Relay Coupler 58 Relay Coupler Contact material Properties Application Fine silver AG 99 % - inexpensive - average tendency to weld and average resistance to burn-off - subject to corrosion in sulphurous atmosphere - high mechanical stability - low tendency to weld - low contact resistance - high resistance to burn-off - mechanical stability > AgNi - tendency to weld < AgNi - resistance to burn-off > AgNi - contact resistance > AgNi - very low tendency to weld - resistance to burn-off > AgCu3/Ni universal use 1 V...250 V up to medium-size loads 1 mA...5 A Silver nickel AgNi 0.15 Hard silver AgCu3 Silver cadmium oxide AgCdO Silver-tinoxide AgSnO2 Tungsten W Hard gold AuNi universal use at medium-size loads U/I 12 V 5 mA...10 A for use with medium-size 12 V loads 10 mA...10 A suitable for switching inductive loads 12 V 100 mA - high thermal decomposition temperature - more arc-resistant with low material transfer suitable for swiching inductive loads 12 V 100 mA - circuits with extremely high on/off loads dry circuits in damp atmospheres 60 V 1A V...60 V A...0.2 V very high resistance to burn-off high switching rate with short closed times < lowest contact resistance best resistance to corrosion = preferred materials Types of contact Contact material The standard range comprises numerous types and combinations of contacts. 1 NC (EGR EG2, EGR EG7, RS 30) 1 NO (EGR EG2, EGR EG7, DKR, RS 30) 1 NC and 1 NO (EGR EG2, WRS) 2 NO (WRS) 3 NO (WRS) 1 Changeover (EGR EG2, EGR/RST EG7, WRS DKR PRS/PRZ MCZ R, RS 30, RS 31) 2 Changeover (EGR EG2, WRS, RS 32, PRS/PRZ) 4/8/16 Changeover (RSM) The all-round capability of Weidmuller relay modules is achieved by the choice of the contact material. The contact is responsible for both the reliable transmission of the control signals and for switching power contactors. Weidmuller uses gold-plated or goldflashed AgNi contacts for most applications. Gold-plated contacts permit the switching of the low-power applications up to 40 W with a gold-plating thicker than 2 m. For switching higher ratings we use AgSnO2 or AgCdO contacts (RS 31). 59 Digital signal processing The universal foot of the Weidmuller relay modules allow them to be assembled on TS 32, TS 35 x 7.5 and TS 35 x 15 mounting rails in accordance with European standards EN 50 035 and EN 50 022. An LED status indicator in the coil of the relay coupler indicates the relay switching status. Relay Coupler Protective circuits of the contacts Switching sparks may occur when switching inductive or capacitive loads that affect the operational life of the relay. The following protective circuits offer the possibility of reducing contact wear: Diode: + - US Last UD Load Switching of small and large power ratings For automation technology, Weidmuller offers the EGR EGR 7 relay coupler to switch ratings up to 40 W under resistive loads. This allows signals to be reliably relayed to control devices. The switching of higher power ratings in power supply technology is achieved by the RS 31 relay coupler, which guarantees switching capacity up to 3.5 kVA under resistive loads. Switching times of the relay modules 1 Advantage: 2 t can be used for all ratings, low overvoltage, minimum space requirements, economic pick-up delay drop-out delay typ. < 10 ms typ. < 12 ms Disadvantage: very long drop-out delay Switching behaviour/load limit curve (dependimg on type) Diode and Z-diode: Single contact US Last UZD Load 1 Advantage: 2 t The contact resistance is largely responsible for heat development within the relay. This link is demonstrated by a derating curve as a function of the permissible current subject to the ambient temperature. We determine the current (curve a) for the following operating conditions: - continuous operation - rated input voltage + 10 % - several relay modules operating under load, mounted horizontally in a row without spacing on mounting rail A higher load is applicable when modules are mounted with a gap of 20 mm as shown in curve "b". In addition, the function of curve "b" shows the max. values for a switching or short-time operation when assembled horizontally on the mounting rail. Number of operations + - Derating curves low overvoltage (determined by Zdiode), low drop-out delay Disadvantage: not usable for high power ratings Switching capacity (kVA) RC combination: + (~) US R Last URC Load C 1 Advantage: Notes for usage Direct current (A) - (~) Contact life with resistive load 2 t low overvoltage, low drop-out delay Disadvantage: higher current loading on contacts at switch-on, complex and expensive for increased power rating Direct Voltage (V) DC-limit with resistive load Varistor: + (~) Last RC combination US VDR Load UVDR 1 Advantage: 2 t Reduction factor F - (~) low drop-out delay, economic Disadvantage: not for all operating voltages and power ratings Power factor US 1 2 Voltage curve Close Open Reduction factor with inductive load cos j < 1 Switching no. eff. = switching no (at cos j = 1) x red. Factor F Relay couplers with plugged relays Relay couplers with plugged relays are only conditionally suitable for use in applications subject to heavy vibrations. Relay couplers with soldered relays are to be preferred. 60 The characteristic data of the actuation are to be meticulously observed when using UC variants in DC circuitry. UC variants have a higher current input at the moment of switching due to their series circuitry. The internal current limiter of commercially available initiators can result in the operated relay coupler not being switched through. Long supply cables are particularly open to electrical and electro-mechanical influences. These can lead to disturbances of the function or even failure of the relay module. A remedy for this problem is an RC combination in series that filters out unwanted disturbances. RC combinations are available for all customary relay couplers: pluggable (PLUGSERIES) or as terminal block (WDU 12C and DKU 12C). Definition of Technical Data All equipment required to guarantee "protective separation" must be constructed in such a way that, for example, a mechanical defect cannot reduce the level of insulation. In the case of a relay, this means that if a mechanical defect occurs (bent solder pin, break in winding conductor or broken spring), "protective separation" must be guaranteed. Relays are specified and tested according to IEC 255 and VDE 0435. Neither standard contains any reference to EN 50 178 (Equipping power installations with electronic equipment) nor is "protective separation" defined. To compound matters the test voltages quoted for the relays are based on different measurement conditions. The test voltages cannot be applied to EN 50 178 or DIN VDE 0106 Part 101. As more and more users employ only equipment that guarantees "protective separation", a lot of manufacturers of relays refer to DIN VDE 0106 and test their products accordingly. Consequently, the quoted values correspond to the requirements for "protective separation". Standards The following standards are fulfilled: EN 50 178 Equipping power installations with electronic equipment DIN VDE 0106 Part 101 Protection against flow of dangerous currents through the human body; basic requirements for protective separation within electrical equipment. DIN VDE 0109 Insulation co-ordination within low-voltage system including clearance and creepage distances for assembled PCBs. DIN VDE 0435 Electrical relays, all-or-nothing relays Input circuit Input voltage [V] Input current [mA] Rated power consumption [W/VA] Pull-in voltage [V] Pick-up current [mA] Pull-in power [W/VA] Drop-out voltage [V] Self reset current [mA] Reference voltage at which the relay coupler operates. Typical reference voltages: => 5 V DC, 12, 24, 48, 60, 115, 230 V AC/DC Quotient resulting from input voltage and input resistance. Input resistance => coil resistance + resistance of drive (R, LED, rect. ...) Input voltage x input current AC/DC with tolerance of +/- 10% or +5/-15% Typical range for relay coupler: 250 mW > Pv > 1 W 0.4 VA > Pv > 1.2 VA Smallest input voltage that relay coupler requires in order to respond (Tamb = 293 K) Smallest input current required to switch relay from inoperative to operating position (Tamb = 293 K) Product of pull-in voltage and pick-up current Voltage level at which relay has definitely released Input current level at which relay has definitely released Output circuit Output voltage [V] Switching current [A] Continuous current [A] Switching power [W/VA] Min. switching power [mW] Service life Pick-up lag [ms] Drop-out lag [ms] Contact bounce time [ms] Switching frequency [Hz] Withstand voltage [kV] Reliable separation Electric arc Contact wear Spark absorption Reduction factor Max. voltage that can be applied to relay contact Current that can flow for max. of 4 sec. after relay contact has closed Current that flows continuously after contact has closed Product of output voltage and switching current with resistive, inductive and capacitive load Smallest amount of power that can be switched via contact Number of switching operations before contact fails - mechanical => with no electric load - electrical => with resistive or inductive AC/DC load Length of time from application of energizing voltage until contact closes/opens Length of time from breaking the energizing circuit until contact closes/opens Length of time between first and last closing/opening of contact when relay picks up or drops out Switching operations per sec. with a duty factor of 1 : 2 (ton = toff) Max. test voltage between input and output circuits which does not cause any discharge Feature of relay coupler that conform to VDE 0160 and VDE 0106 Part 101 Current flow between contact surfaces as they open, caused by ionization Switching inductive loads leads to considerable changes in the composition of the materials used. The results are: => formation of pits or peaks on the surface of contacts => failure due to interlocking of contacts Limitation of transient overvoltages by connecting supplementary circuit across inductive loads => RC combinations => Z-diodes/suppressor diodes => varistors Factor by which service life is reduced when switching inductive loads Digital signal processing Protective separation 61 Types of Housings for Relay Coupler Component housing EG Component housing WAVEBOX Weidmuller coupling modules are enclosed in housings appropriate for industrial applications. The housings are suitable for fitting onto mounting rails TS 32, TS 35 x 7.5 or TS 35 x 15 in accordance with European standards EN 50 035 and EN 50 022. It is important to provide modern electronics components with housings suitable for the function. Setting and operating functions must be guaranteed; technical requirements with respect to heat dissipation and EMC properties are to be supported. An ideal design saves space and wiring costs in the switchgear cabinet. In addition, ergonomics and design are becoming increasingly important for high-quality relay coupler interfaces. The WAVEBOX fulfils these criteria and is further distinguished by the following: Optimal width for any application (12.5 mm, 17.5 mm, 22.5 mm) Large component assembly surface; SMDs mountable on solder side No tools required for assembly Pluggable PCBs Pluggable cross-connection via ZQV 2.5 N Hinged, transparent cover Screw/plug and socket connector BLZ 5.08 Optional tension clamp/plug and socket connector BLFZ 5.08 Marking option with WS tags Mount onto TS 35 Connection systems BLZ screw/plug-in connectors and BLZF tension clamp/plug-in systems for flexible conductors up to 2.5 mm2, to guarantee maximum wiring flexibility. Removing printed circuit boards Accomplished by depressing the locking clips at the side of the headpiece, and withdrawing the terminal level and PCB from the housing. This is not permitted when the supply is connected. Cross-connection The ZQV 2.5 N/2 cross-connector can connect housings of the same family at the base of the housing. The cross-connection can be loaded with a current of up to 8 A. This allows the supply voltage to be cross-connected from one electronics module to another. The voltage at the cross-connection must not exceed 50 V. Ventilation vents Ventilation vents, arranged at an angle, temper and ventilate the lower side of the housings. Weidmuller component housings EG 1 and EG 2 are 18 mm wide. The fully enclosed EG housings are equipped with clamping yoke screw connections or push-on connections to connect conductors. Conductors with the following cross-sections can be connected: solid core: 0.5...4 mm2 or flexible: 0.5...2.5 mm2. The component housing EG 7 has a special status. It has been specifically designed to accommodate 10-mm slim relays and optocouplers. EG 7 relay couplers can be optionally mounted onto TS 32 or TS 35 rails. The RST EG 7 locking socket is also available for use with the pluggable relays couplers. The enclosed EG 7 housing are equipped with clamping yoke screw connections. The following conductor cross-sections can be connected: NO/NC: 0.5...1.5 mm2 Changeover (RST): 0.5...2.5 mm2. 62 Modular system PLUGSERIES/PLUGRELAY is a new generation of pluggable relay couplers. The core of this system is an innovative relay socket PXS or PXZ. Weidmuller has combined the functionality and experience from its relay and terminal block business in this product. The PLUGRELAY is the ideal connection technology between the relay and the application. Modular system principle The PLUGSERIES is particularly service friendly. Commercially available relays are plugged; retainer and release clips ensure stability, LED indicators with free-wheeling diodes can be easily plugged. Relays can be easily plugged - suitable for small electric circuits standard design and BGD Independent connection technology: screw or tension clamp rated cross-section 0.5...2.5 mm2 Robust design of retainer / release clip One or two changeover contacts Max. current switched 16 A Low wiring costs thanks to ZQV 25N cross-connectors (pluggable) Service-friendly modular system - relay socket, LED indicators, retainer clips and relays - mount onto TS 35 - marking options with WS markers on retainer clips Pluggable LED indicator with free-wheeling diode Types of Housings for Relay Coupler Weidmuller RS locking socket Minicoupler DK MICROSERIES Locking sockets with relays RS 30, 31, 32 are either 11.2 mm or 25 mm wide depending on version. The open profile makes the use of pluggable relays possible. Modules mounted onto the locking sockets are provided with clamping yoke screw connections or push-on connectors for wiring conductors. Conductors with the following cross-sections can be connected: solid core: 0.5...4 mm2 flexible: 0.5...2.5 mm2. All DKR mini coupler components fulfil demands for slimmest possible design. The sensational width of only 6 mm is achieved by using state-of-the-art surface mountable components SMDs. 4 and 5 screw-connections are offered for 0.5...4 mm2 conductor cross-sections. The mini couplers offer a wide spectrum for coupling digital sensor/actuator signals between automation devices and the field process. DKR relay couplers can receive and standardise signals with varying voltages from the field. The relay coupler and optocoupler variants from the MICROSERIES are used in applications in industrial automation to isolate and couple digital input and output signals. Their compact design means that they are particularly suitable for use on sub-distribution boards as well as in switchgear cabinets where they help the user to make optimum use of valuable switching space. With its compact design, the MICROSERIES elegantly combines the functionality of the classic coupling level and the terminal level. Locking sockets with multiple interfaces Miniconditioner MCZ 6.1-mm mounting width Pluggable cross-connections of four potentials in the inputs and outputs Proven cross-connection system ZQV 4 N Wide input voltage spectrum from 5 ... 230 V Digital signal processing RSM multiple interfaces can be optionally assembled with 4, 8 or 16 relays. To save wiring costs on the input side, variants are offered with joint positive and negative potentials. The PCB connectors are provided with clamping yoke screw connections for conductors with the following cross-sections: solid core: 0.5...4 mm2 or flexible: 0.5...2.5 mm2. Some versions of the RSM coupler have a male connector block available for connecting pre-assembled cables on the input side in accordance with IEC 603-1/DIN 41 651. The 6-mm MCZ housing is one of the slimmest of its kind. It has the following distinguishing features: - Z-spring reduces mounting costs - integrated cross-connection options in the input and outputs minimise wiring costs MCZR miniconditioner (relay coupler) are available with 4 or 5 Z-spring connections. The clampable conductor cross-section is 0.5...1.5 mm2. LED-indicator reverse-connect protection free-wheeling diode Housing material: WEMID Flammability class: V0 in accordance with UL 94 Innovative retaining and release system Marking surfaces for fitting standard WS 12/6 markers CE-marking Weidmuller relay couplers are marked with the CE symbol and comply with the requirements of EN 50 081 Part 1 and EN 50 082 Part 2. They can therefore be used for both industrial as well as for applications in residential, commercial and light industry. Appropriate ESD measures should be taken during installation. If supply cables are particularly long, overvoltage protection should be provided to prevent interference from electrical disturbance in the atmosphere. 