1
New Product
Solid-state Timer
H3Y Series
Miniature Timer Compatible with
the MY Relay
The Push-In Plus Terminal Block Socket-compatible
H3Y-@-B/H3YN-@-B Timers in a black design join the
Single-mode H3Y and Multi-mode H3YN.
•The H3Y-@-B and H3YN-@-B are UL listed when they
are used together with Push-In Plus Terminal Block
Sockets.
Large transparent time setting knob facilitates time
setting.
A flat-blade and Phillips screwdriver can also be used
for time setting.
Conforms to EMC standards.
Conforms to EN 61812-1 and approved by UL and CSA.
Model Number Structure
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
LR
H3Y Series
H3Y
Mono-function Timers
H3YN
Multi Timers
G On Delay
G Fixed Time Range
G On Delay
G Fixed Time Range
G Four-mode Timers
ON Delay
Interval
Flicker-OFF Start
Flicker-ON Start
G Four-time Ranges
Short-time range (0.1 s to 10 min)
Long-time range (0.1 min to 10 hrs)
G Bifurcated contacts
G Four-mode Timers
ON Delay
Interval
Flicker-OFF Start
Flicker-ON Start
G Four-time Ranges
S
hort-time range (0.1 s to 10 min)
Long-time range (0.1 min to 10 hrs)
G Bifurcated contacts
H3Y-@-B
Mono-function Timers
H3YN-@-B
Multi Timers
Refer to page 3.
The Entire H3Y Series
Refer to page 9. Refer to page 17. Refer to page 23.
H3Y Series
2
Model Number Structure
Note: Specify both the model number, supply voltage, and rated time when ordering.
Note: Specify both the model number, supply voltage when ordering.
H3Y- @ - @ - @
(1) (2) (3)
(1) Output (2) Terminal Type (3) Body Color and Terminal Arrangement
Symbol Meaning Symbol Meaning Symbol Meaning
2 DPDT None Plug-in terminals None Beige with output terminals on top and power
supply terminals on bottom
4 4PDT 0 PCB terminals B Black with power supply terminals on top and
output terminals on bottom
Ex) H3Y-2 100 to 120VAC 0.5S
Supply Voltage
Rated time
H3YN - @ @ @ - @
(1) (2) (3) (4)
(1) Output (2) Time Range (3) Contact Type
Symbol Meaning Symbol Meaning Symbol Meaning
2 DPDT None Short-time range None Single contact
4 4PDT 0 Long-time range Z Twin contacts
(4) Body Color and Terminal Arrangement
Symbol Meaning
None Beige with output terminals on top and power supply terminals on bottom
B Black with power supply terminals on top and output terminals on bottom
Ex) H3YN-2 100 to 120VAC
Supply Voltage
3
Solid-state Timer
H3Y
Miniature Timer Compatible with
the MY Relay
Semi-multi power supply voltage.
Large transparent time setting knob facilitates time
setting.
A flat-blade and Phillips screwdriver can also be
used for time setting.
Pin configuration compatible with MY Power Relay.
LED indication for power and output statuses.
Conforms to EMC standards.
Conforms to EN 61812-1 and approved by UL and
CSA.
Ordering Information
Note: Sockets and Hold-down Clips are not included with the H3Y. They must be ordered separately.
*Use the H3Y-4 or H3Y-4-0 Series when switching micro loads.
Accessories (Order Separately)
Adapter, Mounting Plate, Hold-down Clips
Note: For details, refer to Precautions for H3Y-series Timers on page
31.
Socket
Note: 1. Cannot be used with the H3Y-@-0 (PCB terminals).
2.
The PYF
@@
A-E has a finger-protection structure. Round crimp
terminals cannot be used. Use forked crimp terminals.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
LR
Refer to Safety Precautions on page 36.
