radiation is not on the opposite side side. 6.5 [0.26] [0.26] Mounting Hole 2- 6.5 6.5 Mounting Hole [0.26] [3.15] 80 0.5 Mounting Plate 195 0.5 Tolerance : 1 [0.04] Weight : 3.1kg max Mounting Plate : Aluminum t=2.0 [0.08] Dimensions in mm, [ ]=inches Terminal block screw tightening torque M8 : 9.2N m(93.9kgf cm)max Protection Earth (PE) screw tightening torque M6 : 5.8N m(59.2kgf cm)max Can not be mounted upside-down (mounted the top surface) Keep free ventilation holes for cooling [7.68] FTA-80 / FTA-100 / FTA-125 with switch of line to ground capacitor ON/OFF 210 [8.27] 3-M8 (Option-S: Hexagon socket head cap screws) Output Terminal 169 [6.65] [1.1] M6 (Option-S: Hexagon socket head cap screws) 28 Name Plate 3-M8 (Option-S: Hexagon socket head cap screws) Input Terminal Protection Earth 130 103 20 20 [0.79] [0.79] 103 [4.06] [5.12] Terminal Cover [4.06] Terminal Cover With switch of line to ground capacitor Mounting Hole 6.5 [0.26] [0.26] The air hole for heat radiation is not on the opposite side side. 2- 6.5 80 0.5 Mounting Plate 6.5 Mounting Hole 195 0.5 [0.26] [3.15] [0.22] 5.5 -0.5 +1.5 100 [3.94] 26 [1.02] M6 (Option-S: Hexagon socket head cap screws) Protection Earth Tolerance : 1 [0.04] Weight : 3.1kg max Mounting Plate : Aluminum t=2.0 [0.08] Dimensions in mm, [ ]=inches Terminal block screw tightening torque M8 : 9.2N m(93.9kgf cm)max Protection Earth (PE) screw tightening torque M6 : 5.8N m(59.2kgf cm)max Can not be mounted upside-down (mounted the top surface) Keep free ventilation holes for cooling The switch state is OFF at shipping Switch status ON : " ", OFF : " " HIGH LEAKAGE CURRENT first connect to erath [7.68] FTA-8 FTA series (80,100,125,150A) External view FTA-150 260 3-M8 (Option-S: Hexagon socket head cap screws) [10.24] 219 [8.62] Output Terminal 28 [1.1] Name Plate 100 [3.94] 26 [1.02] M6 (Option-S: Hexagon socket head cap screws) Protection Earth 3-M8 (Option-S: Hexagon socket head cap screws) Input Terminal Protection Earth 170 143 [5.63] The air hole for heat radiation is not on the opposite side side. Tolerance : 1 [0.04] Weight : 4.2kg max Mounting Plate : Aluminum t=2.0 [0.08] Dimensions in mm, [ ]=inches Terminal block screw tightening torque M8 : 9.2N m(93.9kgf cm)max Protection Earth (PE) screw tightening torque M6 : 5.8N m(59.2kgf cm)max Can not be mounted upside-down (mounted the top surface) Keep free ventilation holes for cooling Mounting Hole 6.5 2- 6.5 [0.26] [0.26] 20 20 [0.79] [0.79] [6.69] Terminal Cover [5.63] 6.5 [3.15] Mounting Plate Mounting Hole 245 [0.26] 143 Terminal Cover 80 0.5 M6 (Option-S: Hexagon socket head cap screws) 0.5 [9.65] FTA-150 with switch of line to ground capacitor ON/OFF 260 3-M8 (Option-S: Hexagon socket head cap screws) [10.24] 219 [8.62] Output Terminal 28 Name Plate M6 (Option-S: Hexagon socket head cap screws) 100 [3.94] 3-M8 (Option-S: Hexagon socket head cap screws) Input Terminal [1.1] 26 [1.02] M6 (Option-S: Hexagon socket head cap screws) Protection Earth +1.5 -0.5 5.5 [0.22] Protection Earth Terminal Cover 20 6.5 [0.26] Mounting Hole 6.5 245 0.5 [9.65] [0.26] Mounting Plate [3.15] 80 0.5 [0.26] FTA-9 170 [6.69] 143 [0.79] [0.79] 20 The air hole for heat radiation is not on the opposite side side. 2- 6.5 Mounting Hole [5.63] With switch of line to ground capacitor [5.63] 143 Terminal Cover Tolerance : 1 [0.04] Weight : 4.2kg max Mounting Plate : Aluminum t=2.0 [0.08] Dimensions in mm, [ ]=inches Terminal block screw tightening torque M8 : 9.2N m(93.9kgf cm)max Protection Earth (PE) screw tightening torque M6 : 5.8N m(59.2kgf cm)max Can not be mounted upside-down (mounted the top surface) Keep free ventilation holes for cooling The switch state is OFF at shipping Switch status ON : " ", OFF : " " HIGH LEAKAGE CURRENT first connect to erath Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Cosel: FTA-100-104 FTA-100-104-H FTA-100-104-HS FTA-100-104-S FTA-100-155 FTA-80-683-S FTA-80-223-H FTA80-223-HS FTA-80-223-S FTA-80-683 FTA-80-683-H FTA-80-683-HS FTA-80-104-S FTA-80-155 FTA-80-155-H FTA-80-155-HS FTA-80-155-S FTA-80-223 FTA-150-683-H FTA-150-683-HS FTA-150-683-S FTA-80-104 FTA-80104-H FTA-80-104-HS FTA-150-155-S FTA-150-223 FTA-150-223-H FTA-150-223-HS FTA-150-223-S FTA-150683 FTA-150-104-H FTA-150-104-HS FTA-150-104-S FTA-150-155 FTA-150-155-H FTA-150-155-HS FTA-100223-S FTA-100-683 FTA-100-683-H FTA-100-683-HS FTA-100-683-S FTA-150-104 FTA-100-155-H FTA-100-155HS FTA-100-155-S FTA-100-223 FTA-100-223-H FTA-100-223-HS