63 Relay Coupler Electromechanical switching Output 24 V 2x Housing EG 0133660000 Page 72 0536260000 Page 72 3x 0133560000 2x 4x 8x 16 x 1173461001 1113161001 1113261001 1113361001 1100061001 1100161001 1113461001 1113561001 1113761001 1112361001 1113661001 8018221001 1112761001 1107761001 1107861001 1112661001 1113861001 1173561001 1113061001 0160260000 Page 72 Page 73 0542660000 0123060000 Page 72 Page 73 WAVESERIES 8275350000 8418240000 8418270000 WRS 8286280000 8418250000 8418280000 Page 79 8416210000 Page 76 8418220000 Page 77 8418330000 8418300000 8418310000 8418320000 Page 78 8418230000 Page 74 EG 7* 8216520000 8216530000 8216570000 8147120000 8147140000 8216560000 8092340000 8092350000 Page 80 Page 80 8216580000 Page 80 PLUGSERIES PRS / PRZ 8530621001 8530701001 8536530000 8536560000 8536650000 Page 82 RS 30 1101661001 1100961001 1181511001 1101611001 1100911001 1181521001 1101621001 1100921001 1100260000 1101761001 1101061001 1100210000 1101711001 1101011001 1100220000 1101721001 1101021001 Page 91 RS 31 Page 91 8530631001 8530691001 8536680000 Page 82 1100360000 Page 91 1128361001 1128331001 1128311001 Page 92 RS 32 9406121001 9406221001 Page 94 RSM Page 97 Page 97 1173661001 Page 97 DKR 32 8016620000 8008110000 Page 70 DKR 35 8016610000 8008170000 Page 70 8181980000 8181970000 Page 71 8215620000 Page 71 DKR 35/32 9454910000 Page 71 MCZ R 8365980000 8442960000 8390590000 Page 68 MICROSERIES MRS / MRZ 8533640000 8533660000 8556050000 8556120000 Page 87 * Approval by Germanischer Lloyd Reliable separation 64 24 V dc 24 Vuc/ac Relay Coupler Electromechanical switching Output 48 V 2x Housing EG 0662660000 Page 72 3x 0662460000 2x 4x 8x 16 x 0160360000 0123260000 Page 72 Page 73 WAVESERIES 8286280000 WRS EG 7* Page 74 8092370000 Page 81 RS 30 1101861001 1101811001 1101821001 1101961001 1101911001 1101921001 Page 91 8092380000 Page 81 8418250000 Page 76 8418280000 Page 77 8418310000 Page 78 8216590000 Page 81 1101161001 1100460000 1101111001 1100410000 1101121001 1100420000 1101261001 1100560000 1101211001 Page 91 1101221001 Page 91 RS 31 1150761001 Page 92 RS 32 9406321001 Page 94 9406421001 1122661001 Page 95 RSM 1114061001 1114161001 1113961001 1114261001 1112461001 Page 97 1173761001 1114361001 1114461001 Page 97 Page 97 MICROSERIES MRS / MRZ 8556040000 8556110000 115 V EG Digital signal processing Page 87 0141360000 0160460000 Page 73 WAVESERIES 8418220000 WRS EG 7* Page 75 8092430000 Page 81 8092440000 Page 81 Page 82 Page 91 RS 31 Page 77 8216610000 8536510000 8536610000 8530640000 8530790000 1155161001 1155111001 1155121001 1102161001 1102111001 1102121001 Page 76 8418290000 Page 81 PLUGSERIES PRS / PRZ RS 30 8418260000 8536520000 8536630000 8530660000 8530720000 Page 82 1155211001 1155261001 1155221001 1101461001 1101411001 1101421001 Page 91 1150361001 1150461001 Page 92 RS 32 1122761001 9406621001 Page 95 RSM 1114561001 Page 97 MCZ R 1114661001 Page 97 1114761001 Page 97 8420880000 8467470000 Page 61 MICROSERIES MRS / MRZ 8556030000 8556100000 Page 87 * Approval by Germanischer Lloyd Reliable separation Vdc Vuc/ac 65 Relay Coupler Electromechanical switching Output 230 V 2x Housing EG 0543860000 Page 72 0543660000 8418230000 Page 75 8092470000 8178200000 Page 81 Page 81 8418260000 Page 76 8418290000 Page 77 8418340000 Page 79 8418320000 Page 78 Page 81 8530731001 Page 82 1102261001 1101561001 1102211001 1101511001 Page 91 1102221001 16 x 8216620000 8530671001 Page 91 8x 8216630000 PLUGSERIES PRS / PRZ RS 30 4x Page 73 WRS 8092460000 2x 0142460000 Page 72 WAVESERIES EG 7* 3x 8530681001 8530741001 Page 82 1100860000 1101521001 Page 91 RS 31 1128461001 1128431001 1128411001 Page 93 RS 32 9406721001 1122761001 Page 95 RSM 1114861001 1114961001 1115061001 1123461001 1108061001 1108261001 Page 97 MCZ R 8237710000 Page 69 MICROSERIES MRS / MRZ 8556020000 8556090000 Page 87 240 V RS 30 1128561001 1128661001 1128511001 1128611001 1128521001 Page 91 1128621001 Page 91 * Approval by Germanischer Lloyd Reliable separation 66 230 Vuc/ac Page 97 Page 97 Relay Coupler Electromechanical switching Output 12 V 2x 3x Housing EG 2x 4x 8x 16 x 4x 8x 16 x 0160160000 Page 73 WAVESERIES 8418240000 WRS EG 7* Page 76 8092310000 Page 80 8092320000 Page 80 8418270000 8418300000 Page 77 Page 78 8216550000 Page 80 PLUGSERIES PRS / PRZ 8536471001 8536501001 8536571001 8536591001 Page 82 RS 30 1129421001 Page 91 1129521001 Page 91 Page 82 1129660000 Page 91 RS 32 9406021001 Page 94 DKR 35 8171100000 Page 70 MICROSERIES MRS / MRZ 8556070000 8556140000 Page 86 Output 2x Housing WAVESERIES Page 74 WAVESERIES 8418210000 WRS 60 V Page 74 8092400000 Page 81 RS 30, 60 V 8092410000 Page 81 8216600000 Page 81 1102061001 1100660000 1102011001 1100610000 1102021001 Page 91 DKR 32, 5 V 2x 8275320000 WRS 2, 4...24 V EG 7*, 60 V 3x Digital signal processing 4...60 V 9406521001 Page 94 1100620000 Page 91 8019600000 Page 70 DKR 35, 5 V 8019610000 Page 70 MCZ R, 60 V 8470380000 Page 68 MICROSERIES MRS / MRZ, 5 V 8556080000 8556150000 Page 86 MICROSERIES MRS / MRZ, 60 V 8556060000 8556130000 Page 87 * Approval by Germanischer Lloyd Reliable separation Vdc Vuc/ac 67 Relay Couplers in Component Housings Miniconditioners MCZ R MCZ R 24 Vdc MCZ R 24 Vdc/Au Limit diagram MCZ R 24 Vac/dc MCZ R 60 Vdc Derating curve rowed without clearances on the mounting rail rowed with 20 mm spacing on the mounting rail U/Vdc IL/A 300 6 5 prohibited area 200 4 3 100 2 25 1 1 2 3 4 5 6 IL/Adc 20 25 30 35 40 45 50 C Schematic circuit diagram This module can be used as a universal interface between the controller and actuator for switching medium-sized loads. Reduces installation and commissioning times by use of the proven Z-spring connection technology Pluggable cross-connections in input and output minimise wiring costs 6-mm width Ordering data for TS 35 Type MCZ R 24 Vdc Technical data Input Input voltage Input current at UN Type Cat. No. MCZ R 24 Vdc/Au 8442960000 Type Cat. No. MCZ R 24 Vac/dc 8390590000 Type MCZ R 60 Vdc 24 Vdc 20 % (19.2...28.8 V) 6.3 mA 10 % (5.7...6.9 mA) 24 Vdc 20 % (19.2...28.8 V) 6.3 mA 10 % (5.7...6.9 mA) 60 Vdc 20% (48...72 V) 3 mA 20 % (12.4...3.6 mA) Max. input power 156 mW 10% 156 mW 10% Making threshold Cut-out threshold Reaction time at UN (typ.) Release at UN (typ.) Capacity working resistance to reduction at dissipated energy Functionality 12 V...19 V 4 V...5.5 V 4.5 ms 10 ms no operating indication reverse polarity protect. diode free wheel diode 2, 3, 4 1 changeo. cont. (AgSnO2) max. 300 Vdc / 400 Vac max. 6 A / max. 1500 VA 100 mA (at U = 10 V) max. 6 A see limit diagram 20 x 106 switching operations 0.1 Hz 12 V...19 V 4 V...5.5 V 4.5 ms 10 ms no operating indication reverse polarity protect. diode free wheel diode 2, 3, 4 1 changeo. cont. (5 Au) max. 300 Vdc / 400 Vac max. 6 A* / max. 1500 VA 1) 0.1 mA max. 6 A* see limit diagram 20 x 106 switching operations 0.1 Hz 24 Vac/dc 10% (21.6...26.4 V) ac: 10.8 mA15% (9.2...12.4 mA) dc: 6.1 mA 15% (5.2...7.1 mA) ac: 160 mVA 10 % dc: 151 mW 10 % ac: ca. 17 V / dc: ca. 19 V ac: ca. 7 V / dc: ca. 4 V 5 ms 30 ms no operating indication bridge rectifier 2, 3, 4 1 changeo. cont. (AgSnO2) max. 300 Vdc / 400 Vac max. 6 A / max. 1500 VA 100 mA (at U = 10 V) max. 6 A see limit diagram 20 x 106 switching operations 0.1 Hz ca. 38 V ca. 14 V 4.5 ms 10 ms no operating indication reverse polarity protect. diode free wheel diode 2, 3, 4 1 changeo. cont. (AgSnO2) max. 300 Vdc / 400 Vac max. 6 A / max. 1500 VA 100 mA (at U = 10 V) max. 6 A see limit diagram 20 x 106 switching operations 0.1 Hz 300 V 4 kV III 2 5.5 mm 4 kVeff / 1 min -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA, GL 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 300 V 4 kV III 2 5.5 mm 4 kVeff / 1 min -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA, GL 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 300 V 4 kV III 2 5.5 mm 4 kVeff / 1 min -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA, GL 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 300 V 4 kV III 2 5.5 mm 4 kVeff / 1 min -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 Cross-connection on pin Output Switching voltage ac: continuous current/switching power (see derating diagram) Min. switching current Switch-on current dc: Continuous current/switching power Mechanical service life Max. switching frequency at nominal load Insulation coordination acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances Insulation coord.- and voltage proof, input/output mounting rail Ambient temperature Storage temperature Conductor Conductor cross-section Approvals Overall width Accessories End plate Further accessories, dimensions and connection data see 68 Cat. No. 8365980000 1) depends on load conditions * the hard-gold plating is resistant for parameters 36 Vdc, 50 mA with 106 cycles Cat. No. 8470380000 180 mW 45 % Relay Couplers in Component Housings MCZ R 110 Vdc MCZ R 120 Vac MCZ R 230 Vac Limit diagram Derating curve rowed without clearances on the mounting rail rowed with 20 mm spacing U/Vdc IL/A 300 6 5 prohibited area 200 4 3 2 25 1 1 2 3 4 5 6 IL/Adc 20 25 30 35 Type Cat. No. MCZ R 110 Vdc 8467470000 Type Cat. No. MCZ R 120 Vac 8420880000 Type Cat. No. MCZ R 230 Vac 8237710000 110 Vdc 10% 2.85 mA 25% 120 Vac -15 %/+10 % 7 mA 15 % 230 Vac 10% 9.5 mA 15 % (8...11mA) 340 mW 25% 2.1 VA 15 % ca. 68 V / 1.6 mA ca. 19 V / 0.4 mA 4.5 ms 10 ms no operating indication bridge rectifier 0.85 VA 15 % ( 380 mW 15 %) ca. 70 V / 4 mA ca. 22 V / 1.3 mA 8 ms 30 ms yes operating indication bridge rectifier 2, 3, 4 1 changeo. cont. (AgSnO2) max. 300 Vdc / 400 Vac max. 6 A / max. 1500 VA 100 mA (at U = 10 V) max. 6 A see limit diagram 20 x 106 switching operations 0.1 Hz 2.3, 4 1 changeo. cont. (AgSnO2) max. 300 Vdc / 400 Vac max. 6 mA / max. 1500 VA 100 mA (at U = 10 V) max. 6 A see limit diagram 20 x 106 switching operations 0.1 Hz 2.3, 4 1 changeo. cont. (AgSnO2) max. 300 Vdc / 400 Vac max. 6 A / max. 1500 VA 100 mA (at U = 10 V) max. 6 A see limit diagram 20 x 106 switching operations 0.1 Hz 300 V 4 kV III 2 5.5 mm 4 kVeff / 1 min -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 300 V 4 kV III 2 5.5 mm 4 kVeff / 1 min -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 300 V 4 kV III 2 5.5 mm 4 kVeff / 1 min -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 40 45 50 C Digital signal processing 100 ca. 115 V / 5 mA ca. 60 V / 2.5 mA 8 ms 30 ms no operating indication bridge rectifier 69 Relay Couplers in Component Housings Mini coupler DKR These modules are used for protective separation of input signals and adjustment of signal levels DKR 5 Vdc DKR 12 Vdc DKR 24 Vac/dc DKR 24 Vdc Type Cat. No. DKR 24 Vac/dc 8008110000 DKR 24 Vac/dc 8016610000 Type DKR 24 Vdc DKR 24 Vdc Cost-effective solution for adjustment of power and potential Low input power Screw connection technology 6-mm width Schematic circuit diagram Ordering data for TS 32 for TS 35 With combination foot TS 32/TS 35 Technical data Input voltage Input current Input current, limited = SPS able Input power Pick-up lag Turn off delay Y W Type DKR 5 Vdc DKR 5 Vdc Cat. No. 8019600000 8019610000 Type DKR 12 Vdc Cat. No. 8171100000 Cat. No. 8016620000 8008170000 Input: bottom 5 Vdc 5 % 12.5 mA Input: bottom 12 Vdc 10 % 12 mA Input: bottom 24 Vac/dc 20 % 11.5 mAac/9 mAdc Input: bottom 24 Vdc 20 % 9.3 mA 65 mW typ. 0.7...2.5 ms typ. 0.2...2.0 ms 144 mW typ. 0.7...2.5 ms typ. 0.2...2.0 ms 300 mVA/220 mW 0.6...4.5 ms ac/0.9...1.3 ms dc 12.7...25 ms ac/14.4...16.4 ms dc 225 mW typ. 0.7...2.5 ms typ. 0.2...2.0 ms 500 mA 10 W/10 VA 100 V 500 mA 500 mA 10 W/10 VA 175 V 500 mA 500 mA 10 W/10 VA 170 V 500 mA 500 mA 10 W/10 VA 100 V 500 mA 200 Hz RH/RU 1 normally-open contact 109 switching operations 5 x 108 switching operations 25 Hz RH/RU 1 normally-open contact 109 switching operations 5 x 108 switching operations 5 Hz RH/RU 1 normally-open contact 109 switching operations 5 x 108 switching operations 20 Hz RH/RU 1 normally-open contact 109 switching operations 5 x 108 switching operations 150 V 1.5 kV III 2 3 mm 150 V 1.5 kV III 2 3 mm 150 V 1.5 kV III 2 3 mm 150 V 1.5 kV III 2 3 mm Storage temperature Conductor Conductor cross-section Overall width -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 6 mm Accessories End plate Further accessories, dimensions and connection data see Type AP DKT4 Page 305 Max. switch-on current Max. switching capacity Max. output voltage Max. output current Min. output current Max. switching frequency Contact material Contacts Service life mechanical at lL= 10 mA Insulation coordination acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances Operating temperature 70 without clearance with clearance Cat. No. 0687560000 Type AP DKT4 Page 305 Cat. No. 0687560000 Type AP DKT4 Page 305 Cat. No. 0687560000 Type AP DKT4 Page 305 Cat. No. 0687560000 Relay Couplers in Component Housings Mini coupler DKR Type DKR 24 Vdc Cat. No. DK5R-1U Type DKR 24 Vdc Cat. No. 8215620000 DKR 24 Vdc DK5R-1U 9454910000 Input: bottom 24 Vac/dc 20 % 9 mAac/7 mAdc max. 240 mA Input: top 24 Vdc 20 % 9.3 mA 8181980000 Input: bottom 24 Vdc 20 % 11.5 mA Type Cat. No. DKR 24 Vac/dc 8181970000 384 mW 5A 2 kVA/192 W 250 Vac/dc 8A 100 mA 25 Hz AgCdO 1 changeover contact 107 switching operations 3 x 106 switching operations 5A 2 kVA/192 W 250 Vac/dc 8A 100 mA ac: 5 Hz dc: 25 Hz AgCdO 1 changeover contact 107 switching operations 3 x 106 switching operations 300 V 4 kV III 2 8 mm 300 V 6 kV IV 2 8 mm 300 V 6 kV IV 2 8 mm -40 C...+60 C -40 C...+60 C -40 C...+60 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 18 mm -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 18 mm 6 ms 15 ms ac/dc 500 mA 10 W/10 VA 175 Vac/dc 500 mA 4A 1.5 kVA/140 W 250 Vac/dc 6A 25 Hz RH/RU 1 normally-open contact 109 switching operations 5 x 108 switching operations 20 Hz Ag Ni 1 changeover contact 2x107 switching operations 150 V 1.5 kV III 2 3 mm -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 6 mm Cat. No. 0687560000 Cat. No. Input: bottom 24 Vac/dc 20 % 20 mAac/16 mAdc max. 100 mA 480 mWac/400 mWdc 225 mW typ. 0.7...2.5 ms typ. 0.2...2.0 ms Type AP DKT4 Page 305 Type DKR 24 Vac/dc Type AP DK5 Page 305 Cat. No. 8268870000 Type AP DKT4 Page 305 Cat. No. 0687560000 Type AP DKT4 Page 305 Digital signal processing DKR 24 Vac/dc Cat. No. 0687560000 71 Relay Coupler in Component Housings EG 2 with 1 NO or 1 NC EGR EG 2 24 V EGR EG 2 24 V EGR EG 2 48 V Direct and alternating voltage AC/DC voltage EGR EG 2 230 V AC voltage Schematic circuit diagram Type NC NO Ordering data Rated data Input voltage Rated consumption - (W) Rated consumption ~ (VA) Drop-out current of the relay** (at 20 C) Max. output voltage Continuous current Derating curve a = mounted horizontally on rail without clearance b = mounted horizontally on rail with clearance x 20 mm Cat. No. 01335600001) 01336600001) Type NC NO Cat. No. 0542660000 0536260000 Type NC NO Cat. No. 0662460000 0662660000 Type NC NO Cat. No. 0543660000 0543860000 24 V-, 10 % 0.36 W - 1.5 mA 24 V0, 10 % 0.35 W 0.6 VA 1.5 mA-/4 mA~ 48 V0, 10 % 0.8 W 0.9 VA 1.5 mA-/3.5 mA~ 230 V~, +5 % -15 % - 3.2 VA 4 mA 240 V~/100 V- 3A 240 V~/100 V- 3A 240 V~/100 V- 1A 240 V~/100 V- 1A 5A 600 VA/120 W 40 W < 2 ms 5A 600 VA/120 W 40 W < 2 ms 5A 600 VA/120 W 40 W < 2 ms 5A 600 VA/120 W 40 W < 2 ms < 5.3 ms < 8.3 ms 50 Hz AgNi, gold-plated > 107 switching operations > 6 x 105 switching operations > 105 switching operations Green LED -40 C...+60 C < 8 ms < 22 ms 30 Hz AgNi, gold-plated > 107 switching operations > 6 x 105 switching operations > 105 switching operations Green LED -40 C...+60 C < 9 ms < 12 ms 37 Hz AgNi, gold-plated > 107 switching operations > 6 x 105 switching operations > 105 switching operations Green LED -40 C...+60 C < 5 ms < 7 ms 40 Hz AgNi, gold-plated > 107 switching operations > 6 x 105 switching operations > 105 switching operations Green LED -40 C...+60 C -25 C...+40 C -25 C...+50 C CSA (013366) -25 C...+40 C -25 C...+50 C -25 C...+40 C -25 C...+50 C -25 C...+40 C -25 C...