Operation/
resetting system Time-limit contact Time ranges Supply voltage
Mounting
Surface/DIN-track
mounting
(with socket)
Surface mounting
(with PCB terminals)
Time-limit
operation/
self-resetting
DPDT (for power
switching) 0.04 s to 3 h
24, 100 to 120, 200 to 230,
240 VAC (50/60 Hz);
12, 24, 48, 125, 100 to
110 VDC
H3Y-2 H3Y-2-0
4PDT H3Y-4 *H3Y-4-0 *
Name/specification Model
Flush mounting adapter Y92F-78
Mounting
Plate for
Socket
For 1 Socket PYP-1
For 18
Sockets PYP-18
Hold-down
Clips
For PYF@A Y92H-3
For PY@ and
PYF@MY92H-4
Timer Square Sockets
Contact Model Pin
Connection
Terminal Model
DPDT H3Y-2 8-pin
Front
Connecting
DIN track
mounting PYF08A
DIN track
mounting
(Finger
Protection
Structure)
PYF08A-E
Screw
mounting PYF08M
Back
Connecting
Solder
terminal PY08
PCB
terminal PY08-02
4PDT H3Y-4
14-pin
Front
Connecting
DIN track
mounting PYF14A
DIN track
mounting
(Finger
Protection
Structure)
PYF14A-E
Back
Connecting
Solder
terminal PY14
PCB
terminal PY14-02
H3Y
4
Specifications
Time Ranges
Ratings
*1. Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Timers for details on your OMRON website.
*2. With DC ratings, single-phase full-wave rectified power sources may be used.
*3. Only the H3Y-2 and H3Y-2-0 Series include 12 VDC models.
*4. Use the Timer within 90% to 110% of the rated supply voltage (95% to 110% for 12 VDC) when using it continuously under an ambient
operating temperature of 50°C.
*5. Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC: 10 VAC max.
200 to 230 VAC: 20 VAC max.
100 to 110 VDC: 10 VDC max.
*6. Refer to Safety Precautions for All Timers on your OMRON website when combining the Timer with an AC 2-wire proximity sensor.
*7. A diode to prevent reverse voltages is provided only on models with a DC power supply.
Rated time Time setting range Rated time Time setting range
0.5 s 0.04 to 0.5 s 3 min 0.1 to 3 min
1 s 0.1 to 1 s 5 min 0.2 to 5 min
5 s 0.2 to 5 s 10 min 0.5 to 10 min
10 s 0.5 to 10 s 30 min 1 to 30 min
30 s 1.0 to 30 s 60 min 2 to 60 min
60 s 2.0 to 60 s 3 h 0.1 to 3 h
120 s 5.0 to 120 s --- ---
Item H3Y-2(-0)/H3Y-4(-0)
Rated supply voltage *6, *7100 to 120 (50/60 Hz), 200 to 230 VAC (50/60 Hz), 24 VAC (50/60 Hz) *1
12, 24, 48, 125, 100 to 110 VDC *2, *3
Operating voltage range All rated voltages except 12 VDC: 85% to 110% of rated supply voltage
12 VDC: 90% to 110% of rated supply voltage *4
Reset voltage 10% min. of rated supply voltage *5
Power consumption
100 to 120 VAC: 1.5 VA (at 120 VAC)
200 to 230 VAC: 1.8 VA (at 230 VAC)
24 VAC: 1.5 VA (at 24 VAC)
12 VDC: 0.9 W (at 12 VDC)
24 VDC: 0.9 W (at 24 VDC)
48 VDC: 1.0 W (at 48 VDC)
100 to 110 VDC: 1.3 W (at 110 VDC)
125 VDC: 1.3 W (at 125 VDC)
Control outputs
H3Y-2(-0):
5 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 5 VDC (P reference value).
Contact materials: Ag
H3Y-4(-0):
3 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 1 VDC (P reference value).
Contact materials: Au-clad + Ag-alloy
Ambient operating temperature -10°C to 50°C (with no icing)
Storage temperature -25°C to 65°C
Ambient operating humidity 35% to 85%
H3Y
5
Characteristics
*1. Add ±10 mS to the above value for the 0.5-S range model.
*2. Terminal screw sections are excluded.
*3. The destructive shock resistance test was performed on the Timer.
*4. Check the electrical life curve.
*5. Overvoltage category II.
*6. CCC certification requirements
Accuracy of operating time ±1% FS max. (0.5 s range: ±1%±10 ms max.) *1
Setting error ±10%±50 ms FS max.
