Mode of Operation
The Dupline
®
Master Module
(DMM) controls a 3-wire bus
with signal, DC-power and
common GND. The DMM is
connected to a standard DC-
supply, which it synchronizes
with the Dupline
®
carrier signal
before it is output to supply.
The synchronization is neces-
sary in order to enable the
Dupline
®
and DC-supply to
share the GND-wire.
The Dupline
®
Master Module is
a Dupline
®
Channel Generator
with the function of a master.
This means that the 128
Dupline
®
I/O’s will be read/writ-
ten by the DMM and then sent
to the PLC.
The DMM can run in two dif-
ferent modes – Normal mode
and split I/O mode. In Normal
mode, Dupline
®
operates as a
peer-to-peer system, where
the channel generator auto-
matically establishes a con-
nection between Dupline
®
inputs and Dupline
®
outputs
which are coded to the same
Dupline
®
address. If e.g. an
input coded for B5 is activat-
ed, the output(s) coded for B5
will also be activated.
Consequently, a Dupline
®
-out-
put can either be activated
through the output-data
received on DMM or by an
active Dupline
®
input coded
for the same Dupline
®
-
address. In “Split I/O” mode,
the channel generator treats
the Dupline
®
inputs and
Dupline
®
outputs indepen-
dently. If e.g. an input coded
for B5 is activated, the DMM
will make the information avail-
able for the PLC (like in normal
mode), but it will not automati-
cally activate the Dupline out-
put(s) coded to B5. The
Dupline
®
outputs are con-
trolled exclusively through the
output data received from the
PLC. In this mode, up to 128
Dupline
®
inputs and 128
Dupline
®
outputs are available,
since an input and an output
coded to the same Dupline
®
address can operate indepen-
dently.
G 3496 0003
General Specifications
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions H4-Housing
Material (see Technical information)
Weight 100 g
Dip-Switch Setting
Sw.2 On: If Communication fails, all Dupline
®
chan-
nels activated by the PLC, is deactivated.
Off: If Communication fails, Dupline
®
channels
activated by the PLC, remains activated.
Sw.3 On: Programming-port Protocol (Power up the
Module)
Off: Dedicated Protocol 1 (Power up the
Module)
Sw.4 On: Split I/O Channel Generator Mode
(See “Mode of Operation”)
Off: Normal Dupline
®
Monostable Channel
Generator Mode
Sw.5 On: 64 Dupline
®
channels
Off: 128 Dupline
®
channels
Memory Mapping
Dupline®Mitsubishi Dupline®Mitsubishi
Channel Channel
Read Write Read Write
A1 M0000 M0128 E1 M0032 M0160
A2 M0001 M0129 F1 M0040 M0168
A3 M0002 M0130 G1 M0048 M0176
A4 M0003 M0131 H1 M0056 M0184
A5 M0004 M0132 I1 M0064 M0192
A6 M0005 M0133 J1 M0072 M0200
A7 M0006 M0134 K1 M0080 M0208
A8 M0007 M0135 L1 M0088 M0216
B1 M0008 M0136 M1 M0096 M0224
B8 M0015 M0143 N1 M0104 M0232
C1 M0016 M0144 O1 M0112 M0240
D1 M0024 M0152 P1 M0120 M0248
Table of the memory mapping to the PLC