+50 C III 3 Page 306, Fig. II III 3 Page 306, Fig. II III 2 Page 306, Fig. II III 2 Page 306, Fig. II Continuous current Ambient temperature Switch-on current Max. switching capacity with resistor load Min. switching capacity/switching current Bounce times Switching times, typical -, pick-up lag -, turn off delay Max. switching frequency Contact material Service life, mechanical -, 24 V-, 1 A, resistive load -, 230 V~, 3 A, resistive load Status indicator Storage temperature Ambient temperature -, mounted on rail without clearance -, mounted on rail with clearance 20 mm Approvals Insulation coordination acc. to EN 50178 Overvoltage category Pollution severity Accessories, dimensions and connection data see ** Larger values on request 72 1) no output varistor Relay Coupler in Component Housings EG 2 with 2.8-mm tab connection EGR EG 2 EGR EG 2 DC voltage 2 changeover contacts AC/DC voltage 2 changeover contacts Schematic circuit diagram LED is parallel to coil in 12 V DC and 24 V DC versions Rated data Input voltage Rated consumption - (W) Rated consumption ~ (VA) Drop-out current of the relay** (at 20 C) Max. output voltage Continuous current Derating curve a = mounted horizontally on rail without clearance b = mounted horizontally on rail with clearance x 20 mm Type Cat. No. EGR 2 RT (12 V-) 0160160000 EGR 2 RT (24 V-) 0160260000 Type Cat. No. EGR 2 RT (48 V-) 0160360000 EGR 2 RT (115 V-) 0160460000 Type Cat. No. EGR 2 RT (24 V0) 0123060000 EGR 2 RT (48 V0) 0123260000 EGR 2 RT (115 V0) 0141360000 12 V- 0.61 W - 12 mA 48 V- 0.65 W - 2.5 mA 24 V0 0.7 W 1 VA 3.5 mA-/8 mA~ 115 V0 0.6 W 0.6 VA 1 mA-/1 mA~ 24 V- 0.54 W - 5.5 mA 115 V- 0.6 W - 1 mA 48 V0 0.7 W 0.9 VA 2 mA-/3.5 mA~ Type Cat. No. EGR 2 RT (230 V0) 0142460000 230 V0 1.2 W 1.2 VA 1 mA 250 V 5A 250 V 5A 250 V 5A 250 V 5A 15 A/200 ms 1100 VA/144 W 5A 4 ms 15 A/200 ms 1100 VA/144 W 5A 4 ms 15 A/200 ms 1100 VA/144 W 5A 4 ms 014246 15 A/200 ms 1100 VA/144 W 5A 4 ms 16 ms 22 ms 20 ms 15 ms 20 Hz 20 Hz Ag, gold-flashed 30 x 106 105 (1100 VA, cos : = 1) 18 ms 14 ms 16 ms 23 ms 27 Hz 24 Hz Ag, gold-flashed 30 x 106 105 (1100 VA, cos := 1) 23 ms 18 ms 25 ms 19 ms 19 Hz 21 Hz Ag, gold-flashed 30 x 106 105 (1100 VA, cos := 1) 17 ms 13 ms 17 ms 18 ms 24 Hz 22 Hz Ag, gold-flashed 30 x 106 105 (1100 VA, cos := 1) Red LED -40 C...+85 C Red LED -40 C...+85 C Red LED -40 C...+85 C Red LED -40 C...+85 C -25 C...+40 C -25 C...+40 C -25 C...+40 C -25 C...+40 C III 2 Page 306, Fig. III III 2 Page 306, Fig. III III 2 Page 306, Fig. III III 2 Page 306, Fig. III Digital signal processing Ordering data Continuous current Ambient temperature Switch-on current Max. switching capacity with resistor load Min. braking capacity/switching current Bounce times Switching times, typical -, pick-up lag -, turn off delay Max. switching frequency Contact material Service life, mechanical -, 24 V-, 1 A, resistive load -, 230 V~, 3 A, resistive load Status indicator Storage temperature Ambient temperature -, mounted on rail without clearance -, mounted on rail with clearance 20 mm Insulation coordination acc. to EN 50178 Overvoltage category Pollution severity Accessories, dimensions and connection data see ** Larger values on request 73 WAVESERIES Relay Coupler in Component Housings With 1 changeover contact WRS 1 2.4-24 VDC WRS 1 24 VDC WRS 1 24/48 VUC WRS 1 24/60 VUC Ordering data Screw connection Type Cat. No. WRS 1 2.4-24 Vdc 8275320000 Type WRS 1 24 Vdc Cat. No. 8275350000 Type Cat. No. WRS 1 24/48 Vuc 8286280000 Type Cat. No. WRS 1 24/60 Vuc 8418210000 Tension clamp connection WRZ 1 WRZ 1 8430180000 WRZ 1 WRZ 1 Input Input voltage Input current 2.4...24 Vdc +10 % 4.6 mAdc 15% at Ue 12 V 24 Vdc10 % 9 mAdc15% 24 Vuc10 % /48 Vuc10% 14 mAuc15% at Ue 24 V 14 mAuc15% at Ue 48V Input power 6 mW 15% at Ue 2.4 V 220 mW15% 0.5 VA (W)15% at Ue=48V 0.35 VA (W)15% at Ue=24V Turn off delay max. 150 Vdc /250 Vac max. 5 A /max. 1250 VA* max. 10 A 100 mA/5 Vdc Ag-alloy max. 30 m/max. 100 m at 1 A/6 Vdc typ. 7 ms (NO) / 4.5 ms (NC) typ. 6.3 ms (NO) / max. 150 Vdc /250 Vac max. 5 A /max. 1250 VA* max. 10 A 100 mA/5 Vdc Ag-alloy max. 30 m/max. 100 m at 1 A/6 Vdc typ. 7 ms (NO) / 4.5 ms (NC) typ. 6.3 ms (NO) / max. 150 Vdc /250 Vac max. 5A /max. 1250 VA* max. 10 A 100 mA/5Vdc Ag-alloy max. 30 m/max. 100 m at 1 A/6 Vdc typ. 7 ms (NO) / 4.5 ms (NC) typ. 6.3 ms (NO) / max. 150 Vdc/250 Vac max. 5 A/max. 1250 VA* max. 10 A 100 mA/5 Vdc Ag-alloy max. 30 m/max. 100 m at 1 A / 6 Vdc typ. 5.4 ms (NO) / 4.2 ms (NC) typ. 4.4 ms (NO) / Mechanical service life Electrical service life Max. switching frequency at nominal voltage Ambient temperature Storage temperature Approvals 5.5 ms (NC) 20 x 106 switching operations 150 x 103 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 5.5 ms (NC) 20 x 106 switching operations 150 x 103 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 5.5 ms (NC) 20 x 106 switching operations 1.5 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 5.4 ms (NC) 20 x 106 switching operations 150 x 103 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 300 V 4 kV (1.2/50 ) III 2 5.5 mm 300 V 4 kV (1.2/50 ) III 2 5.5 mm 300 V 4 kV (1.2/50 ) III 2 5.5 mm 300 V 4 kV (1.2/50 ) III 2 5.5 mm 4 kVeff 1 min 4 kVeff 1 min 4 kVeff 1 min 4 kVeff 1 min 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 Relay couplers in the WAVEBOX Independent connection technology - pluggable connection unit screw or tension clamp technology Fast commissioning and after-salesservice service - pluggable PCBs Save wiring tasks - cross-connections possible at input and output Schematic circuit diagram Output Switching voltage Continuous current AC / Switching power AC Switch-on current Min. switching Contact material Contact resistance (when new) Pick-up delay at nominal voltage Insulation coordination acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Implemented clearance and creepage path Insulation and voltage strength Insulation and voltage strength of entire circuit to mounting rail Testing Input/output high voltage test Accessories, dimensions and connection data see * at ambient temperature 20C 74 8430170000 8430190000 8430200000 24 Vuc10% / 60 Vuc10% 11 mAac15% at Ue=60 V 10 mAdc15% at Ue=60 V 10.2 mAac15% at Ue=24 V 9 mAdc15% at Ue=24 V 0.7 VA 15% at Ue=60 V 0.34 VA15% at Ue=24 V 0.6 W 15% at Ue=60 V 0.22 W15% at Ue=24 V WAVESERIES Relay Coupler in Component Housings WRS 1 24/115 VUC WRS 1 24 VUC 230 VAC Mounted horizontally waagerecht montiert Control 26.4Vdc Ansteuerung 26,4Vdc 8 clearance >= 10 mm Abstand>=10mm 7 Output current [A] 6 mounted 5 4 3 2 1 0 0 20 40 60 80 100 Ambient temperature [C] [C] Umgebungstemperatur WRS 1 2.4-24 VDC * 8275320000 Mounted horizontally waagerecht montiert Ansteuerung 52,8Vdc Control 52.8Vdc 8 Output current [A] 7 Abstand>=10mm clearance >= 10 mm mounted 6 5 4 3 2 1 0 0 20 40 60 80 100 Ambient temperature [C] Umgebungstemperatur [C] WRS 1 24/48 VUC * 8286280000 Type Cat. No. WRS 1 24 Vuc/230 Vac 8418230000 WRZ 1 8430220000 Vuc10% / 230 Vac10% mAac15% at Ue=230 V mAac15% at Ue=24 V mAdc15% at Ue=24 V max. 150 Vdc/250 Vac max. 5 A/max. 1250 VA* max. 10 A 100 mA/5 Vdc Ag-alloy max. 30 m/max. 100 m at 1 A / 6 Vdc typ. 5.4 ms (NO) / 4.2 ms (NC) typ. 4.4 ms (NO) / max. 150 Vdc/250 Vac max. 5 A/max. 1250 VA* max. 10 A 100 mA/5 Vdc Ag-alloy max. 30 m/max. 100 m at 1 A / 6 Vdc typ. 5.4 ms (NO) / 4.2 ms (NC) typ. 4.4 ms (NO) / 5.4 ms (NC) 20 x 106 switching operations 150 x 103 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 5.4 ms (NC) 20 x 106 switching operations 150 x 103 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 300 V 4 kV (1.2/50 ) III 2 5.5 mm 300 V 4 kV (1.2/50 ) III 2 5.5 mm 4 kVeff 1 min 4 kVeff 1 min 7 mounted 6 Abstand>=10mm clearance >= 10 mm 5 4 3 2 Digital signal processing 24 15 14 13 8 Output current [A] 24 Vuc10% / 115 Vuc10% 11 mAac15% at Ue=115 V 10.5mAdc15% at Ue=115 V 10.2 mAac15% at Ue=24 V 9 mAdc15% at Ue=24 V 1.3 VA 15% at Ue=115 V 0.34 VA15% at Ue=24 V 1.2 W 15% at Ue=115 V 0.22 W15% at Ue=24 V Mounted horizontally waagerecht montiert Control 66Vdc Ansteuerung 66Vdc 1 3.5 VA 15% at Ue=230 V 0.34 VA15% at Ue=24 V 0.32 W15% at Ue=24 V 0 0 20 40 60 80 100 Ambient temperature [C] [C] Umgebungstemperatur WRS 1 24/60 VUC * 8418210000 Mounted horizontally waagerecht montiert Ansteuerung ac / dc Control26,4V 26.4V ac/dc 8 7 clearance >= 10 Abstand>=10mm Output current [A] mm mounted 6 5 4 3 2 1 0 0 20 40 60 80 100 Ambient temperature [C] [C] Umgebungstemperatur WRS 1 24/115 VUC * 8418220000 Mounted horizontally waagerecht montiert Ansteuerung 253Vac Control 253Vac 8 clearance >= 10 Abstand>=10mm 7 Output current [A] Type Cat. No. WRS 1 24/115 Vuc 8418220000 WRZ 1 8430210000 6 mm mounted 5 4 3 2 1 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 0 0 20 40 60 80 100 Ambient temperature [C][C] Umgebungstemperatur WRS 1 24 VUC/230 VAC * 8418230000 75 WAVESERIES Relay Coupler in Component Housings with 2 NO contacts WRS 2 12/24 VDC WRS 2 24/48 VUC WRS 2 115 VUC/ 230 VAC Type Cat. No. WRS 2 12/24 Vdc 8418240000 WRZ 2 8430230000 Type Cat. No. WRS 2 24/48 Vuc 8418250000 WRZ 2 8430240000 Type Cat. No. WRS 2 115 Vuc/230 Vac 8418260000 WRZ 2 8430250000 12 Vdc10 % / 24 Vdc10 % 21 mAdc15% at Ue=24 V 20 mAdc15%bei Ue=12 V 24 Vuc10 % / 48 Vuc10 % 10 mAac15% at Ue=48 V 11.5 mAac15% at Ue=24 V 8.5 mAdc15% at Ue=48 V 7.2 mAdc15% at Ue=24 V 0.48 VA15% at Ue=48 V 0.21 VA15% at Ue=24 V 0.4 W15% at Ue=48 V 0.17 W15% at Ue=24 V 115 Vuc10%/ 230 Vac10 % 11 mAac15% at Ue=230 V 8.5 mAuc15% at Ue=115 V 8 mAdc15% at Ue=115 V max. 250 Vdc / 250 Vac (UL -> 13300/12300) max. 5 A / max. 1250 VA* max. 8 A 100 mA / 5 Vdc AgSnO2 max. 30 m/max. 100 m at 1 A/6 Vdc typ. 5 ms typ. 6.3 ms (NO) / max. 250 Vdc / 250 Vac (UL -> 13300/12300) max. 5 A / max. 1250 VA* max. 8 A 100 mA / 5 Vdc AgSnO2 max. 30 m/max. 100 m at 1 A/6 Vdc typ. 5 ms --- max. 250 Vdc / 250 Vac (UL -> 13300/12300) max. 5 A / max. 1250 VA* max. 8 A 100 mA / 5 Vdc AgSnO2 max. 30 m/max. 100 m at 1 A/6 Vdc ----- 5.5 ms (NC) 50 x 106 switching operations 1 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 50 x 106 switching operations 1 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 50 x 106 switching operations 1 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA (nur 115 Vuc) 300 V 4 kV (1.2/50 ) III 2 8 mm 300 V 4 kV (1.2/50 ) III 2 8 mm 300 V 4 kV (1.2/50 ) III 2 8 mm Insulation and voltage strength Insulation and voltage strength of entire circuit to mounting rail 4 kVeff 1 min 4 kVeff 1 min 4 kVeff 1 min Testing Input/output high voltage test Accessories, dimensions and connection data see 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 WRS 2 12/24 VDC -> 8418240000 Mounted horizontally waagerecht montiert Control 26.4 Vdc 26.4 Vdc Ansteuerung 26,4Vdc 8 clearance 10 mm Output current [A] 7 Abstand>=10mm mounted angereiht 6 5 4 3 2 1 0 0 20 40 60 80 100 Ambient temperature [C] [C] Umgebungstemperatur WRS 2 12/24 VDC * 8418240000 WRS 2 24/48 VUC -> 8418250000 Mounted horizontally waagerecht montiert Ansteuerung 52,8Vdc Control 26.4 Vdc 52.8 Vdc 8 7 Abstand>=10mm clearance 10 mm Output current [A] angereiht mounted 6 5 4 3 2 Schematic circuit diagram 1 0 0 20 40 60 80 100 Umgebungstemperatur Ambient temperature[C] [C] WRS 2 24/48 VUC * 8418250000 Mounted horizontally 253Vac Control 26.4 Vdc 253 Vdc WRS 2 115 VUC/ 230 VAC -> 8418260000 waagerecht montiert; Ansteuerung 8 clearance 10 mm Output current [A] 7 Abstand>=10mm mounted 6 5 4 3 2 1 0 0 10 20 30 40 50 60 70 80 Umgebungstemperatur [C] Ambient temperature [C] WRS 2 115 VUC/ 230 VAC * 8418260000 Ordering data Screw connection Tension clamp connection Input Input voltage Input current Input power Output Switching voltage Continuous current AC / Switching power AC Switch-on current Min. switching Contact material Contact resistance (when new) Pick-up delay at nominal voltage Turn off delay Mechanical service life Electrical service life Max. switching frequency at nominal voltage Ambient temperature Storage temperature Approvals Insulation coordination acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Implemented clearance and creepage path * at ambient temperature 20C 76 0.5 W15% at Ue=24 V 0.24 W15% at Ue=12 V 2.5 VA15% at Ue=230 V 1 VA15% at Ue=115 V 0.9 W15% at Ue=115 V WAVESERIES Relay Coupler in Component Housings with 1NC / 1 NO WRS 2 12/24 VDC WRS 2 24/48 VUC WRS 2 115 VUC/ 230 VAC Type Cat. No. WRS 2 12/24 Vdc 8418270000 WRZ 2 8430260000 Type Cat. No. WRS 2 24/48 Vuc 8418280000 WRZ 2 8430270000 Type Cat. No. WRS 2 115 Vuc/230 Vac 8418290000 WRZ 2 8430280000 12 Vdc10% / 24 Vdc10% 19.7 mAdc15% at Ue=12 V 20.5 mAdc15% at Ue=24 V 24 Vuc10 % / 48 Vuc10 % 10 mAac15% at Ue=48 V 11.5 mAac15% at Ue=24 V 8.5 mAdc15% at Ue=48 V 7.2 mAdc15%bei Ue=24 V 0.48 VA15% at Ue=48 V 0.21 VA15% at Ue=24 V 0.4 W15% at Ue=48 V 0.17 W15% at Ue=24 V 115 Vuc10 %/230 Vac10 % 11 mAac15% at Ue=230 V 10 mAuc15% at Ue=115 V 8 mAdc15% at Ue=115 V Pick-up delay at nominal voltage Turn off delay max. 250 Vdc/250 Vac max. 5 A/max. 1250 VA* max. 8 A 100 mA/5 V AgSnO2 max. 30 m/max. 100 m at 1 A/6 Vdc typ. 5ms --- max. 250 Vdc/250 Vac max. 5 A/max. 1250 VA* max. 8 A 100 mA/5 V AgSnO2 max. 30 m/max. 100 m at 1 A/6 Vdc ----- max. 250 Vdc/250 Vac max. 5 A/max. 1250 VA* max. 8 A 100 mA/5 V AgSnO2 max. 30 m/max. 100 m at 1 A/6 Vdc ----- Mechanical service life Electrical service life Max. switching frequency at nominal voltage Ambient temperature Storage temperature Approvals 50 x 106 switching operations 1 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 50 x 106 switching operations 1 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 50 x 106 switching operations 1 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA (nur 115 Vuc) Insulation coordination acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Implemented clearance and creepage path 300 V 4 kV (1.2/50 ) III 2 8 mm 300 V 4 kV (1.2/50 ) III 2 8 mm 300 V 4 kV (1.2/50 ) III 2 8 mm Insulation and voltage strength Insulation and voltage strength of entire circuit to mounting rail 4 kVeff 1 min 4 kVeff 1 min 4 kVeff 1 min Testing Input/output high voltage test Accessories, dimensions and connection data see 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 Mounted horizontally Control 26.4 Vdc 26.4 Vdc 8 7 clearance 10 mm Output current [A] Abstand>=10mm 6 angereiht mounted 5 4 3 2 1 0 0 20 40 60 80 100 Ambient temperature [C] WRS 2 12/24 VDC * 8418270000 WRS 2 24/48 VUC -> 8418280000 Mounted horizontally waagerecht montiert Ansteuerung 52,8Vac Control 26.4 Vdc 52.8 Vdc Output current [A] 9 8 clearance 10 mm 7 Abstand>=10mm 6 angereiht mounted 5 4 3 2 Schematic circuit diagram 1 0 0 20 40 60 80 100 Umgebungstemperatur Ambient temperature[C] [C] WRS 2 24/48 VUC * 8418280000 WRS 2 115 VUC/230 VAC -> 8418290000 Mounted horizontally 253Vac Control 26.4 Vdc 253 Vdc waagerecht montiert; Ansteuerung 8 Output current [A] 7 clearance 10 mm Abstand>=10mm mounted 6 5 4 3 2 1 0 0 20 40 60 80 100 Umgebungstemperatur Ambient temperature [C] Ambient temperature[C] [C] Ordering data Screw connection Tension clamp connection Input Input voltage Input current Input power Output Switching voltage Continuous current AC / Switching power AC Switch-on current Min. switching Contact material Contact resistance (when new) 0.5 W15% at Ue=24 V 0.24 W15% at Ue=12 V Digital signal processing WRS 2 115 VUC/230 VAC * 8418290000 2.5 VA15% at Ue=230 V 1 VA15% at Ue=115 V 0.9 W15% at Ue=115 V * at ambient temperature 20C 77 WAVESERIES Relay Coupler in Component Housings with 2 changeover contacts WRS 2 12/24 VDC WRS 2 24/48 VUC WRS 2 24 VUC/ 230 VAC Type Cat. No. WRS 2 12/24 Vdc 8418300000 WRZ 2 8430290000 Type Cat. No. WRS 2 24/48 Vuc 8418310000 WRZ 2 8430300000 Type Cat. No. WRS 2 24 VUC/230 Vac 8418320000 WRZ 2 8430310000 12 Vdc10% /24 Vdc10 % 21 mAdc15% at Ue=12 V 22 mAdc15% at Ue=24 V 24 Vuc10% /48 Vuc10 % 14 mAuc15% at Ue=48 V 14 mAuc15% at Ue=24 V 24 Vuc10% /230 Vac10% 15 mAac15% at Ue=230 V 14 mAuc15% at Ue=24 V 0.26 W15% at Ue=12 V 0.53 W15% at Ue=24 V 0.7 VA(W)15% at Ue=48 V 0.35 VA(W)15% at Ue=24 V 0.35 W15% at Ue=24 V 3.45 VA 15% at Ue=230 V Turn off delay max. 150 Vdc /250 Vac max. 5 A/max. 1250 VA* max. 10 A 100 mA/5 Vdc Ag-alloy max. 30 m / max. 100 m at 1 A / 6 Vdc typ. 6.5 ms (NO) / 4.5 ms (NC) typ. 8 ms (NO) / max. 150 Vdc /250 Vac max. 5 A/max. 1250 VA* max. 10 A 100 mA/5 Vdc Ag-alloy max. 30 m / max. 100 m at 1 A / 6 Vdc typ. 6.5 ms (NO) / 4.5 ms (NC) typ. 8 ms (NO)/ max. 150 Vdc /250 Vac max. 5 A/max. 1250 VA* max. 10 A 100 mA / 5 Vdc Ag-alloy max. 30 m / max. 100 m at 1 A / 6 Vdc typ. 6 ms (NO)/4.2 ms (NC)/Eingang: 24 Vuc/230 Vac typ. 4.4 ms (NO)/ Mechanical service life Electrical service life Max. switching frequency at nominal voltage Ambient temperature Storage temperature Approvals 11 ms (NC) 20 x 106 switching operations 1.5 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 11 ms (NC) 20 x 106 switching operations 1.5 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 5.4 ms (NC) 20 x 106 switching operations 150 x 103 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C Insulation coordination acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Implemented clearance and creepage path 300 V 4 kV (1.2/50 ) III 2 5.5 mm 300 V 4 kV (1.2/50 ) III 2 5.5 mm 300 V 4 kV (1.2/50 ) III 2 5.5 mm Insulation and voltage strength Insulation and voltage strength of entire circuit to mounting rail 4 kVeff 1 min 4 kVeff 1 min 4 kVeff 1 min Testing Input/output high voltage test Accessories, dimensions and connection data see 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 WRS 2 12/24 VDC 8418300000 Mounted horizontally waagerecht montiert Ansteuerung 26,4Vdc Control 26.4 Vdc 26.4 Vdc 7 clearance 10 mm Abstand>=10mm Output current [A] 6 angereiht mounted 5 4 3 2 1 0 0 20 40 60 80 100 Umgebungstemperatur Ambient temperature[C] [C] WRS 2 12/24 VDC * 8418300000 WRS 2 24/48 VUC 8418310000 Mounted horizontally waagerecht montiert Control 26.4 Vdc 26.4 Vdc Ansteuerung 26,4Vac 8 Output current [A] 7 clearance 10 mm Abstand>=10mm 6 angereiht mounted 5 4 3 2 Schematic circuit diagram 1 0 0 20 40 60 80 100 Umgebungstemperatur Ambient temperature[C] [C] WRS 2 24/48 VUC * 8418310000 