Reset time Min. power-opening time: 0.1 s max. (including halfway reset)
Influence of voltage ±2% FS max. *1
Influence of temperature ±2% FS max. *1
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min
(between current-carrying terminals and exposed non-current-carrying metal parts) *2
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output) *2
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) *2
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Impulse withstand voltage
Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC
Noise immunity ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 4 kV
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude
Shock resistance Destruction: 1,000 m/s2 (approx. 100G) *3
Malfunction: 100 m/s2 (approx. 10G)
Life expectancy
Mechanical:10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
H3Y-2: 500,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h)
H3Y-4: 200,000 operations min. (3 A at 250 VAC, resistive load at 1800 operations/h) *4
Enclosure rating IP40
Weight Approx. 50 g
EMC
(EMI) EN 61812-1
Emission Enclosure: EN 55011 Group 1 class A
Emission AC Mains: EN 55011 Group 1 class A
(EMS) EN 61812-1
Immunity ESD: IEC 61000-4-2
Immunity RF-interference: IEC 61000-4-3
Immunity Burst: IEC 61000-4-4
Immunity Surge: IEC 61000-4-5
Immunity Conducted Disturbance: IEC 61000-4-6
Immunity Voltage Dip/Interruption: IEC 61000-4-11
Approved standards UL 508, CSA C22.2 No. 14, Lloyds, CCC: GB/T 14048.5 *6
Conforms to EN 61812-1 and IEC 60664-1. (2.5 kV/2 for H3Y-2/-2-0, 2.5 kV/1 for H3Y-4/-4-0) *5
Model H3Y-2 (-0) H3Y-4 (-0)
Recommended fuse RT14-20/6A (380 VAC 6 A), manufactured by
DELIXI
RT14-20/4A (380 VAC 4 A), manufactured by
DELIXI
Rated operating voltage Ue
Rated operating current Ie
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
AC-15: Ue: 250 VAC, Ie: 2 A
AC-13: Ue: 250 VAC, Ie: 3 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
Rated insulation voltage 250 V
Rated impulse withstand voltage
(altitude: 2,000 m max.) 2.5 kV (at 240 VAC)
Conditional short-circuit current 1000 A
H3Y
6
Engineering Data
Connections
Connections
H3Y-2, H3Y-2-0
Switching operations (×104)
Load current (A)
H3Y-2, H3Y-2-0
H3Y-4, H3Y-4-0
Load current (A)
Load current (A)
H3Y-4, H3Y-4-0
Load current (A)
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both
cases, a life of 100,000 operations can be expected.The minimum
applicable load is 1 mA at 5 VDC (P reference value).
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both
cases, a life of 100,000 operations can be expected.The minimum
applicable load is 1 mA at 1 VDC (P reference value).
Switching operations (×104)
Switching operations (×104)
Switching operations (×104)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
250 VAC, cosφ = 1
24 VDC, cosφ = 1
250 VAC, cosφ = 1
24 VDC, cosφ = 1
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
500
100
50
20
500
100
50
20
500
100
50
20
500
100
50
20
H3Y
7
Operation
Timing Chart
Nomenclature
H3Y-2, H3Y-2-0 H3Y-4, H3Y-4-0
NC NC
Note: t = Set time
Rt = Reset time
Note: t = Set time
Rt = Reset time
Run/Power Indicator (Green)
(Lit: Power ON)
Output Indicator (Orange)
(Lit: Output ON)
Main Dial
H3Y
8
Dimensions (Unit: mm)
Timers
(63.0)
6.4
6.3
28 max.
21.5
max.
H3Y-2
Mounting Holes
(60.7)
28 max.
6.3
21.5
max.
Eight,
1.3-dia. holes
Pin 1
H3Y-2-0
(63.0)
6.4
6.3
21.5
max.
28 max.
H3Y-4
Mounting Holes
(60.7)
28 max.
6.3
21.5
max.
Fourteen,
1.3-dia. holes
Pin 1
H3Y-4-0
9
Solid-state Timer
H3YN
Miniature Timer with Multiple Time
Ranges and Multiple Operating Modes
Minimizes stock.
Pin configuration compatible with MY Power Relay.
Standard multiple operating modes and multiple time ranges.
Conforms to EN 61812-1 and IEC 60664-1 for Low Voltage,
and EMC Directives.
Ordering Information
List of Models
Note: Sockets and Hold-down Clips are not included with the H3YN. They must be ordered separately.
*1. Use the H3YN-4 or H3YN-41 Series when switching micro loads, and use the H3YN-4-Z or H3YN-41-Z Series when switching even smaller
loads.
*2. Only models with 24 VDC power supply are available.
Accessories (Order Separately)
Adapter, Mounting Plate, Hold-down Clips
Note: For details, refer to Precautions for H3Y-series Timers on page 31.
Socket
Note: 1. Cannot be used with the H3Y-@-0 (PCB terminals).
2. The PYF@@A-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
3. For details, refer to Precautions for H3Y-series Timers on page 31.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
LR
Refer to Safety Precautions on page 36.
