Notes concerning the product group
Fitted directly to the contactor Separate mounting
1 Contactor 051608
2 Bases 278473
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Climatic proofing Damp heat, constant, to IEC 60068−2−78;
Damp heat, cyclic, to IEC 60068−2−30
Ambient temperature
Open °C −25/50
Enclosed °C −25/40
Temperature compensation Continuous
Weight
Mechanical shock resistance half−sinusoidal shock 10
ms to IEC 60068−2−27 g 10
Protection type IP00
Protection against direct contact when actuated from
front (IEC 536) Finger− and back−of−hand proof
Main conducting paths
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage
AC UiV AC 690
Rated operational voltage UeV AC 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts V AC 440
Between main circuits V AC 440
Overload release setting range A 0,1 – 32
Temperature compensation residual error > 20ºC %/K f 0.25
Current heat loss (3 conductors)
Lower value of the setting range W 2,5
Maximum setting W 6
2