WRS 2 24 VUC/ 230 VAC 8418320000 Mounted horizontally waagerecht montiert Ansteuerung 253Vac Control 26.4 Vdc 253 Vdc Output current [A] 8 7 6 Abstand>=10mm mounted 5 4 3 2 1 0 0 10 20 30 40 50 60 70 80 Umgebungstemperatur [C] Ambient temperature [C] WRS 2 24 VUC/ 230 VAC * 8418320000 Ordering data Screw connection Tension clamp connection Input Input voltage Input current Input power Output Switching voltage Continuous current AC / Switching power AC Switch-on current Min. switching Contact material Contact resistance (when new) Pick-up delay at nominal voltage * at ambient temperature 20C 78 WAVESERIES Relay Coupler in Component Housings with 3 NO contacts WRS 2 24 VUC WRS 2 230 VAC WRS 2 24 VUC 8418330000 Mounted horizontally26,4Vdc Control 26.4 Vdc 26.4 Vdc waagerecht montiert; Ansteurung 7 Output current [A] 6 Abstand>=10mm clearance 10 mm 5 angereiht mounted 4 3 2 1 0 0 20 40 60 80 100 80 100 Umgebungstemperatur [C] Ambient temperature [C] WRS 2 24 VUC * 8418330000 WRS 2 230 VAC -> 8418340000 Mounted horizontally253Vac Control 26.4 Vdc 253 Vdc waagerecht montiert; Ansteuerung 7 Output current [A] 6 angereiht mounted 5 Abstand>=10mm clearance 10 mm 4 3 2 Schematic circuit diagram 1 0 0 20 40 60 Ambient temperature C] [C] WRS 2 230 VAC * 8418340000 Input Input voltage Input current Type WRS 2 24 Vuc WRZ 2 Cat. No. 8418330000 8430320000 Type Cat. No. WRS 2 230 Vac 8418340000 WRZ 2 8430330000 3fach 24 Vac 10 % 10.5 mAac 15 % at Unenn (per channel) 3 x 230 Vac 10 % 10.3 mAac 15 % at Unenn (per channel) 0.3 VA 15 % (per channel) 0.25 W 15 % 2.4 VA 15 % (per channel) Pick-up delay at nominal voltage max. 250 Vdc /250 Vac max. 4 A/max. 1500 VA* max. 6 A 12 V/10 mA AgSnO2 max. 100 m at 1 A/24 Vdc typ. 5 ms max. 250 Vdc / 250 Vac max. 4 A/max. 1500 VA* max. 6 A 12 V/10 mA AgSnO2 max. 100 m at 1 A/24 Vdc typ. 8 ms Turn off delay typ. 21 ms typ.11 ms Mechanical service life Electrical service life Max. switching frequency at nominal voltage Ambient temperature Storage temperature Approvals 20 x 106 switching operations 1 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C UL/CSA 20 x 106 switching operations 1 x 105 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C Insulation coordination acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Implemented clearance and creepage path 300 V 4 kV (1.2/50 ) III 2 5.5 mm 300 V 4 kV (1.2/50 ) III 2 5.5 mm Insulation and voltage strength Insulation and voltage strength of entire circuit to mounting rail 4 kVeff 1 min 4 kVeff 1 min Testing Input/output high voltage test Accessories, dimensions and connection data see 4 kVeff 1 s Page 298 + 308 4 kVeff 1 s Page 298 + 308 Input power Output Switching voltage Continuous current AC / Switching power AC Switch-on current Min. switching Contact material Contact resistance (when new) Digital signal processing Ordering data Screw connection Tension clamp connection * at ambient temperature 20C 79 Relay Couplers in Components Housings EG 7 Plugs on to locking socket RS EG 7 with combination foot TS 32, 35 Overall width: 10 mm With combination foot for TS 15, TS 32 or TS 35 Versions with 12 V, 24 V and 48 V fulfil protective separation in accordance with VDE 0160, Part 101 All EGR EG 7 and RST EG 7 are approved by Germanischer Lloyd. Approval No. 35962 HH EGR EG 7 RST EG 7 RS EG 7 RST EG 7 RS EG 7 EGR EG 7 12 V0 24 V- 24 V- 24 V0 Schematic circuit diagram Derating curve a = mounted horizontally on rail without clearance b = mounted horizontally on rail, rowed with clearances Continuous current Ambient temperature Ordering data Combination foot for TS 15, TS 32, TS 35 1 NO 1 NC EGR EG 7 spare relays, without connection unit Plug-in relay-coupl., without engagem. socket, 1 changeo. cont. Engage.socket f. plug-in relay coupler w. combin.foot TS 32, 35 Rated data of the coil Input voltage Rated consumption Max. switch-on current Combination foot for drop current Connection - NO and NC - changeover contacts Rated data der Contacts Max. output voltage Continuous current Max. switch-on current Min. switching capacity/switching current Bounce times Contact material2) Bounce times Switching times pick up delay drop-out delay Service life, mechanical -, 24 V-, 1.1 A, inductive load -, 230 V~, 5 A, resistive load Status indicator Storage temperature Ambient temperature Insulation coordination acc. to EN 50178 Safe isolation according to VDE 0106 part 101 Rated impulse voltage Clearances and creepage distances Overvoltage category Pollution severity Accessories Cross-connection comb. 16fold Accessories, dimensions and connection data see 1) Serves only as a spare part for NO and NC Type EGR EG7 EGR EG7 EGR EG7 RST EG7 RS EG7 Cat. No. 8092310000 8092320000 80923300001) 8216550000 8193830000 Type EGR EG7 EGR EG7 EGR EG7 RST EG7 RS EG7 Cat. No. 8216520000 8216530000 82182000001) 8216570000 8193830000 Type EGR EG7 EGR EG7 EGR EG7 RST EG7 RS EG7 Type EGR EG7 EGR EG7 EGR EG7 RST EG7 RS EG7 Cat. No. 8092340000 8092350000 80923600001) 8216580000 8193830000 12 V0 +15 % -10 % 320 mW +20 % -10 % 120 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 24 V- +15 % -10 % 280 mW +20 % -10 % 12 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 24 V- +15 % -10 % 280 mW +20 % -10 % 12 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 24 V0 +15 % -10 % 280 mW +20 % -10 % 240 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 250 V 5A 8A 100 mW/10 mA 1 ms AgNi 0.15 gold-flashed 1 ms 250 V 5A 8A 100 mW/10 mA 1 ms AgNi 0.15 gold-flashed 1 ms 250 V 5A 8A 40 W2) 1 ms AgNi 0.15 5 Au 1 ms 250 V 5A 8A 100 mW/10 mA 1 ms AgNi 0.15 gold-flashed 2.4 ms 8 ms 6 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C 8 ms 6 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C 8 ms 6 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C 11 ms 10 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C DIN VDE 0106 8 kV 8 mm III 2 DIN VDE 0106 8 kV 8 mm III 2 DIN VDE 0106 8 kV 8 mm III 2 DIN VDE 0106 8 kV 8 mm III 2 QB 16/10.16 Page 304 1650330000 QB 16/10.16 Page 304 1650330000 QB 16/10.16 Page 304 2) The following ratings can safely be b ) 5 V... 24 V dc/10 mA ... 1.2 A c ) 24 V ... 60 V dc/10 mA ... 500 mA switched: 5A a ) 100 mV...60 V ac/dc/100 A...300 mA d ) 10 V...250 V ac/10 mA ... 80 Cat. No. 8147120000 8147140000 81600300001) 8216560000 8193830000 1650330000 QB 16/10.16 Page 304 1650330000 After switching higher powers (b...d) lower powers (a) can no longer be switched. Relay Couplers in Components Housings EG 7 RST EG 7 RS EG 7 EGR EG 7 Type EGR EG7 EGR EG7 EGR EG7 RST EG7 RS EG7 60 V~ Cat. No. 8092370000 8092380000 80923900001) 8216590000 8193830000 Type EGR EG7 EGR EG7 EGR EG7 RST EG7 RS EG7 115 V0 Cat. No. 8092400000 8092410000 80924200001) 8216600000 8193830000 Type EGR EG7 EGR EG7 EGR EG7 RST EG7 RS EG7 230 V~ Cat. No. 8092430000 8092440000 80924500001) 8216610000 8193830000 Type EGR EG7 EGR EG7 EGR EG7 RST EG7 RS EG7 230 V~ Cat. No. 8092460000 8092470000 80924800001) 8216620000 8193830000 Type EGR EG7 Cat. No. 8178200000 RST EG7 RS EG7 8216630000 8193830000 48 V0 +15 % -10 % 280 mW +15 % -10 % 480 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 60 V0 +15 % -10 % 280 mW +15 % -10 % 600 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 115 V0 +15 % -10 % 330 mW +15 % -10 % 160 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 230 V~ +15 % -10 % 280 mW +15 % -10 % 185 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 230 V~ +15 % -10 % 280 mW +15 % -10 % 185 mA 3 mA Screw connection 0.5...1.5 mm2 AWG-Conductor 26...16 0.5...2.5 mm2 250 V 5A 8A 100 mW/10 mA 1 ms AgNi 0.15 gold-flashed 2.5 ms 250 V 5A 8A 100 mW/10 mA 1 ms AgNi 0.15 gold-flashed 3.8 ms 250 V 5A 8A 100 mW/10 mA 1 ms AgNi 0.15 gold-flashed 3.8 ms 250 V 5A 8A 100 mW/10 mA 1 ms AgNi 0.15 gold-flashed 2 ms 250 V 5A 8A 40 W2) 1 ms AgNi 0.15 5 Au 2 ms 12 ms 12 ms 12 ms 12 ms 12 ms 10 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C 10 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C 10 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C 10 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C 10 ms > 15 x 106 switching operations 2 x 106 switching operations with free wheel diode > 2 x 105 switching operations Green LED -40 C...+60 C -25 C...+60 C DIN VDE 0106 8 kV 8 mm III 2 8 kV 8 mm III 2 8 kV 8 mm III 2 8 kV 8 mm III 2 8 kV 8 mm III 2 QB 16/10.16 Page 304 1650330000 QB 16/10.16 Page 304 1650330000 QB 16/10.16 Page 304 1650330000 QB 16/10.16 Page 304 1650330000 QB 16/10.16 Page 304 Digital signal processing 48 V0 1650330000 81 PLUGSERIES Relays on Sockets PRZ/PRS PRS/PRZ xxx 1CO PRS/PRZ xxx 2CO DC-Version Type/Version Screw connection PRS 12Vdc LD 1CO PRS 12Vdc LD 2CO PRS 24Vdc LD 1CO PRS 24Vdc LD 2CO PRS 115Vdc LD 1CO PRS 115Vdc LD 2CO PRS 24Vdc LD 2CO SGR 282 with gold-plated relay contacts: PRS 24Vdc LD 2CO AU Modular system comprising: - Relay socket for mounting rails - LED indicator unit / RC combination - retainer clip - pluggable relays Independent connection technology: screw or tension clamp technology Compatible with low power relays type RT / Standard with 1 or 2 CO contacts Coil and root-contacts cross-connectable with cross-connection type ZQV 2.5 N Available as complete module or as spare parts PRZ/PRS Tension clamp connection PRZ 12Vdc LD 1CO PRZ 12Vdc LD 2CO PRZ 24Vdc LD 1CO PRZ 24Vdc LD 2CO PRZ 115Vdc LD 1CO PRZ 115Vdc LD 2CO PRZ 24Vdc LD 2CO SGR 282 with gold-plated relay contacts: PRZ 24Vdc LD 2CO AU Other variants on request Technical data Input voltage Rated consumption, typ Status indicator Output Contact version Max. output voltage Max. switching current Continuous current Rated braking capacity Service life, mech. Input/output Clearance and creepage path Protective separation Dielectric strength Insulation coordinates acc. to EN 50178 Miscellaneous data Ambient temperature Protection class Rated cross-section Flammability Relay type Dimensions WxHxT Approvals Rail mounted Accessories Cross-connection 2-pole black 2-pole red 2-pole blue Marking tags AC-Version Cat. No. 8536471001 8536501001 8530621001 8530631001 8536510000 8536520000 8596000000 10 10 10 10 10 10 10 8561760000 10 8536571001 8536591001 8530691001 8530701001 8536610000 8536630000 8595970000 10 10 10 10 10 10 10 8552440000 10 12 V dc ... 24Vdc ... 115Vdc 400 mW pluggable LED-housing, green LED 1 CO /2 CO contacts 1 x UM / 2 x UM 250Vuc 16A / 2 x 8A 10A 4kVA / 2 x 2kVA 30 x 106 > 8mm DIN VDE 0106 T. 101 > 4kV eff III / 2 -40C ... +50C IP 20 0.5...2.5mm2 V0 Schrack RT1 / RT2 15.2 x 91 x 85 CE, UL recognized, cUL TS 35 ZQV 2.5N/4-2 SW1784270000 60 ZQV 2.5N/4-2 RT 1784280000 60 ZQV 2.5N/4-2 BL 1784290000 60 WS 10/5 WS 15/5 82 Qty. 1060860000 1609880000 Type/Version Screw connection PRS 24Vac LD 1CO PRS 24Vac LD 2CO PRS 120Vac LD 1CO PRS 120Vac LD 2CO PRS 230Vac LD 1CO PRS 230Vac LD 2CO 8536530000 8536560000 8530641001 8530661001 8530671001 8530681001 10 10 10 10 10 10 with gold-plated relay contacts: PRS 120Vac LD 2CO AU PRS 230Vac LD 2CO AU 8595960000 8595990000 10 10 Tension clamp connection PRZ 24Vac LD 1CO PRZ 24Vac LD 2CO PRZ 120Vac LD 1CO PRZ 120Vac LD 2CO PRZ 230Vac LD 1CO PRZ 230Vac LD 2CO 8536651001 8536681001 8530710000 8530720000 8530731001 8530741001 10 10 10 10 10 10 8575940000 8575950000 10 10 with gold-plated relay contacts: PRZ 120Vac LD 2CO AU PRZ 230Vac LD 2CO AU Other variants on request Technical data Input voltage Rated consumption, typ Status indicator Output Contact version Max. output voltage Max. switching current Continuous current Rated braking capacity Service life, mech. Input/output Clearance and creepage path Protective separation Dielectric strength Insulation coordinates acc. to EN 50178 Miscellaneous data Ambient temperature Protection class Rated cross-section 0.5 mm2 Flammability Relay type Dimensions WxHxT Approvals Rail mounted Accessories Cross-connection 2-pole black 2-pole red 2-pole blue Marking tags Cat. No. Qty. 24Vac ...120Vac ... 230Vac 760 VA pluggable LED-housing, green LED 1 CO /2 CO contacts 1 x UM / 2 x UM 250Vuc 16A / 2 x 8A 10A 4kVA / 2 x 2kVA 5 x 106 > 8mm DIN VDE 0106 T. 101 > 4kV eff III / 2 -40C ... +50C IP 20 0.5...2.5mm2 V0 Schrack RT1 / RT2 15.2 x 91 x 85 CE, UL recognized, cUL TS 35 ZQV 2.5N/4-2 SW1784270000 60 ZQV 2.5N/4-2 RT 1784280000 60 ZQV 2.5N/4-2 BL 1784290000 60 WS 10/5 WS 15/5 1060860000 1609880000 PLUGSERIES Relays on Sockets Accessories marking field retaining-clip 87 (PXZ35) 87 95 (PXS35) Cross-connection channel 11 / 21 Cross-connections channel A1 / A2 92 92 Screw connection 15,3 15.3 15.3 22 12 (NC) 22 12 (NC) 21 11 (COM) 21 11 (COM) 24 14 (NO) 24 14 (NO) Empty base for rail mounted TS 35 Screw connection Tension clamp connection Type PXS35 PXZ35 Technical data Rated current Rated voltage Dielectric strength coil/contacts Protection class Rated cross-section Insulation stripping length - Screw connection - Tension clamp connection Ambient temperature Flammability class UL 94 A2 A2 A1 (COIL) Cat. No. 8536700000 Qty. 100 6 ... 24 Vdc 6 ... 24 Vdc 48 ... 60 Vdc 115 Vdc 12 ... 24 Vac 115 Vac 230 Vac 230 Vac RC combination 120...230 VAC/DC PLED 24 Vdc PLED 24 Vdc red PLED 48 Vdc PLED 115 Vdc PLED 24 Vac PLED 120 Vac PLED 230 Vac PLED 230 Vac red PLRC 200 nF/200 8536710000 8611010000 8536720000 8536730000 8536750000 8536760000 8536780000 8611000000 8566530000 20 20 20 20 20 20 20 20 20 ZQV 2.5N/4-2SW ZQV 2.5N/4-2RT ZQV 2.5N/4-2BL 1784270000 1784280000 1784290000 60 60 60 Type WS 10/5 WS 15/5 Cat. No. 1060860000 1609880000 Qty. 200 96 Pluggable cross-connectionen 14 A1 Type PRC 8 mm 10 mm -40C ... +60C V0 Operating indication LED indicator with free-wheeling diode Operating indication DC-Version Qty. 10 10 16 A 250 V > 4 kV IP 20 2.5 mm2 Holding clamp A1 (COIL) Cat. No. 8533771001 8536691001 12 24 2-pole black 2-pole red 2-pole blue 22 * Marking tags 10 x 5 mm A2 21 11 * free wheel diode AC-Version A1 A2 14 12 11 24 22 21 83 Digital signal processing Tension clamp PLUGSERIES Relays on Sockets Pluggable relay types 1 changeover contact SCHRACK RT Print figure/circuit diagram Relay type RT/SGR 2 changeover contacts Pluggable relay 12 Vdc 1 changeover contact 12 Vdc 2 changeover contacts Type Schrack RT Cat. No. RT 314012 4058470000 RT 424012 4058560000 24 Vdc 1 changeover contact 24 Vdc 1 changeover contact AU RT 314024 RT 315024 4058480000 4058490000 20 20 24 Vdc 2 changeover contacts 24 Vdc 2 changeover contacts AU RT 424024 RT 425024 4058570000 4058580000 20 20 48 Vdc 1 changeover contact 48 Vdc 2 changeover contacts RT 314048 RT 424048 4058740000 4058750000 20 20 60 Vdc 2 changeover contacts RT 424060 4058760000 20 110 Vdc 1 changeover contact 110 Vdc 2 changeover contacts RT 314110 RT 424110 4058500000 4058590000 20 20 24 Vac 1 changeover contact 24 Vac 2 changeover contacts RT 315524 RT 424524 4058510000 4058600000 20 20 115 115 115 115 Vac Vac Vac Vac 1 1 2 2 changeover changeover changeover changeover contact contact AU contacts contacts AU RT RT RT RT 314615 315625 424615 425615 4058520000 4058530000 4058610000 4058620000 20 20 20 20 230 230 230 230 Vac Vac Vac Vac 1 1 2 2 changeover changeover changeover changeover contact contact AU contacts contacts AU RT RT RT RT 314730 315730 424730 425730 4058540000 4058550000 4058630000 4058640000 20 20 20 20 Technical data Contact number and type Contact material Switching current Switching voltage Braking capacity Min. switching current / braking capacity Min. braking capacity AU contact Rated consumption Dielectric strength Sp./Kont. Response / drop out time: Bounce time NO contact/normally closed contact Mechanical service life: Braking capacity Miscellaneous data Protection class Flammability class UL Ambient temperature Weight Approvals 84 DC coil AC coil DC coil AC coil 1-pole DC 13 2-pole DC 13 2-pole AC 15 DC coil AC coil 1 changeover contact or 2 changeover contacts AgNi 90/10, AgNi 0.15 htv 16 A 1We/2 x 8 A 2We 250 V ac 4 kVA 10 mA /100 mW 40 W 400 mW dc/0.55 VA ac 5 kV typ. 7/3 ms 9/45 ms typ. 1/3 ms > 30 x 106 switching operations > 30 x 106 switching operations 1.25A, L/R = 80 ms 2.3 x 105 1.25A, L/R = 80 ms 2.8 x 105 1.2A, cosL/R = 0.3 6050x IP 40 V0 -40C ... +85C -40C ... +70C 14 g UL, CSA, VDE, OVE Qty. 20 20 PLUGSERIES Relays on Sockets ELESTA SGR Relais with manual operation Type ELESTA SGR Cat. No. SGR 662 24 Vdc T 8550510000 24 Vdc 2 changeover contacts with test button SGR 282 24 Vdc T 24 Vdc 1 normally-open contact Technical data Contact number and type Contact material Switching current Peak inrush current Switching voltage Braking capacity Min. switching current / braking capacity Rated consumption Dielectric strength Sp./Kont. Response / drop out time: Bounce time NO contact/normally closed contact Mechanical service life: Miscellaneous data Protection class Flammability class UL Ambient temperature Weight Approvals 8550520000 Qty. 10 Type Schrack RP 3SL DC coil DC coil DC coil 250 Vac 4 kVA 10 mA /100 mW 500 mW 5 kV typ. 10/3 ms typ. 0.5/5 ms > 30 x 106 switching operations IP 40 V1 -25C ... +70C 20 g SEV, UL, CSA, DEMKO, VDE, PTB 8588510000 20 1 normally-open contact AgSnO2 25 A 120 A / 20 ms 250 V 4 kVA 500 mW 4 kV typ. 8/2 ms typ. 2 ms 30 x 106 switching operations IP 40 -40C ... +70C 18 g SEV, UL, CSA, VDE Contact service life Type Load switch. oper. RP3SL 12 A, 250 V~, cos=1 3x105 RP3SL TV 8 25x103 RP3SL 2500 W, 230 V~, halogene lamps >104 RP3SL 1000 W, 250 V~, glow lamps 2.3x105 RP3SL 3000 W, 250 V~, glow lamps 3.6x104 RP3SL 1500 VA, flurescent tubes 163 F 104 Regulation UL 508 Power relay RP 3SL Electrical life Operations Leistungsrelais Type RT2 2 changeover contacts Qty. 10 RP3SL 24 Vdc 1NO 2 changeover contacts with test button AgCuNi 16 A 1We/2 x 8 A 2We Cat. No. 85 Digital signal processing Pluggable relay 24 Vdc 1 changeover contact with test button RP 3SL Relays for high switching currents Relay Couplers on Sockets MICROSERIES in Terminal Format MICRORELAY MRS/MRZ This module can be used as a universal interface between the controller and actuator for switching small to medium-sized loads. MRS 5 Vdc 1CO MRS 12 Vdc 1CO MRZ 5 Vdc 1CO MRZ 12 Vdc 1CO Schematic circuit diagram Pluggable cross-connection in the input and output reduces wiring costs 6-mm width Flexible thanks to screw and tension clamp connection versions Ordering data for TS 35 Screw connection Tension clamp connection Limit diagram Output current [A] Type Cat. No. MRS 12 Vdc 1CO 8556070000 MRZ 12 Vdc 1CO 8556140000 5 Vdc 20 % (4...6 V) 12 Vdc 20 % (9.6...14.4 V) 38 .5 mAdc 10 % 193 mW 10% 3.2 V / 21.6 mA 1.6 V / 8 mA Green LED 6.2 ms 3.9 ms 5V 17.2 mAdc 10 % 210 mW 10% 6.4 V / 8.4 mA 2.5 V / 2.4 mA Green LED 5.8 ms 6.9ms 12 V yes yes yes yes yes yes 1 changeover contact 250 Vac acc. to VDE 240 Vac acc. to UL/CSA max. 6 A / max. 1500 VA max. 6 A see limit diagram 12 V /10 mA AgSnO 20 x 10 6 switching operations 0.1 Hz 1 changeover contact 250 Vac acc. to VDE 240 Vac acc. to UL/CSA max. 6 A / max. 1500 VA max. 6 A see limit diagram 12 V /10 mA AgSnO 20 x 10 6 switching operations 0.1 Hz Approvals -25 C...