Supply voltage Time-limit contact Short-time range model
(0.1 s to 10 min)
Long-time range model
(0.1 min to 10 h)
24, 100 to 120, 200 to 230 VAC;
12, 24, 48, 100 to 110, 125 VDC
DPDT H3YN-2 H3YN-21
4PDT H3YN-4 *1H3YN-41 *1
24 VDC 4PDT (Twin contacts) H3YN-4-Z *1, *2H3YN-41-Z *1, *2
Name/specification Model
Flush mounting adapter Y92F-78
Mounting Plate for Socket For 1 Socket PYP-1
For 18 Sockets PYP-18
Hold-down Clips For PYF@A Y92H-3
For PY@ and PYF@M Y92H-4
Timer Square Sockets
Contact Model Pin
Connection
Terminal Model
DPDT H3YN-2@8-pin
Front Connecting
DIN track mounting PYF08A
DIN track mounting
(Finger Protection Structure) PYF08A-E
Screw mounting PYF08M
Back Connecting Solder terminal PY08
PCB terminal PY08-02
4PDT H3YN-4@14-pin
Front Connecting
DIN track mounting PYF14A
DIN track mounting
(Finger Protection Structure) PYF14A-E
Back Connecting Solder terminal PY14
PCB terminal PY14-02
H3YN
10
Specifications
Ratings
*1. Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Timers for details on your OMRON website.
*2. Single-phase, full-wave-rectified power supplies can be used.
*3. When using the H3YN continuously in any place where the ambient temperature is in a range of 45°C to 50°C, supply 90% to 110% of the
rated supply voltages (supply 95% to 110% with 12 VDC type).
*4. Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC: 10 VAC max.
200 to 230 VAC: 20 VAC max.
100 to 110 VDC: 10 VDC max.
*5. Refer to Safety Precautions for All Timers on your OMRON website when combining the Timer with an AC 2-wire proximity sensor.
*6. A diode to prevent reverse voltages is provided only on models with a DC power supply.
Item H3YN-2/-4/-4-Z H3YN-21/-41/-41-Z
Time ranges 0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max.
selectable)
0.1 min to 10 h (1 min, 10 min, 1 h, or 10 h max.
selectable)
Rated supply voltage *5, *624, 100 to 120, 200 to 230 VAC (50/60 Hz) *1
12, 24, 48, 100 to 110, 125 VDC *2
Pin type Plug-in
Operating mode ON-delay, interval, flicker OFF start, or flicker ON start (selectable with DIP switch)
Operating voltage range 85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage) *3
Reset voltage 10% min. of rated supply voltage *4
Power consumption
100 to 120 VAC: Relay ON: Approx. 1.8 VA (1.6 W) at 120 VAC, 60 Hz
Relay OFF: Approx. 1 VA (0.6 W) at 120 VAC, 60 Hz
200 to 230 VAC: Relay ON: Approx. 2.2 VA (1.8 W) at 230 VAC, 60 Hz
Relay OFF: Approx. 1.5 VA (1.1 W) at 230 VAC, 60 Hz
24 VAC: Relay ON: Approx. 1.8 VA (1.4 W) at 24 VAC, 60 Hz
Relay OFF: Approx. 0.3 VA (0.2 W) at 24 VAC, 60 Hz
12 VDC: Relay ON: Approx. 1.1 W at 12 VDC
Relay OFF: Approx. 0.1 W at 12 VDC
24 VDC: Relay ON: Approx. 1.1 W at 24 VDC
Relay OFF: Approx. 0.1 W at 24 VDC
48 VDC: Relay ON: Approx. 1.2 W at 48 VDC
Relay OFF: Approx. 0.3 W at 48 VDC
100 to 110 VDC: Relay ON: Approx. 1.6 W at 110 VDC
Relay OFF: Approx. 0.4 W at 110 VDC
125 VDC: Relay ON: Approx. 1.6 W at 125 VDC
Relay OFF: Approx. 0.4 W at 125 VDC
Control outputs
DPDT:
5 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 5 VDC (P reference value).
Contact materials: Ag
4PDT:
3 A at 250 VAC, resistive load (cosφ = 1)
H3YN-4/-41 series: The minimum applicable load is 1 mA at 1 VDC (P reference value).
H3YN-4-Z/-41-Z series: The minimum applicable load is 1 mA at 1 VDC (P reference value).
Contact materials: Au-clad + Ag-alloy
Ambient operating temperature -10°C to 50°C (with no icing)
Storage temperature -25°C to 65°C
Ambient operating humidity 35% to 85%
H3YN
11
Characteristics
*1. Terminal screw sections are excluded.
*2. The destructive shock resistance test was performed on the Timer.
*3. Refer to the Life-test Curve.
*4. Overvoltage category II.
*5. CCC certification requirements
Item H3YN-2/-21/-4/-41
Accuracy of operating time ±1% FS max. (1 s range: ±1%±10 ms max.)
Setting error ±10%±50 ms FS max.
Reset time Min. power-opening time: 0.1 s max. (including halfway reset)
Influence of voltage ±2% FS max.
Influence of temperature ±2% FS max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min
(between current-carrying terminals and exposed non-current-carrying metal parts) *1
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output)
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model)
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions
Shock resistance Destruction: 1,000 m/s2 *2
Malfunction: 100 m/s2
Life expectancy
Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: DPDT:
500,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
4PDT:
200,000 operations min. (H3YN-4-Z/-41-Z: 100,000 operations min.)
(3 A at 250 VAC, resistive load at 1,800 operations/h) *3
Impulse withstand voltage
Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC, 24 VAC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC, 24 VAC
Noise immunity ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 4 kV
Degree of protection IP40
Weight Approx. 50 g
EMC
(EMI) EN 61812-1
Emission Enclosure: EN 55011 Group 1 class A
Emission AC Mains: EN 5CCC: GB/T 14048.5 5011 Group 1 class A
(EMS) EN 61812-1
Immunity ESD: IEC 61000-4-2
Immunity RF-interference: IEC 61000-4-3
Immunity Burst: IEC 61000-4-4
Immunity Surge: IEC 61000-4-5
Immunity Conducted Disturbance: IEC 61000-4-6
Immunity Voltage Dip/Interruption: IEC 61000-4-11
Approved standards
UL 508, CSA C22.2 No. 14, Lloyds, CCC: GB/T 14048.5 *5
Conforms to EN 61812-1 and IEC 60664-1. (2.5 kV/2 for H3YN-2/-21, 2.5 kV/1 for H3YN-4/-41,
H3YN-4-Z/-41-Z) *4
Model H3YN-2/-21 H3YN-4/-41
Recommended fuse RT14-20/6A (380 VAC 6 A),
manufactured by DELIXI RT14-20/4A (380 VAC 4 A), manufactured by DELIXI
Rated operating voltage Ue
Rated operating current Ie
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
AC-15: Ue: 250 VAC, Ie: 2 A
AC-13: Ue: 250 VAC, Ie: 3 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
Rated insulation voltage 250 V
Rated impulse withstand voltage
(altitude: 2,000 m max.) 2.5 kV (at 240 VAC)
Conditional short-circuit current 1000 A
H3YN
12
Life-test Curve (Reference Value)
500
100
50
20
500
100
50
20
500
100
50
20
500
100
50
20
500
100
50
10
6
H3YN-2/-21
H3YN-4/-41
H3YN-4-Z/-41-Z
Switching operations (x 104)
Load current (A)
Switching operations (x 104)
Load current (A)
Switching operations (x 104)
Load current (A)
Switching operations (x 104)
Load current (A)
Switching operations (x 104)
Load current (A)
250 VAC, resistive load
250 VAC, cosφ = 1
24 VDC, cosφ = 1
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 5 VDC (P reference value)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
250 VAC, cosφ = 1
24 VDC, cosφ = 1
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 1 VDC (P reference value)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
24 VDC,
resistive load
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
The minimum applicable load is 0.1 mA at 1 VDC (P reference value
H3YN
13
Connections
Connection
Pulse Operation
A pulse output for a certain period can be obtained with a random external input signal.
Use the H3YN in interval mode as shown in the following timing charts.
Mode Terminals
Pulse operation
Power supply between 9 and 14
Short-circuit between 5 and 13
Input signal between 9 and 13
Operating mode; interval and all other modes Power supply between 13 and 14
UP PW
H3YN-2/-21
DIN Indication DIN Indication
UP PW
Timer
circuit
Timer
circuit
H3YN-4/-41
H3YN-4-Z/-41-Z
(Bottom View) (Bottom View)
H3YN-2/-21
External input
Power (9-14)
Power (9-14)
External input
H3YN-4/-41
H3YN-4-Z/-41-Z
Timer
circuit
Timer
circuit
External short circuit
(5-13)
External input
(9-13)
Time limit contact
NO (12-8)
Time limit contact
NC (12-4)
Run/Power indicator
(PW)
Output indicator (UP)
50 ms
min.