+50 C -40 C...+60 C 40 C / 93 % rel. humidity, no condensation CE, cUL -25 C...+50 C -40 C...+60 C 40 C / 93 % rel. humidity, no condensation CE, cUL Insulation coordination acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Insulation coord.- and voltage proof, input/output mounting rail Achieved clearances and creepage distances 300 V 4 kV (1.2 / 50 s) III 2 4 kVeff / 1 min 5.5 mm 300 V 4 kV III 2 4 kVeff / 1 min 5.5 mm Technical data Input Input voltage Input voltage ac with UNenn Input voltage dc with UNenn Input power Making threshold , (typ.) Cut-out threshold (typ.) Status indicator Reaction time at UN (typ.) Release at UN (typ.) Voltage of relay coil Output Switching voltage ac: continuous current/switching power (see derating diagram) Switch-on current dc: Continuous current/switching power Min. braking capacity Contact material Mechanical service life Max. switching frequency at nominal voltage Ambient temperature Storage temperature Climate Ambient temperature [C] 86 Cat. No. MRS 5 Vdc 1CO 8556080000 MRZ 5 Vdc 1CO 8556150000 Functionality Operating indication Reverse polarity protection Free wheel diode Current temperature-rise curve Type Relay Couplers on Sockets MICROSERIES in Terminal Format MRS 24 Vdc 1CO MRS 24 Vuc 1CO MRS 48 Vuc 1CO MRS 60 Vdc 1CO MRS 120 Vuc 1CO MRS 230 Vac 1CO MRZ 24 Vdc 1CO MRZ 24 Vuc 1CO MRZ 48 Vuc 1CO MRZ 60 Vdc 1CO MRZ 120 Vuc 1CO MRZ 230 Vac 1CO Type Cat. No. Type Cat. No. Type Cat. No. Type Cat. No. Type Cat. No. Type Cat. No. MRS 24 Vuc 1CO8556050000 MRZ 24 Vuc 1CO 8556120000 MRS 48 Vuc1CO 8556040000 MRZ 48 Vuc1CO 8556110000 MRS 60 Vdc1CO 8556060000 MRZ 60 Vdc1CO 8556130000 MRS 120 Vuc 1CO 8556030000 MRZ 120 Vuc 1CO 8556100000 MRS 230 Vac1CO8556020000 MRZ 230Vac1CO 8556090000 24 Vdc 20 % (19.2...28.8 V) 48 Vuc 10% (43.2...52.8 V) 5 mA 20 % 4 mA 20 % 190 mW 20 % 29 V / 2.2 mA 11 V / 1.3 mA Green LED 6.1 ms 5.8 ms 48 V 60 Vdc 20% (48...72 V) 120 Vuc +10% / -15% (102...132 V) 3.5 mAac 15 % 230 Vac 10% (207...253 V) 7.6 mA 15% 6.6 mAdc 10 % 160 mW 10% 15.4 V / 4 mA 6.5 V / 1.2 mA Green LED 6.6 ms 5.8 ms 24 V 24 Vuc 10% (21.6...26.4 V) 11 mA 10 % 6.4 mA 20 % 154 mW 10 % 15.8 V / 3.6 mA 7 V / 1.3 mA Green LED 7.3 ms 9 ms 24 V 3.3 mAdc 20 % 200 mW 10 % 35 V / 1.6 mA 11 V / 0.6 mA Green LED 5.9 ms 6.5 ms 60 V 0.42 VA 15 % 71 V / 1.8 mA 22 V / 0.5 mA Green LED 6.7 ms 8.1 ms 60 V 1.55 VA 15 % 103 V / 5 mA 49 V / 2.5 mA Green LED 13 ms 11 ms 24 V yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes - - 1 changeover contact 250 Vac acc. to VDE 240 Vac acc. to UL/CSA max. 6 A / max. 1500 VA max. 6 A see limit diagram 12 V /10 mA AgSnO 20 x 10 6 switching operations 0.1 Hz 1 changeover contact 250 V ~ acc. to VDE 240 V ~ acc. to UL/CSA max. 6 A / max. 1500 VA max. 6 A see limit diagram 12 V /10 mA AgSnO 20 x 10 6 switching operations 0.1 Hz 1 changeover contact 250 Vac acc. to VDE 240 Vac acc. to UL/CSA max. 6 A / max. 1500 VA max. 6 A see limit diagram 12 V /10 mA AgSnO 20 x 10 6 switching operations 0.1 Hz 1 changeover contact 250 Vac acc. to VDE 240 Vac acc. to UL/CSA max. 6 A / max. 1500 VA max. 6 A see limit diagram 12 V /10 mA AgSnO 20 x 10 6 switching operations 0.1 Hz 1 changeover contact 250 V ~ acc. to VDE 240 V ~ acc. to UL/CSA max. 6 A / max. 1500 VA max. 6 A see limit diagram 12 V /10 mA AgSnO 20 x 10 6 switching operations 0.1 Hz 1 changeover contact 250 V ~ acc. to VDE 240 V ~ acc. to UL/CSA max. 6 A / max. 1500 VA max. 6 A see limit diagram 12 V /10 mA AgSnO 20 x 10 6 switching operations 0.1 Hz -25 C...+50 C -40 C...+60 C 40 C / 93 % rel. humidity, no condensation CE, cUL -25 C...+50 C -40 C...+60 C 40 C / 93 % rel. humidity, no condensation CE, cUL -25 C...+50 C -40 C...+60 C 40 C / 93 % rel. humidity, no condensation CE, cUL -25 C...+50 C -40 C...+60 C 40 C / 93 % rel. humidity, no condensation CE, cUL -25 C...+50 C -40 C...+60 C 40 C / 93 % rel. humidity, no condensation CE, cUL -25 C...+50 C -40 C...+60 C 40 C / 93 % rel. humidity, no condensation CE, cUL 300 V 4 kV III 2 4 kVeff / 1 min 5.5 mm 300 V 4 kV III 2 4 kVeff / 1 min 5.5 mm 300 V 4 kV III 2 4 kVeff / 1 min 5.5 mm 300 V 4 kV III 2 4 kVeff / 1 min 5.5 mm 300 V 4 kV III 2 4 kVeff / 1 min 5.5 mm 300 V 4 kV III 2 4 kVeff / 1 min 5.5 mm Digital signal processing MRS 24 Vdc 1CO 8533640000 MRZ 24 Vdc 1CO 8533660000 87 Relay Couplers on Sockets MICROSERIES in Terminal Format Accessories Tension clamp version MRZ Screw version MRS 92 mm 91 mm 94 mm 93 mm 6.1 mm 6.1 mm General technical data Clampable conductor: Solid H07V-U mm2 Fsolid H07V-K mm2 f" with ferrules acc. to DIN 46 228/1* mm2 f" with ferrules with plastic collar* mm2 Max. clampable range in mm2 /gauge pin acc. to IEC 60 947-1 Size 0.5...2.5 0.5...2.5 0.5...1.5 0.5...1.5 0.13...2.5 Rated torque Continuous current of cross-connection 2-pole Continuous current of cross-connection multipole Insulation stripping length Protection class Housing material Flammability class UL 94 Rated current Rated voltage 10 10 10 IP 20 Wemid V0 6A 250 V Cross-connection Pluggable cross-connection ZQV Markings 12 x 6 mm Screwdriver 88 A A mm Tension clamp version 0.5...4 0.5...2.5 0.5...1.5 0.5...1.5 0.13...4 A2 A3 0.6 Nm 10 10 7 IP 20 Wemid V0 6A 250 V Type yellow Screw version Cat. No. Qty. Type Cat. No. Qty. ZQV ZQV ZQV ZQV ZQV 4N 4N 4N 4N 4N / / / / / 2 GE 3 GE 4 GE 10 GE 41 GE 1758250000 1762630000 1762620000 1758260000 1758270000 60 60 60 20 10 ZQV ZQV ZQV ZQV ZQV 4N 4N 4N 4N 4N / / / / / 2 GE 3 GE 4 GE 10 GE 41 GE 1758250000 1762630000 1762620000 1758260000 1758270000 60 60 60 20 10 red ZQV ZQV ZQV ZQV ZQV 4N 4N 4N 4N 4N / / / / / 2 RT 3 RT 4 RT 10 RT 41 RT 1793950000 1793980000 1794010000 1794040000 1794070000 60 60 60 20 10 ZQV ZQV ZQV ZQV ZQV 4N 4N 4N 4N 4N / / / / / 2 RT 3 RT 4 RT 10 RT 41 RT 1793950000 1793980000 1794010000 1794040000 1794070000 60 60 60 20 10 blue ZQV ZQV ZQV ZQV ZQV 4N 4N 4N 4N 4N / / / / / 2 BL 3 BL 4 BL 10 BL 41 BL 1793960000 1793990000 1794020000 1794050000 1794080000 60 60 60 20 10 ZQV ZQV ZQV ZQV ZQV 4N 4N 4N 4N 4N / / / / / 2 BL 3 BL 4 BL 10 BL 41 BL 1793960000 1793990000 1794020000 1794050000 1794080000 60 60 60 20 10 black ZQV ZQV ZQV ZQV ZQV 4N 4N 4N 4N 4N / / / / / 2 SW 3 SW 4 SW 10 SW 41 SW 1793970000 1794000000 1794030000 1794060000 1794090000 60 60 60 20 10 ZQV ZQV ZQV ZQV ZQV 4N 4N 4N 4N 4N / / / / / 2 SW 3 SW 4 SW 10 SW 41 SW 1793970000 1794000000 1794030000 1794060000 1794090000 60 60 60 20 10 Cat. No. 1060960000 1061160000 Qty. 200 200 Cat. No. 1060960000 1061160000 Qty. 200 200 Cat. No. 9008330000 Qty. 10 Cat. No. 9008330000 Qty. 10 Type WS 10/6 WS 12/6 Type SD 0.6 x 3.5 x 100 Type WS 10/6 WS 12/6 Type SD 0.6 x 3.5 x 100 Relay Couplers on Sockets MICROSERIES in Terminal Format Accessories acc. to Pluggable relay Coil voltage 5 V, 1 changeover contact Coil voltage 12 V, 1 changeover contact Coil voltage 24 V, 1 changeover contact Coil voltage 48 V, 1 changeover contact Coil voltage 60 V, 1 changeover contact Coil voltage 24 V, 1 changeover contact, 5 AU Type NAIS APE... ... 30005V ... 30012V ... 30024V ... 30048V ... 30060V ... 30124V Cat. No. 4061580000 4061610000 4060120000 4061620000 4061630000 4061590000 Qty. 20 20 20 20 20 20 Coil voltage 60 V, 1 changeover contact, 5 AU ... 30160V 4061600000 20 Technical data (of relay manufacturer) Contact number and type Contact version Switching current Switching voltage / max. Switching voltage Braking capacity Contact material Recommended min. load Typ. bounce time NO contact Typ. bounce time normally closed contact 1 changeover contact Single contact 6A 300 Vdc / 400 Vac 1500 VA AgSnO2 100 mA, 12 V 1 ms 5 ms Miscellaneous data Flammability class UL Ambient temperature Max. switching operations with rated load / without load Response / drop out time Bounce time NO contact / normally closed contact Protection class Housing V-0 -40 ... +85 C 6/1200 switching operations per minute 5 / 2.5 ms 1.5 / 5 ms IP 67 For further data see also Digital signal processing switch. operations switch. operations Contact service life Material AgSnO2 www.matsushita.de 89 Relay Couplers on Sockets RS 30 1 NC, 1 NO or 1 changeover contact Schematic circuit diagram 1 Rated data Input voltage 5...60 V 10%; 115 V/230 V + 5% - 15% Rated consumption - (W) Rated consumption ~ (VA) Drop-out current of the relay (at 20 C) Drop-out current of the relay (at 20 C) Pick-up current Max. output voltage Continuous current Derating curve a = mounted horizontally on rail without clearance b = mounted horizontally on rail with clearance x 20 mm 5 VTTL 0.45 W1) - - - - 250 V 5A 12 V- 0.45 W - 3 mA - - 250 V 6A 2 24 V- 0.45 W - 3 mA - 12 mA 250 V 6A 24 V0 0.45 W 0.7 VA 2.5 mA- 3.5 mA~ - 250 V 6A 3 48 V- 0.45 W - 2 mA - 10 mA 250 V 6A 48 V0 0.45 W 0.6 VA 2.5 mA- 4.5 mA~ - 250 V 5A 60 V- 0.45 W - 1 mA- - - 250 V 5A 115 V~ - 0.8 VA - 1 mA~ 6 mA 250 V 5A 4 115 V- 0.82 W - 2 mA- - 4.3 mA 250 V 5A 230 V~2) - 0.8 VA - 1 mA~ - 250 V 3A 240 V~ - 1.2 VA 0.5 mA- 1 mA~ - 250 V 3A Continuous current Continuous operation Clearance > 20 mm Continuous current 48 V~/230 V~/240 V~ On/off switch. mode < 1 min (50/50 %) Ambient temperature Switch-on current Switching capacity with resistive load Min. switching capacity/switching current Bounce times Switching times, typical -, pick-up lag -, turn off delay Max. switching frequency Contact material Service life, mechanical -, 24 V-, 1 A, resistive load -, 230 V~, 3 A, resistive load Storage temperature Ambient temperature -, mounted on rail without clearance -, mounted on rail with clearance 20 mm Insulation coordination acc. to EN 50178 Overvoltage category Pollution severity Dimensions Mounting width Length (perpendicular to mounting rail) Height TS 32/TS 35 x 7.5 8A 2000 VA/100 W 250 mW/10 mA 3 ms 8 ms 8 ms 8 ms 7 ms 7 ms 7 ms 70 Hz 70 Hz 70 Hz AgNi, gold-flashed >107 switching operations > 5 x 105 switching operations >7 x 105 switching operations -40 C...+60 C 12 ms 11 ms 70 Hz -25 C...+40 C -25 C...+50 C III 2 11.2 mm NO/NC, 25 mm changeover contacts 70 mm (74 mm BL/SL version) 56 mm/51.5 mm 1) 2) 90 8 ms 16 ms 30 Hz Rated consumption with 24 VDC auxilary voltage. 230 V- on request 13 ms 12 ms 20 Hz 12 ms 11 ms 70 Hz 9 ms 8 ms 30 Hz 12 ms 11 ms 70 Hz 10 ms 9 ms 30 Hz 10 ms 9 ms 30 Hz Relay Couplers on Sockets RS 30 RS 30 RS 30 RS 30 RS 30 TTL Screw connection Screw connection Disconnect plug with Disconnect plug with 1 NO 1 changeover contact screw connection screw connection 1 changeover contact 1 NO and 1 NC 1 NC 6 7 8 Ordering data Connection method Screw connection (LP) Schematic circuit diagram 1 2 3 4 5 6 7 8 8 Contact NO NO NC NC changeo. c. changeo. c. changeo. c. NO NC 1167760000 1167660000 Input voltage 5 V-, TTL 12 V- 24 V- 24 Vb 48 V- 48 Vb 60 V- 115 V- 115 V~ 230 V~ 240 V~ Disconnect plug with screw connection (BL/SL) Digital signal processing 5 Function indicator None None Red LED None Green LED Red LED None Green LED Red LED None Green LED Red LED None Green LED Red LED None Green LED Red LED None Green LED Red LED None Green LED Red LED None Green LED Red LED None Green LED Red LED 1129660000 1129421001 1101661001 1101611001 1101621001 1129521001 1100961001 1100911001 1100921001 1101761001 1101711001 1101721001 1101861001 1101811001 1101821001 1181511001 1181521001 1101061001 1101011001 1101021001 1101161001 1101111001 1101121001 1101961001 1101911001 1101921001 1102061001 1102011001 1102021001 1155161001 1155111001 1155121001 1100260000 1100210000 1100220000 1100360000 1100460000 1100410000 1100420000 1101261001 1101211001 1101221001 1100560000 1100660000 1100610000 1100620000 1155261001 1155211001 1155221001 1102161001 1102111001 1102121001 1102261001 1102211001 1102221001 1128561001 1128511001 1128521001 1101461001 1101411001 1101421001 1101561001 1101511001 1101521001 1128661001 1128611001 1128621001 1100760000 1100860000 91 Relay Couplers on Sockets RS 30 RS 31 1 changeover contact with power contacts Usable for high switching-power Suitable for switching inductive loads Schematic circuit diagram Type RS 31, 24 V- RS 31, 24 V- RS 31, 24 V- Ordering data Rated data Input voltage Rated consumption - (W) Rated consumption - (VA) Drop-out current of the relay (at 20 C) Drop-out current of the relay (at 20 C) Max. output voltage Continuous current Derating curve mounted horizontally on rail without clearance Cat. No. 1128361001 1128331001 1128311001 Type RS 31, 48 V- Cat. No. 1150761001 Type RS 31, 115 V- Cat. No. 1150361001 Type RS 31, 115 V~ Cat. No. 1150461001 24 V-, 10 % 1W - 11.5 mA- - 250 V 16 A 48 V-, 10 % 1W - 13.5 mA- - 250 V 16 A 115 V-, +5 % -15 % 1W - 5.5 mA- - 250 V 16 A 115 V~, +5 % -15 % - 1 VA - 1.5 mA~ 250 V 16 A 60 A/200 ms 3.5 kVA/480 W 1 W/100 mA < 3 ms 60 A/200 ms 3.5 kVA/480 W 1 W/100 mA < 6 ms 60 A/200 ms 3.5 kVA/480 W 1 W/100 mA < 6 ms 60 A/200 ms 3.5 kVA/480 W 1 W/100 mA < 6 ms < 9 ms < 10 ms < 12 ms < 8 ms < 10 ms < 12 ms < 4 ms < 11 ms AgCdO 3 x 107 switching operations 2.5 x 105 switching operations 1128361001 1128331001 1128311001 -40 C...+60 C -25 C...+40 C AgCdO 3 x 107 switching operations 2.5 x 105 switching operations 1150761001 AgCdO 3 x 107 switching operations 2.5 x 105 switching operations 1150361001 AgCdO 3 x 107 switching operations 2.5 x 105 switching operations 1150461001 -40 C...+60 C -25 C...+40 C -40 C...+60 C -25 C...+40 C -40 C...+60 C -25 C...+40 C III 2 III 2 III 2 III 2 25 mm 70 mm 58 mm/53.5 mm 25 mm 70 mm 58 mm/53.5 mm 25 mm 70 mm 58 mm/53.5 mm 25 mm 70 mm 58 mm/53.5 mm Continuous current Ambient temperature Switch-on current Max. switching capacity with resistor load Min. switching capacity/switching current Bounce times Switching times, typical -, pick-up lag -, turn off delay Max. switching frequency Contact material Service life, mechanical - 230 V, 50 Hz, 3.5 kV A Status indicator Storage temperature Ambient temperature Insulation coordination acc. to EN 50178 Overvoltage category Pollution severity Dimensions Mounting width Length (perdendicular to mounting rail) Height with TS 32/TS 35 x 7.5 92 Red LED Yellow LED Green LED Relay Coupler on Locking Socket Profile RS 31 RS 31 with power contacts Type RS 31, 230 V~ RS 31, 230 V~ RS 31, 230 V~ Cat. No. 1128461001 1128431001 1128411001 Digital signal processing 230 V~, +5 % -15 % - 1 VA - 2.2 mA~ 250 V 16 A 60 A/200 ms 3.5 kVA/480 W 1 W/100 mA < 6 ms < 10 ms < 8 ms AgCdO 3 x 107 switching operations 2.5 x 105 switching operations 1128461001 1128431001 1128411001 -40 C...+60 C -25 C...+40 C III 2 25 mm 70 mm 58 mm/53.5 mm 93 Relay Couplers on Sockets RS 32 with 2 changeover contacts RS 32 RS 32 Schematic circuit diagram 9406021001 Ordering data Type RS 32 Rated data Input voltage Rated consumption - (W) Rated consumption ~ (VA) Drop-out current of the relay** (at 20 C) Drop-out current of the relay** (at 20 C) Max. output voltage Continuous current Derating curve mounted horizontally on rail without clearance Cat. No. 9406021001 Type RS 32 9406121001 9406321001 9406521001 Cat. No. 9406121001 Type RS 32 Cat. No. 9406221001 Type RS 32 Cat. No. 9406321001 12 V-, 10 % 0.6 W - 9.5 mA - 250 V 2x4A 24 V-, 10 % 0.6 W - 5 mA - 250 V 2x4A 24 V0, 10 % 0.6 W 0.9 VA 24 V-: 4.5 mA 24 V~: 2.5 mA 250 V 2x4A 48 V-, 10 % 0.6 W - 2 mA - 250 V 2x4A 2x6A 1400 VA 2x6A 1400 VA 2x6A 1400 VA 2x6A 1400 VA 4 ms 4 ms 4 ms 4 ms 13 ms 10 ms 13 ms 10 ms 13 ms 10 ms 13 ms 10 ms AgNi0.15, gold-flashed > 30x106 switching operations AgNi0.15, gold-flashed > 30x106 switching operations AgNi0.15, gold-flashed > 30x106 switching operations AgNi0.15, gold-flashed > 30x106 switching operations Red LED -40 C...+60 C -25 C...+40 C Red LED -40 C...