Note: t: Set time
Rt: Reset time
External short circuit
(5-13)
External input
(9-13)
Time limit contact NO
(10-6, 11-7, 12-8)
Time limit contact NC
(10-2, 11-3, 12-4)
Run/Power indicator
(PW)
Output indicator (UP)
50 ms
min.
Note: t: Set time
Rt: Reset time
!Caution
Be careful when connecting wires.
H3YN
14
Nomenclature
Dimensions (Unit: mm)
Timers
Run/Power Indicator (Green)
(Lit: Power ON)
Output Indicator (Orange)
(Lit: Output ON)
Main Dial
Set the desired time according
to time range selectable by
DIP switch.
6.4
(63.0)
H3YN-2/-21 Front Mounting
Fourteen, 3 × 1.2 elliptic holes
28 max.
21.5 max.
28 max.
21.5 max.
Eight, 3 × 1.2 elliptic holes
H3YN-4/-41 Front Mounting
H3YN-4-Z/-41-Z
Mounting Holes
Eight,
1.3-dia. holes
Pin 1
Mounting Holes
Fourteen,
1.3-dia. holes
Pin 1
H3YN
15
Operation
DIP Switch Settings
The 1-s range and ON-delay mode for H3YN-2/-4/-4-Z, the 1-min range and ON-delay mode for H3YN-21/-41/-41-Z are factory-set before shipping.
Time Ranges
Note: The top two DIP switch pins are used to select the time ranges.
Operating Modes
Note: The bottom two DIP switch pins are used to select the operating mode.
Model Time range Time setting
range Setting Factory-set
H3YN-2,
H3YN-4
H3YN-4-Z
1 s 0.1 to 1 s Yes
10 s 1 to 10 s No
1 min 0.1 to 1 min No
10 min 1 to 10 min No
H3YN-21,
H3YN-41
H3YN-41-Z
1 min 0.1 to 1 min Yes
10 min 1 to 10 min No
1 h 0.1 to 1 h No
10 h 1 to 10 h No
Operating mode Setting Factory-set
ON-delay Yes
Interval No
Flicker OFF-start No
Flicker ON-start No
H3YN
16
Timing Chart
Note: t: Set time
Rt: Reset time
Operating mode Timing chart
H3YN-2/-21 H3YN-4/-41
ON-delay
Power
Output
Power (13-14)
Time limit contact
NC (9-1, 12-4)
Time limit contact
NO (9-5, 12-8)
Run/Power indicator
(PW)
Output indicator
Power (13-14)
Time limit contact
NC (9-1, 10-2, 11-3,
12-4)
Time limit contact
NO (9-5, 10-6, 11-7,
12-8)
Run/Power indicator
(PW)
Output indicator
(UP)
Interval
Power
Output
Power (13-14)
Time limit contact
NC (9-1, 12-4)
Time limit contact
NO (9-5, 12-8)
Run/Power
indicator (PW)
Output indicator
(UP)
Power (13-14)
Time limit contact
NC (9-1, 10-2, 11-3,
12-4)
Time limit contact
NO (9-5, 10-6, 11-7,
12-8)
Run/Power
indicator (PW)
Output indicator
(UP)
Flicker OFF-start
Power
Output
Power (13-14)
Time limit contact
NC (9-1, 12-4)
Time limit contact
NO (9-5, 12-8)
Run/Power indicator
(PW)
Output indicator
(UP)
Power (13-14)
Time limit contact
NC (9-1, 10-2, 11-3,
12-4)
Time limit contact
NO (9-5, 10-6, 11-7,
12-8)
Run/Power indicator
(PW)
Output indicator
(UP)
Flicker ON-start
Power
Output
Power (13-14)
Time limit contact
NC (9-1, 12-4)
Time limit contact
NO (9-5, 12-8)
Run/Power
indicator (PW)
Output indicator
(UP)
Power (13-14)
Time limit contact
NC (9-1, 10-2, 11-3,
12-4)
Time limit contact
NO (9-5, 10-6, 11-7,
12-8)
Run/Power
indicator (PW)
Output indicator
(UP)
17
Solid-state Timer
H3Y-@-B
Miniature Timer Compatible with the MY
Relay
UL listed when used with a Push-In Plus Terminal Block Socket. *
Conforms to CSA, CE Marking, CCC and LR.
Black design with power supply terminals on top and contact output
terminals on bottom.