+60 C -25 C...+40 C CSA Red LED -40 C...+60 C -25 C...+40 C Red LED -40 C...+60 C -25 C...+40 C CSA III 2 III 2 III 2 III 2 25 mm 70 mm 68 mm/63.5 mm 25 mm 70 mm 68 mm/63.5 mm 25 mm 70 mm 68 mm/63.5 mm 25 mm 70 mm 68 mm/63.5 mm Continuous current Ambient temperature Switch-on current Max. switching capacity with resistor load Min. switching capacity/switching current Bounce times Switching times, typical -, pick-up lag -, turn off delay Max. switching frequency Contact material Service life, mechanical -, 24 V-, 1 A, resistive load -, 230 V~, 3 A, resistive load Status indicator Storage temperature Ambient temperature Approvals Insulation coordination acc. to EN 50178 Overvoltage category Pollution severity Dimensions Mounting width Length (perpendicular to mounting rail) Height with TS 32/TS 35 x 7.5 94 Relay Couplers on Sockets RS 32 RS 32 Type RS 32 Cat. No. 9406421001 Type RS 32 Cat. No. 9406521001 Type RS 32 Cat. No. 9406621001 1122661001 1122761001 Type RS 32 Cat. No. 9406721001 Type RS 32 Cat. No. 1122661001 Type RS 32 Cat. No. 1122761001 48 V0, 10 % 0.6 W 0.9 VA 48 V-: 2 mA 48 V~: 4.5 mA 250 V 2x4A 60 V-, 10 % 0.6 W - 1.5 mA - 250 V 2x4A 115 V0, +5 % -15 % 0.5 W 0.6 VA 115 V-: 1 mA 115 V~: 1.5 mA 250 V 2x4A 230 V0, +5 % -15 % 1W 1 VA 230 V-: 1.2 mA 230 V~: 2 mA 250 V 2x4A 24 V/48 V0, 10 % 0.5 W/0.6 W 0.7 VA/0.9 VA -: 5 mA/2 mA ~: 3 mA/4.5 mA 250 V 2x4A 115 V/230 V0, +5 % -15 % 0.5 W/1 W 0.6 VA/1 VA -: 1 mA/1.2 mA ~: 1.5 mA/2 mA 250 V 2x4A 2x6A 1400 VA 2x6A 1400 VA 2x6A 1400 VA 2x6A 1400 VA 2x6A 1400 VA 2x6A 1400 VA 4 ms 4 ms 4 ms 4 ms 4 ms 4 ms 13 ms 10 ms 10 ms 10 ms 13 ms 10 ms 13 ms 10 ms 13 ms 10 ms 13 ms 10 ms AgNi0.15, gold-flashed > 30x106 switching operations AgNi0.15, gold-flashed > 30x106 switching operations AgNi0.15, gold-flashed > 30x106 switching operations AgNi0.15, gold-flashed > 30x106 switching operations AgNi0.15, gold-flashed > 30x106 switching operations AgNi0.15, gold-flashed > 30x106 switching operations Red LED -40 C...+60 C -25 C...+40 C Red LED -40 C...+60 C -25 C...+40 C Red LED -40 C...+60 C -25 C...+40 C Red LED -40 C...+60 C -25 C...+40 C Green LED -40 C...+60 C -25 C...+40 C Green LED -40 C...+60 C -25 C...+40 C III 2 III 2 III 2 III 2 III 2 III 2 25 mm 70 mm 68 mm/63.5 mm 25 mm 70 mm 68 mm/63.5 mm 25 mm 70 mm 68 mm/63.5 mm 25 mm 70 mm 68 mm/63.5 mm 25 mm 70 mm 68 mm/63.5 mm 25 mm 70 mm 68 mm/63.5 mm 95 Digital signal processing 9406221001 9406421001 9406621001 9406721001 Multiple Socket Interface RSM (Relay Coupler) RSM 4 R with one changeover contact each RSM 4 RS Also available as opto-coupler (max. 48 V), See page 120/121 Schematic circuit diagram Rated data Input voltage Rated consumption -(W) Rated consumption ~(VA) Pick-up current - (mA) - (mA) Pick-up current ~ (mA) - (mA) soldered relay plug-in relay soldered relay plug-in relay soldered relay plug-in relay soldered relay plug-in relay Drop-out current of the relay (at 20 C) Max. output voltage Continuous current Derating-curve a = mounted horizontally on rail without clearance b = mounted horizontally on rail with clearance 20 mm RSM 8 R 4 relays, soldered 8 relays, soldered RSM 8 RS 4 relays, plug-in 8 relays, plug-in Fixing feet can also be mounted turned through 180 DC voltage, positive switching 24 V- 0.45 W 0.55 W - - 12 mA 23 mA - - 24 V0 0.45 W - 0.5 VA - - 12 mA - 16.5 mA 48 V- 0.45 W 0.55 W - - 10 mA 14 mA - - 48 V0 0.45 W - 0.6 VA - - - - - 115 V~ - - 0.6 VA 0.6 VA - - - 5 mA 115 V0 - - 0.6 VA 0.6 VA 5 mA - 6 mA - 230 V~ - - 0.9 VA 1.2 VA - - - 4 mA 230 V0 - - 0.9 VA 1.2 VA 3 mA - 3.5 mA - 2 mA 250 V 6A 250 V 6A 1.5 mA 250 V 6A 250 V 6A 1 mA 250 V 6A 250 V 6A 1 mA 250 V 3A 250 V 3A 10 ms/12 ms 15 ms/20 ms 3 ms 8A 2000 VA 10 ms 10 ms 3 ms 8A 2000 VA 8 ms/10 ms 5 ms/8 ms 3 ms 8A 2000 VA 10 ms 10 ms 3 ms 8A 2000 VA 8 ms/10 ms 7 ms/8 ms 3 ms 8A 2000 VA Continuous current Ambient temperature Switching times, typical -, pick-up lag (-/~) -, turn off delay (-/~) Bounce times Switch-on current Switching capacity with resistive load Min. switching capacity/switching current Contact material Service life, mechanical -, 24 V-, 1 A, resistive load -, 230 V~, 3 A, resistive load Storage temperature Ambient temperature Insulation coordination acc. to EN 50178 Overvoltage category Pollution severity Dimensions Conductor cross-section (screw connection) Spare relay (pluggable) for 24 V-RSM types for 48 V-RSM types for 115 V, 230 V-RSM types 96 8 ms 10 ms/10 ms 12 ms 7 ms 15 ms/20 ms 11 ms 3 ms 3 ms 3 ms 8A 8A 8A 2000 VA 2000 VA 2000 VA 250 mW/10 mA AgNi 90/10, AgNi0,15, gold-flashed > 30x106 switching operations >5 x 105 switching operations >7 x 105 switching operations -40 C...+60 C -25 C...+50 C III 2 0.5...2.5 mm2 Input voltage 24 V- 24 V- 48 V- 48 V- 115 V- 115 V- 115 V- Contact material AgNi 90/10 AgNi 90/10 AgNi 90/10 AgNi 90/10 AgNi 90/10 AgNi 90/10 Au 5 Cat. No. 8630780000 4058480000 8630790000 4058740000 8630770000 4058500000 4156970000 Notes RT 314024 with yoke RT 314024 without yoke RT 314048 with yoke RT 314048 without yoke RT 314110 with yoke RT 314110 without yoke ZLT input relay KHU/BV 1680 Multiple Socket Interface RSM RSM 16 RS 16 relays, plug-in Red LEDs, further colours on request Ordering data Connection technology Input/output Ribbon cable/ Screw connection Male connector block with interlock according to DIN 41651/Parts 1 and 2 Input voltage 24 VDC AC-DC/DC voltage RSM 4 R/RS RSM 8 R/RS RSM 16 R/RS Positve 4 relays 8 relays 16 relays switching1) Relay pluggable - Relay pluggable 11133610013) 11134610013) 11135610013) 11136610013) 11137610013) 11138610013) 1173461001 1173561001 1173661001 24 VDC Screw connection * Input: - Relay pluggable Screw connection and male conn. block acc. to IEC 603-1/ DIN 41651 - Relay soldered male conn. block acc. to IEC 603-1/ DIN 41651 * Output: Screw connection Negative switching2) 24 V0 48 VDC 1113961001 1114061001 1114161001 1114261001 1114361001 1114461001 1173761001 48 V0 Relay soldered 1113161001 1100061001 1113261001 1100161001 80175810014) 1112361001 1112761001 * 80036710014) * 1107761001 * 1112661001 * 80182210014) * 1107861001 * 1113061001 Mounted width 145 mm 145 mm 285 mm 285 mm 75 mm 75 mm 145 mm 145 mm 285 mm 285 mm 75 mm 145 mm 285 mm 1112461001 75 mm 75 mm 145 mm 145 mm 285 mm 285 mm 75 mm * * * * 115 V0 1114561001 1114661001 1114761001 75 mm 145 mm 285 mm 230 V~ 1114861001 1114961001 1115061001 75 mm 145 mm 285 mm 75 mm 145 mm 285 mm 230 V0 1123461001 1108061001 1108261001 Digital signal processing DC voltage, negative switching Spare relays on request 1) 2) Common negative potential, positive is switched Common negative potential, negative is switched 3) 4) Approval by the Germanischer Lloyd Empty modules without relays 97 Relay Socket Module for Industry Relays Weidmuller relay sockets for mounting rails enable plug-in relays most commonly used in industry to be mounted; they make possible installations in which the control section and power section are perfectly separated. The coil terminals and the connection terminals are located on opposite sides of the locking socket modules. The conductors are connected via screw terminals; the securing in the terminal is achieved by a clamping yoke system. This method has been used by Weidmuller for many years, and is the only method that guarantees a reliable connection in industrial applications. Thanks to their combination foot, these modules can be mounted onto TS 32, TS 35x7.5, TS 35x15 mounting rails in accordance with European standards EN 50035 and EN 50022. The connections are marked according to European Standard EN 50005. The modules are designed for DC relays (with a damping diode parallel to the coil, as well as a protection diode for reverse polarity protection) and AC relays. They can be provided with an LED on request. The contacts available at the output are: 2, 3 or 4 changeover contacts. The marking of the contacts in the following diagram corresponds to European standard EN 50005. The standard range of relay socket modules is divided as follows: DC voltage Ac voltage The input terminals are doubled, in order to pick off the poles. Note the following for DC current operation: A1 = + A2 = - 98 Group 1: RS 3 (2 changeover contacts) RS 4, RS 14 (4 changeover contacts) For relays of the type "international" Group 2: RS 6 (2 changeover contacts) Size 1 RS 7, 17 (3 changeover cont.) Size 2 RS 8, 18 (4 changeover cont.) Size 2 RS 9 (2 changeover cont.) Size 2 For relays of the type "European". Relays with 4 changeover contacts (size 2) can be secured to RS 7, RS 17 and RS 9; however, only 3 or 2 changeover contacts are connected to the terminals, which results in space savings. Group 3: RS 21 (2 changeover contacts) RS 23 (3 changeover contacts) RS 24 (2 x 3 changeover cont.) For relays with one socket with 8 or 11 pins. The table on page 87 offers an overview of the most important manufacturers of relays in groups 2, 3 and 4. The list is provided for information purposes only, and does not claim to be complete List of Plug-in Relays for Weidmuller Relay Socket Modules Group 1 International relays Group 2 European relays Group 3 Relays with socket oktal * RS 3 2 changeover contacts * RS 4, RS 14 4 changeover contacts * RS 6 2 changeover contacts (Size 1) * RS 7, RS 17 3 changeover cont. (Size 2) * RS 8, RS 18 4 changeover cont. (Size 2) * RS 9 2 changeover cont. (Size 2) Relay type * - * Type 40701 * Type 40701 * RS 21 2 changeover contacts * RS 23 3 changeover contacts * RS 24 2x3 changeover contacts Relay type * * - - ELESTA * * - - FEME * * - - GRUNER * * - - HALLER * * - - ITT (MTI) * MAT 2 * MAT 4 FUJITSU * FRL 263-02 * FRL 263-04 KUHNKE * * Type 111 A4 - KUKE * * - - NATIONAL * HC 2 * HC 4 OMRON * MY 2 * MY 4 POTTER & BRUMFIELD * * Series KH - RAPA * * - - Tyco/SCHRACK * ZT 4 * PT 4 SDS * HC 2 * HC 4 TEC * * Type 1301 - ZETTLER * * TEC 1401 - * * * * * * * * * * * * * * - - - - - - - - Series Series Series Series Series Series 9065 G 9059 G/9066 G 9059 G/9066 G 9059 G/9066 G H-561 Size 1 H-561 Size 2 Relay type * * Type 41454 * Type 41454 - * SKR 085 * SKR 115 * RCP 8 * RCP 11 * RCP 11 * Series 668 B 2 changeover contacts * Series 668 A 3 changeover contacts * Series 668 A 3 changeover contacts * HB-1/1 * HB-1/2 * Series H-561 Size 2 * Series H-561 Size 2 * Type 24 * HB-1/2 * - * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * - - Type 25 Type 25 Type 25 - - - - - - - - Miniature Miniature Miniature Miniature relays relays relays relays Type Type Type Type 01 02 02 02 - - - - MHS-2 MHS-4 MHS-4 MHS-4 * Universal relays-M/-H/-U * Universal relays-M/-H/-U * Universal relays-M/-H/-U * * * - - - * * * - - - * MK 2 * MK 3 * MK 3 - Series R 10 Series R 10 Series R 10 Series 012 Size 1 Series 012 Size 2 Series 012 Size 2 Series 012 Size 2 Relays N, S, W Size 1 Relays N, S, W Size 2 Relays N, S, W Size 2 Relays N, S, W Size 2 K2 K4 K4 K4 Type 1350 Type 1360 Type 1360 Type 1360 AZ E 20, AZ 420, AZ 420 AZ E 21, AZ 421, AZ 421 AZ E 21, AZ 421, AZ 421 AZ E 21, AZ 421, AZ 421 * FRL 256-02 * FRL 256-04 * FRL 256-04 Digital signal processing Manufacturer EBERLE * Series KAP * Series KAP * Series KAP * Series C-Type CKR * Series C-Type CKR * Series C-Type CKR * Series RN/RC * Series RN/RC * Series RN/RC * Type 1210 * Type 1210 * Type 1210 W W W W * AZ 1010 - AZ 509 2 C * AZ 1010 - AZ 509 3 C * AZ 1010 - AZ 509 3 C 99 Relay Sockets for Industry Relays PT 4 industry relays 4-pole, with test button Rated data Contact data Contact number and type Contact version Contact material Max. braking capacity AC Rated voltage Continuous current Switch-on current Min. contact rating 4 changeover contacts Single contacts AgNi 90/10, AgNi 90/10 htv 1500 VA 250 V~ 6 A / contact 12 A / contact 24V, 10 mA / 20 m, 1 mA htv DC coil > 30x106 AC coil > 20x106 15/10 ms 5 ms 2.5 kVeff coil / contact B, 60 V~/75 V 250 V 2 III B/250 VDE, UL, CSA Mechanical service life Response / drop out time Bounce time Test voltage Isolation acc. to IEC664 Rated voltage Pollution severity Overvoltage category Insulation group / reference voltage Approvals Miscellaneous data Protection class Flammability class UL 94 Ambient temperature DC coil AC coil Weight IP50 V-0 -40 ... + 70 C -40 ... + 70 C 30g Correspond. relay socket * Relay sockets Type RS 3, RS 4 and RS 14 * Alternatives to ZT 4 see table on page 99 6 12 24 48 60 115 V- V- V- V- V- V- Type (ZT 4) PT 570006 PT 570012 PT 570024 PT 570048 PT 570060 PT 570110 Best.-Nr 8074650000 8054360000 1180700000 8074670000 8074680000 8074700000 6 12 24 48 60 115 230 V~ V~ V~ V~ V~ V~ V~ PT PT PT PT PT PT PT 8074710000 8074730000 1181800000 1180900000 8074760000 1180800000 1181100000 Ordering data Retainer clip for SIEMENS-Relays 100 570506 570512 570524 570548 570560 570615 570730 PT 28800 8572170000 Relay Sockets for Industry Relays RS 3 RS 4 RS 14 Relay sockets for DC and AC voltage relays 0125661001 Relay type* Contacts on module Ordering data Relay socket for AC relays (without diode) With red LED (230 V~) Relay socket for DC relays with suppressor diode and reserve voltage protection (diode 1 N 4007) With red LED (24 V-) With green LED (24 V-) Dimensions Relay socket width Insulation stripping length Connection data Screw connection, solid Screw connection, flexible Conductor cross-section Rated data Coil voltage (types without LED) Contact voltage Contact current Accessories Mounting rail (2 m lenghts) End bracket (thickness mm) Insert tag (blanc)** Protective strip, transparent** Retainer clip for Schrack relays Sockeltyp Schrack Type PT 5 4-pole Schrack Type PT 5 4-pole Schrack Type PT 5 4-pole 2 changeover contacts 4 changeover contacts 4 changeover contacts RS 3 0115161001 RS 4 0116261001 RS 14 0125561001 Digital signal processing with fixing foot for TS 32/TS 35x7.5 and TS 35x15 1157561001 0115061001 0116161001 0125661001 0116121001 1127661001 0115011001 8025451001 35 mm 7 mm 65 mm 7 mm 45 mm 7 mm 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 250 V0 250 V~ 5A Type TS 32 TS 35x7.5 TS 35x15 EWK 2 EW 35 ESo 7 SSt 7 ZG 28800 250 V0 125 V~ 5A Cat. No. 0122800000 0383400000 0498000000 0199360000 0383560000 0515200000 0515300000 0116000000 250 V0 125 V~ 5A Type TS 32 TS 35x7.5 TS 35x15 EWK 2 EW 35 ESo 7 SSt 7 ZG 28800 Qty. - - - 50 50 - 100 25 Cat. No. 0122800000 0383400000 0498000000 0199360000 0383560000 0515200000 0515300000 0116000000 Qty. - - - 50 50 - 100 25 * Relay not included in delivery 101 Relay Sockets for Industry Relays Relay socket for DC and AC voltage relays with locking foot for TS 32 TS 35x7.5 and TS 35x15 RS 6 Assigning commercially available relays to the Weidmuller relay sockets RS 6...RS 24: * Relay socket RS 6 Siemens cradle relay, size I Zettler cradle-operated relay AZ 420 RAPA range 012, size 1 * Relay socket type RS 7, RS 8, RS 9, RS 17 and RS 18 Siemens cradle relay, size II Zettler cradle-operated relay AZ 421 RAPA range 012, size II * Relay socket type RS 21, RS 23 and RS 24 Siemens/Schrack Universal Industry relay RS/RN/RC Siemens industry relay 10 Kuhnke universal relay Zettler industrial relay AZ 1010 RAPA range C 0115461001 RS 6 RS 8 RS 9 RS 17 RS 18 0126061001 (No claim is made that this is a complete list of manufacturers of relays or types of relays.) Relay type* Ordering data Relay socket for AC relays (without diode) Socket type Relay socket for DC relays with suppressor diode and reserve voltage protection (diode 1 N 4007) With red LED (24 V-) Kamm-R.(R) Gr. I Kamm-R.(R) Gr. II Kamm-R.(R) Gr. II Kamm-R.(R) Gr. II Kamm-R.(R) Gr. II Kamm-R.(R) Gr. II 2 changeov. c. 3 changeov. c. 4 changeov. c. 2 changeov. c. (e. g. B 104) (e. g. B 110) (e. g. B 110) (e. g. B 104) RS 6 RS 7 RS 8 RS 9 0115361001 3 changeov. c. 4 changeov. c. (e. g. B 110) (e. g. B 110) RS 17 RS 18 0115261001 0125861001 0115461001 0116361001 0188961001 0126061001 0126011001 With green LED (24 V-) Dimensions Relay socket width Insulation stripping length Connection data Screw connection, solid Screw connection, flexible Conductor cross-section 35 mm 7 mm 50 mm 7 mm 65 mm 7 mm 35 mm 7 mm 35 mm 7 mm 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 0.5...4 mm2 0.5...4 mm2 0.5...2.5 mm2 0.5...2.5 mm2 AWG 26...14 AWG 26...14 Rated data Coil voltage (types without LED) Contact voltage Contact current Accessories Mounting rail (2 m lenghts) 250 V0 250 V~ 5A Type TS 32 TS 35x7.5 TS 35x15 EWK 2 EW 35 ESo 7 SSt 7 250 V0 250 V~ 5A 250 V0 125 V~ 5A Cat. No. 0122800000 0383400000 0498000000 0199360000 0383560000 0515200000 0515300000 250 V0 250 V~ 5A 50 V0 125 V~ 5A Type TS 32 TS 35x7.5 TS 35x15 EWK 2 EW 35 ESo 7 SSt 7 End bracket (thickness mm) Insert tag (blanc)** Protective strip, transparent** Retainer clip for Schrack relays * Relay not included in delivery 102 Qty. - - - 50 50 - 100 45 mm 7 mm 250 V0 125 V~ 5A ** Not suitable for RS 12 Cat. No. 0122800000 0383400000 0498000000 0199360000 0383560000 0515200000 0515300000 Qty. - - - 50 50 - 100 Relay Coupler, Relay Sockets Module for Industry Relays RS 21 RS 23 RS 24 0167161001 Plug-in relay for Octal socket 8-pole Plug-in relay for submagnal socket 11-pole RS 21 on request RS 23 8010061001 RS 24 on request 0167161001 0188661001 on request 35 mm 7 mm 40 mm 7 mm 75.5 mm 7 mm 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 0.5...4 mm2 0.5...2.5 mm2 AWG 26...14 250 V0 250 V~ 6A Type TS 32 TS 35x7.5 TS 35x15 EWK 2 EW 35 ESo 7 SSt 7 250 V0 250 V~ 6A 250 V0 250 V~ 6A Cat. No. 0122800000 0383400000 0498000000 0199360000 0383560000 0515200000 0515300000 Digital signal processing 2 changeov. c. 3 changeov. c. 2 x 3 changeov. c. Qty. - - - 50 50 - 100 103 Opto-coupler 104 Opto-coupler - low power uptake on control side - high switching frequency - no contact bounce - wear-free switching - insensitive to vibration - use independent of location - no mechanical parts - long life - high insulation voltage Because of these features, opto-coupler are an alternative to conventional, mechanical relay interfaces. For industrial usage, Weidmuller offers modules with various input voltages and housings. Basic construction of the opto-coupler To eliminate these effects where possible, interface: Weidmuller opto-coupler use almost exclusively semiconductors which have a The heart of the system is the optolong life in terms of CTR. electronic component (opto-coupler) that effects the coupling. Moreover, the insulation of a module is highly important, since the actual coupling of the input and output circuits takes place optically. Thus the optical component has to guarantee separation of Input from Output to both circuits even in case of a defect. control periphery Weidmuller opto-coupler comply with DIN VDE 0884 to provide a maximum level of safety. Sender Receiver An important parameter of this type of modules is the CTR = current transfer rate. Appropriate switching circuits need to be included to ensure that the entire component provides reliable separation in accordance with DIN VDE 0106, Part 101. The CTR is given in % and is the ratio between the input current IF and the maximum available output current IC. Example: IF = 10 mA; CTR = 100% => IC = 10 mA. The CTR is affected by a number of parameters such as: - Ambient temperature - efficiency of the luminescence diode - geometric dimensions within the module Circuit diagram of an opto-coupler It also drops with time. The result is that the switching levels change due to ageing. Opto-coupler for protective separation or galvanic isolation The most important precondition for achieving protective separation with optoelectronic coupling modules is the partial discharge test in accordance with DIN VDE 0884. Double or reinforced insulation for protective separation must be discharge proof. High voltage tests, as are usual with relays, cannot be carried out with semi-conductors, because they could lead to the destruction of the semi-conductor. Safe separation for the given rated voltage is applicable to coupling modules that are integrated into opto-couplers if: CTR in % - the opto-couplers are tested according to DIN VDE 0884 CTR as a function of operating life t (Life time) - clearance and creepage distances on the PCB and connection elements correspond to EN 50 178, DIN VDE 0106 and 0109. 105 Digital signal processing With increasing automation, potential separation between the control and field sides of circuits is becoming increasingly important. The control unit being the core of the automation must be electrically safe and free from feedback when coupled with the various sensors and actuators. Optocoupler are being used in a growing number of applications. They offer the necessary safety and have further advantages such as: Opto-coupler Control side of the opto-coupler interface 3 basic circuits are to be differentiated on the input side of the opto-coupler#s interface: - as a pure DC input with polarity protection diode wich prevents the opto-coupler from being destroyed if the input polarity is reversed. - as an AC/DC input: Wrong polarity of the DC input signal is not possible with this switching. The disadvantage of an AC/DC input circuit (driven by DC signal) is the low switching rate since the charging capacitor (CL, necessary for AC-input signal) lowers the max. switching rate. - pure AC-Input: * Sample circuit Here, too, the charging capacity lowers the max. switching rate considerably. Weidmuller opto-coupler with AC/DC or AC input signals are designed for 40...60 Hz power supply. With AC-signal input the max. switching rate is below half the power supply frequency. A high switching rate is not possible, otherwise continuous switching in tune with the power frequency would occur. 106 Output side of the opto-coupler Weidmuller opto-coupler are designed and sized for a wide variety of applications. Demands regarding the load side of optocouple modules could be: - power amplification - signal conditioning AC/DC, DC/AC - short-circuit protection - interference proof, etc. To fulfil these requirements, the opto-coupler must contain additional electronic components which determine the functionality of the opto-coupler. Thus there are 2 basic output variations for opto-coupler Output as - 2 pole and - 3 pole circuits 2-pole DC output * Wiring example The 2-pole DC output is comparable to a conventional switch. With this type it is immaterial where the load is in the output circuit. It is, however, important to provide the necessary output supply voltage with the right polarity. Opto-coupler 2-pole AC output Zero voltage switch Sample circuit A special semiconductor element (TRIAC) in the output stage of the opto-coupler is used to switch AC voltages. As for the DC-versions the appropriate parameters (such as voltage, frequency, max. load current, ambient temperature) should be given consideration. A neutral voltage switch ensures that the load is switched only in the voltage zero. To protect against voltage spikes, the modules are allways fitted with appropriate protection elements (varistors, RC-combination). To prevent decoupling of interference signals to other leads the load side should be protected. Protection Standards Weidmuller opto-coupler comply with the following standards: Protective circuit for DC output EN 50 178 Furnishing of power engineering systems with electronic equipment DIN VDE 0106 Part 101 Protection against flow of dangerous currents into the human body; basic requirements for reliable separation within electrical equipment. DIN VDE 0884 Optoelectronic coupling devices for reliable Protective circuit for AC output separation Application example DIN VDE 0109 Insulation coordination within low-voltage PLC Inputs Inputs system including clearance and creepage distances for equipment Protection Opto-coupler output Optoc-oupler input Digital signal processing The derating curve shows the dependency of the output current as a function of the Ambient temperature (see under the respective product on the following pages). This type of output stage requires for safe function a potential-linked output voltage supply with an output that is either positive switching (common reference potential is GND or 0 V) or negative switching (common reference potential is the positive voltage pole). All opto-coupler have a protective circuit in the output (generally a free-wheeling diode). Load The load current should not be higher than the stated max. output current. Continuously exceeding this value will destroy the output stage. Protective circuit Load Opto-couplers are normally given with an 3-pole DC output output voltage supply from 5...48 VDC. These values should not be cut or exceeded on any occasion. PLC Opto-coupler output Opto-coupler input Namurinitiator Actuator, e. g. solenoid Monitoring an actuator Position monitoring with namur intiator 107 Types of housing for opto-coupler Weidmuller coupler modules are enclosed in housings that are appropriate for industrial applications. The housings are suitable for fitting onto mounting rails TS 32, TS 35 x 7.5 or TS 35 x 15 in accordance with European Standards EN 50 035 and EN 50 022. Component housing EG Weidmuller component housings EG 1 and EG 2 are 18 mm wide. The fully enclosed EG housings are fitted with clamping yoke screw connections or push-on blade connectors for attaching wires. Conductors with the following cross-sectional dimensions can be connected: solid conductors: 0.5...4 mm2 or flexible conductors: 0.5...2.5 mm2. The component housing EG 7 has a special status. Is has been specifically designed to accommodate 10-mm slim opto-couplers. EG 7 opto-coupler modules can be mounted onto TS 32 or TS 35 rails. The RS EG7 locking socket is also available for the OST opto-couplers. The fully-enclosed EG 7 housing is fitted with clamping yoke connections. Conductors with the following crosssections can be connected: Component housing EG7: 0.5...1.5 mm2 Locking socket: 0.5...2.5 mm2. 108 Component Housing WAVEBOX Component housing WAVEBOX It is important for modern electronics to create a functional housing. Setting and operating functions must be guaranteed, technical demands regarding heat dissipation and EMC properties are to be supported. The ideal design saves space and mounting costs in the switchgear cabinet. Moreover, ergonomics and the design are gaining in importance for high-quality opto-couplers interfaces. The WAVEBOX fulfils these criteria and has the following distinguishing features: The WAVEBOX is characterised by: * Optimal width for any application (12.5 mm, 17.5 mm, 22.5 mm) * Large component assembly surface; SMD's can be mounted on the solder side * No tools required for assembly * Plug-in printed circuit board * Plug-in cross-connection via ZQV 2.5 N * Hinged, transparent cover * BLZ 5.08 screw/plug and socket connector * BLFZ 5.08 optional tension clamp/plug and socket connector * Marking option with WS tags * Suitable for snap-fitting on TS 35 Connection systems Available are BLZ screw-type connectors as well as the BLZF tension clamp system for up to 2.5 mm2 flexible conductors for maximum wiring flexibility. Printed-circuit board removal This takes place by pushing in the locking hooks in way of the cover and with drawing of the terminal level and printed circuit board from the housing. This must not take place with the supply connected. Cross-connection Housings of the same family arranged side by side, can be cross-connected in the base of the housing with the ZQV 2.5 N/2 cross-connector. The cross-connection can be loaded with a current of up to 8 A. By means of this arrangement, the supply voltage can be cross-connected from one electronic module to another. The voltage transferred from the cross-connection to the terminal level must not exceed 50 V. Air vents Slanted air vents control the temperature and ventilate the housing base. Modular system PLUGSERIES/PLUGOPTO is a new generation of pluggable SSR. The core is an innovative relay socket PXS or PXZ. Both products combine Weidmuller functionality and experience gained from the relay and terminal business. The PLUGopto is the ideal connection technology between SSR and the application. Modular principle The new PLUGSERIES is particularly service friendly. Commercially available SSRs are simply plugged: holding / dismounting clamps guarantee secure mounting; LED indicators with free-wheeling diode can be simply plugged. * Easy plugging of SSR - suitable for the standard design and RT * Independent connection technology: screw or tension clamp Rated cross-section 0.5 2.5 mm2 * Robust holding / dismounting clamp * Control voltage 24 Vac/Vdc * Rated switching voltage 24 Vdc, 24 Vac/Vdc, 230 Vac * Up to 5 A continuous current * Low wiring costs thanks to ZQV 2.5N (pluggable) cross-connectors * Service-friendly modular system - relay socket, LED indicator - holding clamp and SSR - mount onto TS 35 - marking options with WS marking tags and holding clamps * Pluggable LED indicator with free-wheeling diode Mini-coupler Miniconditioner MCZ The locking socket with opto-couplers RS 40 have a width of 11.2 mm. The modules on locking socket profiles are equipped with clamping yoke (screw connection) units for conductor connection. Connectable are: solid conductors: 0.5...4 mm2 flexible conductors: 0.5...2.5 mm2. All parts of the mini-coupler DKR and DKO meet the specifications for a design that is as slim as possible. The sensational width of a mere 6 mm can be achieved by employing the latest surface-mounted devices (SMD). There are 4 or 5 screw connections available which accept conductors with cross-sectional dimensions from 0.5...4 mm2. The minicoupler offer a wide range of options for coupling digital sensor/actuator signals between automation devices and the process stage. With DKO opto-coupler, signals from the field with different voltages can be picked up and unified. The MCZ-housing is distinguished as one of the slimest component-housings. A tool width of only 6 mm reduces space requirements in cabinets. The MCZ is characterized by: - Tension-clamp connection - integrated cross-connection option for input and output minimise wiring costs. The mini conditioner MCZO (opto-couplers) have 4 and 5 Z-tension spring connections. The clampable conductor crosssection is 0.5...1.5 mm2. Locking socket with multiple interfaces Multiple interfaces RSM are optionally available assembled with 4, 8 or 16 pluggable opto-couplers. Versions are available with joint positive and negative potentials in order to reduce wiring on the input side. PCB clamping yoke screw connecter elements have clamping yoke units for connecting conductors with the following cross-sections: solid conductors: 0.5...4 mm2 flexible conductors: 0.5...2.5 mm2 Digital signal processing Weidmuller locking socket RS Variants of the RSM couplers have male connector blocks on the input side for connecting pre-assembled cables, in accordance with IEC 603-1/DIN 41651. CE-marking Weidmuller opto-coupler are marked with the CE symbol and comply with the requirements of EN 50 081 Part 1 and EN 50 082 Part 2. They can therefore be used for both industrial as well as for commercial and light industry. Appropriate ESD measures should be taken during installation. If connecting wires are particularly long, overvoltage protection should be provided in order to prevent interference from electrical disturbance in the atmosphere. 109 Opto-coupler Electronic switching Output 24 V 4x 5 - 48 V 20 mA Housing EG 0558160000 Page 122 5 - 48 V 0.1 A 5 - 48 V 0.5 A 5 - 48 V 20 mA 5 - 48 V 2.5 A 0609860000 5 - 48 V 5A 24 - 250 V 3.5 A 5 - 48 V 0.1 A 8x 5 - 48 V 0.1 A 16 x 5 - 48 V 0.1 A 8220870000 Page 123 Page 130 WAVESERIES 8275190000 WOS 8237720000 Page 126 EG 7 8269050000 Page 131 Page 128 8281720000 Page 131 8092530000 8234580000 Page 132 RS 40 1160961001 1117461001 1161761001 8065031001 1177860000 Page 137 1119460000 Page 137 RSM 1123861001 1124261001 1124661001 1123761001 1125261001 8018220000 1125161001 8003671001 1124900000 8017581001 1124900000 1170200000 1153200000 1124900000 1170200000 1170200000 1153200000 1121300000 1153200000 1121300000 8082471001 1121300000 8021391001 1124900000 Page 139 1124900000 1170200000 1170200000 1153200000 1153200000 1121300000 1121300000 Page 139 Page 139 DKO 32 8008090000 8019580000 Page 116 DKO 35 Page 117 8008150000 8019590000 Page 116 Page 117 8028300000 8215630000 8215600000 8181990000 Page 118 Page 118 8215640000 8248790000 Page 117 DKO 35/32 8228640000 8228630000 Page 119 MCZ O 8365940000 Page 114 Page 118 8398940000 Page 115 8287730000 Page 114 8324610000 (5 V TTL) Page 115 PLUGSERIES POS/POZ 8610840000 8610860000 8610920000 8610930000 8610900000 8610910000 8610970000 8610980000 8610890000 8615590000 8610960000 8615630000 8615600000 Page 134 8615640000 8615620000 8615650000 Page 134 Reliable separation 110 24 V dc 24 Vuc/ac Replacement opto-coupler dc and ac/dc Empty socket Opto-coupler Electronic switching Output 48 V 4x 5 - 48 V 20 mA Housing EG 7 5 - 48 V 0.1 A 5 - 48 V 0.5 A 5 - 48 V 20 mA 5 - 48 V 2.5 A 5 - 48 V 5A 24 - 250 V 3.5 A 5 - 48 V 0.1 A 8x 5 - 48 V 0.1 A 16 x 5 - 48 V 0.1 A 8092550000 Page 132 8234590000 Page 132 RS 40 1161061001 Page 137 1161860000 Page 137 DKO 35 8151230000 Page 120 Output 115 V 4 xx 4 5 - 48 V 20 mA Housing EG 5 - 48 V 0.1 A 5 - 48 V 0.5 A 5 - 48 V 20 mA 5 - 48 V 2.5 A 5 - 48 V 5A 24 - 250 V 3.5 A 5 - 48 V 0.1 A 8 xx 8 5 - 48 V 0.1 A 16 xx 16 5 - 48 V 0.1 A 0131860000 Page 123 8235180000 WOS Page 125 EG 7 8296250000 Page 126 8259950000 Page 127 8275360000 Digital signal processing WAVESERIES Page 128 8092570000 8234600000 8397420000 8315590000 Page 133 RS 40 1161161001 1161960000 Page 137 DKO 32 8027980000 Page 119 DKO 35 8077860000 Page 119 8131660000 Page 120 MCZ O 8421060000 Page 114 Reliable separation Vdc Vuc/ac 111 Opto-coupler Electronic switching Output 230 V 4x Housing EG 5 - 48 V 20 mA 5 - 48 V 0.1 A 5 - 48 V 0.5 A 5 - 48 V 20 mA 5 - 48 V 2.5 A 5 - 48 V 5A 24 - 250 V 3.5 A 5 - 48 V 0.1 A 0546360000 Page 123 WAVESERIES 8275380000 WOS Page 125 EG 7 8092590000 8234610000 8387580000 8394990000 Page 133 RS 40 1161461001 1162060000 8182690000 Page 137 DKO 32 8008100000 Page 119 DKO 35 8008160000 Page 119 MCZ O 8421380000 Page 114 230 Vuc/ac 112 8275220000 Page 126 8275400000 Page 127 8275340000 Page 128 8x 5 - 48 V 0.1 A 16 x 5 - 48 V 0.1 A Opto-coupler Electronic switching Output 12 V 4x 5 - 48 V 20 mA Housing EGO 8011250000 Page 122 5 - 48 V 0.1 A 5 - 48 V 0.5 A 5 - 48 V 20 mA 5 - 48 V 2.5 A 5 - 48 V 5A 24 - 250 V 3.5 A 5 - 48 V 0.1 A 8x 5 - 48 V 0.1 A 16 x 5 - 48 V 0.1 A 0114260000 Page 122 WAVESERIES 8275500000 WOS Page 124 EGO 7 8092510000 