Large transparent time setting knob facilitates time setting.
A flat-blade and Phillips screwdriver can also be used for time setting.
Semi-multi power supply voltage.
*When used in combination with a Push-In Plus Terminal Block Socket (PYF-@-PU-L).
Ordering Information
Note: Sockets and Hold-down Clips are not included with the H3Y-B. They must be ordered separately.
*Use the H3Y-4-B Series when switching micro loads.
Accessories (Order Separately)
Hold-down Clips
Note: For details, refer to Precautions for H3Y-series Timers on page 31.
Socket
Note: 1. Cannot be used with the H3Y-@-0 (PCB terminals).
2. For details, refer to Precautions for H3Y-series Timers on page 31.
Operation/resetting
system Time-limit contact Time ranges Supply voltage
Mounting
Surface/DIN-track mounting
(with socket)
Time-limit operation/
self-resetting
DPDT
(for power switching) 0.04 s to 3 h
100 to 120,
200 to 230 VAC (50/60 Hz);
12, 24, 48, 100 to 110 VDC
H3Y-2-B
4PDT H3Y-4-B *
Name/specification Model
Hold-down Clips For PYF-@-PU-L Y92H-3
For the most recent information on models that
have been certified for safety standards, refer to
your OMRON website.
LR
Refer to Safety Precautions on page 36.
Timer Square Sockets
Contact Model Pin Connection Terminal Model Terminal Type
DPDT H3Y-2-B 8-pin Front Connecting DIN track mounting PYF-08-PU-L Push-In Plus Terminal Block
4PDT H3Y-4-B 14-pin Front Connecting DIN track mounting PYF-14-PU-L Push-In Plus Terminal Block
H3Y-@-B
18
Specifications
Time Ranges
Ratings
*1. Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Timers for details on your OMRON website.
*2. With DC ratings, single-phase full-wave rectified power sources may be used.
*3. Only the H3Y-2-B Series include 12 VDC models.
*4. Use the Timer within 90% to 110% of the rated supply voltage (95% to 110% for 12 VDC) when using it continuously under an ambient
operating temperature of 50°C.
*5. Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC: 10 VAC max.
200 to 230 VAC: 20 VAC max.
100 to 110 VDC: 10 VDC max.
*6. Refer to Safety Precautions for All Timers on your OMRON website when combining the Timer with an AC 2-wire proximity sensor.
*7. A diode to prevent reverse voltages is provided only on models with a DC power supply.
Rated time Time setting range Rated time Time setting range
0.5 s 0.04 to 0.5 s 3 min 0.1 to 3 min
1 s 0.1 to 1 s 5 min 0.2 to 5 min
5 s 0.2 to 5 s 10 min 0.5 to 10 min
10 s 0.5 to 10 s 30 min 1 to 30 min
30 s 1.0 to 30 s 60 min 2 to 60 min
60 s 2.0 to 60 s 3 h 0.1 to 3 h
120 s 5.0 to 120 s --- ---
Item H3Y-2-B/H3Y-4-B
Rated supply voltage *6, *7100 to 120 (50/60 Hz), 200 to 230 VAC (50/60 Hz), 24 VAC (50/60 Hz) *1
12, 24, 48, 125, 100 to 110 VDC *2, *3
Operating voltage range All rated voltages except 12 VDC: 85% to 110% of rated supply voltage
12 VDC: 90% to 110% of rated supply voltage *4
Reset voltage 10% min. of rated supply voltage *5
Power consumption
100 to 120 VAC: 1.5 VA (at 120 VAC)
200 to 230 VAC: 1.8 VA (at 230 VAC)
24 VAC: 1.5 VA (at 24 VAC)
12 VDC: 0.9 W (at 12 VDC)
24 VDC: 0.9 W (at 24 VDC)
48 VDC: 1.0 W (at 48 VDC)
100 to 110 VDC: 1.3 W (at 110 VDC)
125 VDC: 1.3 W (at 125 VDC)
Control outputs
H3Y-2-B:
5 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 5 VDC (P reference value).
Contact materials: Ag
H3Y-4-B:
3 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 1 VDC (P reference value).
Contact materials: Au-clad + Ag-alloy
Ambient operating temperature -10°C to 55°C (with no icing)
Storage temperature -25°C to 65°C
Ambient operating humidity 35% to 85%
H3Y-@-B
19
Characteristics
*1. Add ±10 mS to the above value for the 0.5-S range model.
*2. Terminal screw sections are excluded.
*3. The destructive shock resistance test was performed on the Timer.
*4. Check the electrical life curve.
*5. cULus listing applies when the OMRON PYF-@-PU-L is used.
cURus recognition applies when any other socket is used.
*6. Overvoltage category II.
*7. CCC certification requirements
Accuracy of operating time ±1% FS max. (0.5 s range: ±1%±10 ms max.) *1
Setting error ±10%±50 ms FS max.
Reset time Min. power-opening time: 0.1 s max. (including halfway reset)
Influence of voltage ±2% FS max. *1
Influence of temperature ±2% FS max. *1
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min
(between current-carrying terminals and exposed non-current-carrying metal parts) *2
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output) *2
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) *2
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Impulse withstand voltage
Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC
Noise immunity ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 4 kV
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude
Shock resistance Destruction: 1,000 m/s2 (approx. 100G) *3
Malfunction: 100 m/s2 (approx. 10G)
Life expectancy
Mechanical:10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
H3Y-2-B: 500,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h)
H3Y-4-B: 200,000 operations min. (3 A at 250 VAC, resistive load at 1800 operations/h) *4
Enclosure rating IP40
Weight Approx. 50 g
EMC
(EMI) EN 61812-1
Emission Enclosure: EN 55011 Group 1 class A
Emission AC Mains: EN 55011 Group 1 class A
(EMS) EN 61812-1
Immunity ESD: IEC 61000-4-2
Immunity RF-interference: IEC 61000-4-3
Immunity Burst: IEC 61000-4-4
Immunity Surge: IEC 61000-4-5
Immunity Conducted Disturbance: IEC 61000-4-6
Immunity Voltage Dip/Interruption: IEC 61000-4-11
Approved standards UL 508/CSA C22.2 No.14 *5, CSA C22.2 No.14, Lloyds, CCC: GB/T 14048.5 *7
Conforms to EN 61812-1 and IEC 60664-1. (2.5 kV/2 for H3Y-2-B *6, 2.5 kV/1 for H3Y-4-B *6)
Model H3Y-2-B H3Y-4-B
Recommended fuse RT14-20/6A (380 VAC 6 A), manufactured by
DELIXI
RT14-20/4A (380 VAC 4 A), manufactured by
DELIXI
Rated operating voltage Ue
Rated operating current Ie
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
AC-15: Ue: 250 VAC, Ie: 2 A
AC-13: Ue: 250 VAC, Ie: 3 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
Rated insulation voltage 250 V
Rated impulse withstand voltage
(altitude: 2,000 m max.) 2.5 kV (at 240 VAC)
Conditional short-circuit current 1000 A
H3Y-@-B
20
Engineering Data
Connections
Connections
H3Y-2-B
Switching operations (×104)
Load current (A)
H3Y-2-B
H3Y-4-B
Load current (A)
Load current (A)
H3Y-4-B
Load current (A)
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both
cases, a life of 100,000 operations can be expected.The minimum
applicable load is 1 mA at 5 VDC (P reference value).
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both
cases, a life of 100,000 operations can be expected.The minimum
applicable load is 1 mA at 1 VDC (P reference value).
Switching operations (×104)
Switching operations (×104)
Switching operations (×104)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
250 VAC, cosφ = 1
24 VDC, cosφ = 1
250 VAC, cosφ = 1
24 VDC, cosφ = 1
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
500
100
50
20
500
100
50
20
500
100
50
20
500
100
50
20
H3Y-2-B H3Y-4-B
Connect the DC power supply to
terminals A1(13) and A2(14)
according to the polarity marks.
Connect the DC power supply to
terminals A1(13) and A2(14)
according to the polarity marks.
(Bottom View) (Bottom View)
(DIN notation) (DIN notation)
A2
(14)
11
(9)
41
(12)
A1
(13) 44
(8)
12
(1)
14
(5)
42
(4)
PW UP
A2
(14)
41
(12)
A1
(13)
11
(9)
44
(8)
14
(5)
12
(1)
42
(4)
Timer
circuit A2
(14)
UP
PW
44
(8)
41
(12)
42
(4)
34
(7)
31
(11)
32
(3)
24
(6)
21
(10)
22
(2)
12
(1)
11
(9)
A2
(14)
A1
(13)
21
(10)
31
(11)
41
(12)
14
(5)
22
(2)
24
(6)
32
(3)
34
(7)
42
(4)
44
(8)
14
(5)
11
(9)
12
(1)
A1
(13)
Timer
circuit