8234570000 Page 132 RS 40 1118760000 1161660000 Page 137 RSM O 8017581001 8003671001 8018221001 1121200000 1121200000 1121200000 1124800000 1124800000 1124800000 Page 139 8021391001 8082471001 1121200000 1121200000 1124800000 Page 139 DKO 35 1124800000 Page 139 8184030000 Page 116 3...60 V EGO, 3...5 V 0266160000 Page 122 EGO, 3...12 V 8011250000 Page 122 WAVESERIES 8275430000 WOS 5 V Page 124 WAVESERIES Digital signal processing 8275210000 WOS 5 V TTL Page 129 WAVESERIES 8275390000 WOS 3.5 - 15 V Page 124 WAVESERIES 8275450000 WOS 12 - 28 V Page 129 WAVESERIES 8237730000 WOS 15 - 60 V Page 124 EGO, 7.5 V 8237730000 Page 124 8275440000 Page 127 8092490000 8234560000 Page 132 RS 40, 5 V 1118861001 1161560000 Page 137 RSM, 5 V 1123661001 1124061001 1124461001 1121100000 1121100000 1121100000 Page 139 DKO 32 Page 139 Page 139 8018620000 Page 116 DKO 35 8018630000 Page 116 DKO 32/35 8067100000 Page 120 8228650000 Page 116 Reliable separation 12 Vdc 12 Vuc/ac Replacement opto-coupler dc and ac/dc Empty socket 113 Opto-coupler in component housing mini coupler MCZ Opto-couplers MCZ O MCZ O 24 Vac/dc 20 mA MCZ O 24 Vac/dc 2 A2* MCZ O 120 Vac/dc MCZ O 230 Vac Output current Derating curve rated to ambient temperature a+b at Uin a = rowed without clearances on the mounting rail b = rowed with clearances 20 mm Ambient temperature 28 Vac/dc 126 Vac/dc 2A 241.50 Vac 26.4 Vac/dc b a 50 mA b a 20 mA 40 50 C 50C 20 mA 40 50 C 50C Schematic circuit diagram This module can be used: * between controller and sensor, for feedback of different statuses. * for direct switching of load currents up to a Adc, but also provides "online" information about the behaviour of the load current. The MCZ-O modules do have following features: * Reduction of installation- and power-up times by using the proved tension-clamp technology * Pluggable cross-connection units in the input side reduce wiring costs * 6 mm width Ordering data For TS 35 Technical data Input Input voltage Making threshold Input current at Unom Rated input consumption Max. input frequency Capacity working resistance to reduction at dissipated energy Functionality Output Supply voltage Max. output current Voltage drop at max. load current Pulse duration, limiting overload current (not periodic) Reverse current (close-circuit current) at Uout = 48 V Reverse polarity protection Free-wheel diode - typ. Switch-on delay (at ac phase position dependent) - typ. Switch-off delay (at ac phase position dependent) Short-circuit proof Insulation coordin./Reliable separation acc. to EN 50 178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances Insulation coordin.- and voltage proof, input/output mounting rail Opto-coupler Ambient temperature rowed on mounting rail without clearances Ambient temperature rowed with clearances 20 mm Storage temperature Conductor Conductor cross-section Approvals Overall width Accessories End plate Further accessories, dimensions and connection data 114 Type Cat. No. MCZ O 24 Vac/dc 8365940000 Type Cat. No. MCZ O 24 Vac/dc 8287730000 Type Cat. No. MCZ O 120 Vac/dc 8421060000 Type Cat. No. MCZ O 230 Vac 8421380000 24 Vac/dc 10 % (21.6...26.4ac/dc) 24 Vac/dc 20 % (19.2...28.8ac/dc) ac: 14.1 Vac / dc: 16.8 Vdc ac: 11.4 mA / dc: 9.6 mA approx.16 Vac/dc ac: 13 mA / dc: 12 mA ac: approx.220 mW dc: ca.195 mW ac: 10 Hz duty factor 1:2 dc: 30 Hz duty factor 1:2 no operating indication 120 Vac/dc -15 % +5 % approx.65 Vac/approx.70 Vdc approx.3 mA 230 Vac -15 % +5 % approx.170 Vac ac: 10 mA ac: 5 Hz duty factor 1:2 dc: 20 Hz duty factor 1:2 no operating indication ac: 5 Hz duty factor 1:2 5...48 Vdc 50 mA < 1.6 V < 150 mA / 10 ms max.0.16 mA 5...48 Vdc 20 mA < 1.6 V < 150 mA / 10 ms max.0.16 mA present 30 ms 40 ms present 300 V 6 kV III 2 5.5 mm 4 kVeff / 1 min acc. to VDE 0884 -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 300 V 6 kV III 2 3 mm 4 kVeff / 1 min acc. to VDE 0884 -25 C...+50 C ac: 5 Hz duty factor 1:2 dc: 10 Hz duty factor 1:2 no operating indication 5...48 Vdc 20 mA 1V < 150 mA / 10 ms max. 0.16 mA present ac: 10 ms / dc: 20 ms ac: 45 ms / dc: 40 ms 24 Vdc 20 % 2A (19.2...28.8 Vdc) present external necessary yes operating indication yes 300 V 6 kV III 2 5.5 mm 4 kVeff / 1 min acc. to VDE 0884 -25 C...+50 C -40 C...+85 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 300 V 6 kV III 2 5.5 mm 4 kVeff / 1 min acc. to VDE 0884 -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 -40 C...+85 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 Opto-coupler in component housing mini coupler MCZ Opto-couplers MCZ O MCZ O 24 Vdc/5 VTTL1* MCZ O 5 V TTL/5...48 Vdc2* Derating curve rated to ambient temperature a = rowed on the mounting rail without clearances b = rowed with clearances 20 mm This module can be used: 1* - between controller and actuator, for the signal conversion of 24 Vdc to 5 VTTL 2* - between controller and actuator, for the signal conversion of 5 VTTL to 5...48 Vdc Output current 5.25 Vdc a+b at Uin 28.8 Vdc 100 mA 8 mA a b a b 40 50 C 40 50 C Ambient temperature Schematic circuit diagram Input signal 2 s Output signal 2.5 s at 832461 Ordering data For TS 35 Technical data Input Supply voltage Input voltage Making threshold Input current at Unom Rated input consumption Max. input frequency Min. input impulse width Output Supply voltage Output voltage Max. output current Voltage drop at max. load current Pulse duration, limiting overload current (not periodic) Reverse current (static current) at Uout = 48 V Reverse polarity protection Free-wheel diode - typ. switch-on delay - typ. switch-off delay Insulation coordin./Reliable separation acc. to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances Insulation coordination/dielectric strength I/O to TS Opto-coupler Ambient temperature rowed on mounting rail without clearances Ambient temperature rowed with clearances 20 mm Storage temperature Conductor Conductor cross-section Approvals Overall width Accessories End plate Further accessories, dimensions and connection data Type Cat. No. MCZ O 24 Vdc 8324610000 24 Vdc 16 % (20...28 Vdc) approx.17 Vdc 4.7 mA (2.9.2..6.5 mA) dc: 112 mW 100 kHz switching ratio 1:2 50 kHz switching ratio 1:10 2 s 5 V (4.75...5.25 V) 5 V TTL (4.75...5.25 V) 8 mA, Fan Out = 20 LS-TTL Type Cat. No. MCZ O 24 Vdc 8398940000 5 Vdc 5 % 5 V TTL Digital signal processing 1s IIL = 1 A / IIH = 8 A 2.4 kHz 5...48 Vdc 100 mA 1.8 V 1 s (at 20 Vdc) 2.5 s (at 28 Vdc) present (input) present approx.27 s approx.210 s 300 V 6 kV III 2 5.5 mm 4 kVeff / 1 min acc. to VDE 0884 -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 300 V 6 kV III 2 5.5 mm 4 kVeff / 1 min acc. to VDE 0884 -25 C...+50 C -25 C...+50 C -40 C...+85 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm Type Cat. No. AP MCZ 1.5 8389030000 Page 305 115 Opto-coupler in component housing mini coupler DK Opto-couplers DKO DKO 5 Vdc DKO 5 VTTL DKO 12 Vdc DKO 24 Vac/dc * Coupling of digital sensor-/actuator-signals between PLC and process * Low cost solution for level- and potential-equalization * Low input power * Screw clamp connection technology * 6 mm width Schematic circuit diagram Switching ratio Switching ratio Ordering data For TS 32 For TS 35 With combination foot TS 32/TS 35 Technical data Input voltage Switch-on voltage Input current Max. input power Output voltage Max. output current Min. output current Max. switching frequency; switching ratio 1: 2 Y W Type DKO 5 Vdc DKO 5 Vdc Cat. No. 8018620000 8018630000 Type Cat. No. DKO 12 Vdc DKO DK5 5 VTTL 8228650000 Input: bottom 5 VTTL Input: bottom 5 Vdc 5 % 2.4 Vdc 10 mA 50 mW 5...48 Vdc 20 mA 50 A 20 Hz Type Cat. No. 8184030000 Type Cat. No. DKO 24 Vac/dc 8008090000 DKO 24 Vac/dc 8008150000 5...48 Vdc 100 mA 50 A 3 kHz Input: bottom 12 Vdc 20 % approx.7 V 11 mA 130 mW 24 Vdc 10 % 50 mA 50 A 10 kHz Input: bottom 24 Vac/dc 10 % 112.8 Vac/16.8 Vdc 11.4 mAac/9.6 mAdc 280 mVA/230 mW 5...48 Vdc 20 mA 50 A ac: 5 Hz dc: 10 Hz 1 A Switch-on delay 15 s approx.27 s 1 s 15 ms at dc Switch-off delay 70 s approx.35 s 2.5 s 25 ms at dc Voltage drop at max. load 1.6 V 1.6 V 1 V 1 V Insulation coordination to EN 50 178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances 150 V 4 kV IV 2 4 mm 300 V 6 kV IV 2 5.5 mm 300 V 6 kV IV 2 5.5 mm 300 V 4 kV III 2 4 mm Storage temperature Conductor Conductor cross-section Overall width -25 C...+50 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+50 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+50 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 12 mm -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm Accessories End plate Further accessories, dimensions and connection data Type AP DKT4 Page 305 Operating temperature 116 without clearances with clearances Cat. No. 0687560000 Type AP DK5 Page 305 Cat. No. 8268870000 Type AP DKT4 Page 305 Cat. No. 0687560000 Type AP DKT4 Page 305 Cat. No. 0687560000 Opto-coupler in component housing mini coupler DK Opto-couplers DKO DKO 24 Vdc DKO 24 Vdc DKO 24 Vdc DKO 24 Vdc Schematic circuit diagram Switching ratio Switching ratio Type Y W DKO 24 Vdc Cat. No. 8028300000 Type DKO 24 Vdc Cat. No. 8215640000 Type DKO 24 Vdc Cat. No. 8248790000 Type DKO 24 Vdc DKO 24 Vdc Technical data Input voltage Switch-on voltage Input current Max. input power Output voltage Max. output current Min. output current Max. switching frequency; switching ratio 1: 2 Input: top 24 Vdc 10 % approx.19 V/7.5 mA 15 mA 360 mW 5...48 Vdc 20 mA 50 A 3 kHz Input: bottom 24 Vdc 10 % approx.19 V/7.5 mA 15 mA 360 mW 5...48 Vdc 20 mA 50 A 3 kHz Input: bottom 24 Vdc 10 % approx.19 V/7.5 mA 8.5 mA 204 mW 5...48 Vdc 20 mA 50 A 3 kHz Input: bottom 24 Vdc 10 % approx.17 V 6 mA 145 mW 5...48 Vdc 500 mA 50 A 200 Hz Switch-on delay approx.50 s approx.50 s approx.50 s approx.40 s Switch-off delay approx.80 s approx.80 s approx.80 s approx.65 s Voltage drop at max. load 900 mV 900 mV 900 mV 800 mV Insulation coordination to EN 50 178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances 300 V 4 kV II 2 4 mm 300 V 4 kV II 2 4 mm 300 V 4 kV III 2 4 mm 300 V 4 kV II 2 4 mm Storage temperature Conductor Conductor cross-section Overall width -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm Accessories End plate Further accessories, dimensions and connection data Type AP DKT4 Page 305 Operating temperature without clearances with clearances Cat. No. 0687560000 Type AP DKT4 Page 305 Cat. No. 0687560000 Type AP DKT4 Page 305 Cat. No. 0687560000 Type AP DKT4 Page 305 Cat. No. 8019580000 8019590000 Digital signal processing Ordering data For TS 32 For TS 35 Cat. No. 0687560000 117 Opto-coupler in component housing mini coupler DK Opto-couplers DKO DKO 24 Vdc DKO 24 Vdc DKO 24 Vdc DKO 24 Vac/dc * Coupling of digital sensor-/actuator-signals between PLC and process * Low cost solution for level- and potential-equalization * Low input power * Screw clamp connection technology * 6 mm width Schematic circuit diagram Switching ratio Switching ratio Mode: Ordering data For TS 32 For TS 35 With combination foot TS 32 / TS 35 Technical data Input voltage Switch-on voltage Input current Max. input power Output voltage Max. output current Min. output current Max. switching frequency; switching ratio 1: 2 Type Y W DKO 24 Vdc Cat. No. 8215630000 Input: top 24 Vdc 10 % approx.17 Vdc 6 mA 145 mW 5...48 Vdc 500 mA 50 A 200 Hz Type DKO 24 Vdc green yellow red Cat. No. 8181990000 Load current 500mA Idling Short circuit Type DKO 24 Vdc Cat. No. Type 8215600000 Input: bottom 24 Vdc 10 % approx.18 Vdc 12 mA 290 mW 24 Vdc 10 % 2A Input: top 24 Vdc 10 % approx.18 Vdc 12 mA 290 mW 24 Vdc 10 % 2A DKO 24 Vac/dc 8228630000 Input: bottom 24 Vac/dc 20 % approx.16 Vac/dc 13 mAac/12 mAdc 220 mVA/195 mW 24 Vdc 20 % 2A 100 Hz 100 Hz ac: 10 Hz dc: 30 Hz Switch-on delay approx.40 s 2 ms Switch-off delay approx.65 s 7 ms Voltage drop at max. load 800 mV Insulation coordination to EN 50 178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances Operating temperature Storage temperature Conductor Conductor cross-section Overall width 300 V 4 kV III 2 4 mm -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm Accessories End plate Further accessories, dimensions and connection data Type AP DKT4 Page 305 118 without clearances with clearances 300 V 4 kV III 2 3 mm -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 12 mm Cat. No. 0687560000 Cat. No. Type AP DKT4 Page 305 300 V 4 kV III 2 3 mm -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 12 mm Cat. No. 0687560000 Type AP DKT4 Page 305 300 V 6 kV IV 2 5.5 mm -25 C...+40 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm Cat. No. 0687560000 Type AP DK 5 Page 305 Cat. No. 8268870000 Opto-coupler in component housing mini coupler DK Opto-couplers DKO DKO DK5 24 Vdc DKO 115 Vac/dc DKO 230 Vac/dc Type Cat. No. DKO 115 Vac/dc 8027980000 DKO 115 Vac/dc 8077860000 Type Cat. No. DKO 230 Vac/dc 8008100000 DKO 230 Vac/dc 8008160000 DKO 24 Vdc 8228640000 Input: top 24 Vdc 20 % approx.17 Vdc 4.7 mA 112 mW 5 VTTL 8 mA, Fan Out = 20 LS-TTL Input: bottom 115 Vac/dc +5 % -15 % approx.65 Vac/approx.66 Vdc 2.65 mAac/3 mAdc 390 mVA/350 mW 5...48 Vdc 50 mA 100 kHz 1:2/50 kHz 1:10 ac: 5 Hz/dc: 20 Hz Input: bottom 230 Vac/dc +5 % -15 % approx.130 Vac/approx.140 Vdc 1.8 mAac/1.7 mAdc 395 mVA/370 mW 5...48 Vdc 20 mA 50 A ac: 5 Hz/dc: 20 Hz Switch-on delay 1 s 17.4 ms 20 ms Switch-off delay 2.5 s 27.4 ms 20 ms <1.6 V <1.6 V 300 V 6 kV IV 2 5.5 mm -25 C...+40 C -25 C...+50 C - 40 C...+85 C AWG 22..12 0.5...4 mm2 6 mm 300 V 4 KV III 2 3 mm -25 C...+50 C -25 C...+50 C -40 C...+85 C AWG 22...12 0.5...4 mm2 6 mm Schematic circuit diagram Switching ratio Ordering data For TS 32 For TS 35 With combination foot TS 32/TS 35 Technical data Input voltage Switch-on voltage Input current Max. input power Output voltage Max. output current Min. output current Max. switching frequency; switching ratio 1: 2 Type Cat. No. Y W Voltage drop at max. load Insulation coordination to EN 50 178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances Operating temperature Storage temperature Conductor Conductor cross-section Overall width 300 V 4 kV III 2 5.5 mm -25 C...+40 C -25 C...+50 C -25 C...+85 C AWG 22...12 0.5...4mm2 6 mm Accessories End plate Further accessories, dimensions and connection data Type AP DK5 Page 305 without clearances with clearances Cat. No. 8268870000 Type AP DKT4 Page 305 Cat. No. 0687560000 Type AP DKT4 Page 305 Digital signal processing Switching ratio Cat. No. 0687560000 119 Opto-coupler in component housing mini coupler DK Opto-couplers DKO DKO 35 48 Vdc DKO 35 60 Vdc DKO 35 125 Vdc W Schematic circuit diagram Ordering data For TS 32 For TS 35 With combination foot TS 32 / TS 35 Technical data Input voltage Input current Input nominal power Total power loss Making threshold Input reverse voltage Type Y W Cat. No. Type Cat. No. Type Cat. No. DKO 35 48 Vdc 8151230000 DKO 35 60 Vdc 8067100000 DKO 35 125 Vdc 8131660000 48 Vdc 10 % 3.7 mA 20 % 178 mW 400 mW approx.32 Vdc max. 1 kV 60 Vdc 10 % 5.6 mA 20 % 340 mW 420 mW approx.42 Vdc / 5.3 mA max. 1 kV 125 Vdc 10 % 1.7 mA 20 % 215 mW 400 mW approx.80 Vdc max. 1 kV Output voltage Output current Voltage drop at max. load 5...28 Vdc max. 20 mA 1.6 V 5...48 Vdc max. 100 mA 0.8 V 5...28 Vdc max. 20 mA 1.6 V Feature of output circuit Indication Disconnection plug LED red LED green Disconnection plug LED red Dielectric strength input/output Dielectric strength to mounting rail Clearances and creepage distances 3.75 kVeff / 5.3 kVdc 4 kVeff >5 mm 3.75 kVeff / 5.3 kVdc 4 kVeff >4 mm 3.75 kVeff / 5.3 kVdc 4 kVeff >5 mm Operating temperature Storage temperature -25 C...+50 C -40 C...+60 C -25 C...+50 C -40 C...+60 C -25 C...+50 C -40 C...+60 C Conductor Conductor cross-section Overall width AWG 22...12 0.5...4 mm2 6 mm AWG 22...12 0.5...4 mm2 6 mm AWG 22...12 0.5...4 mm2 6 mm Accessories End plate Type AP DKT4 120 Cat. No. 0687560000 Type AP DKT4 Cat. No. 0687560000 Type AP DKT4 Cat. No. 0687560000 Opto-coupler in component housing mini coupler DK DKO switching amplifiers/opto-couplers for Namur initiators Application example: Signals for consumers are normally transferred via an interface. Generally, this interface must conform with DIN 43867 (interface for signal transmission). There must be a differentiation between the passive interface and active S0 interface. The actual signals, that are correspondingly proportional to the relevant consumption (electrical energy, gas consumption, water, district heating, etc.) are shown at measuring sensors (electric meter, etc.) The interface itself is purely passive (acceptor) and must be supplied via a source. The source for providing the current is built into the active interface. The following threshold values are specified: Imax = 27 mAdc Umax = 27 Vdc fmax = 16.66 Hz For the recognition of the corresponding consumption signals, the following currents are integrated: ON (active) -> 10...27 mA Off (inactive) -> 0...2 mA The module accepts the input from the signal sensor and outputs the opto-decoupled output signal, i. e. galvanically isolated. Ordering data For TS 32 For TS 35 With combination foot TS 32 / TS 35 Technical data Input Input voltage Input current Pulse generator Y W DKO DK4 S0 W Schematic circuit diagram Type DKO DK4 S0 DKO DK4 S0 Cat. No. 8467030000 8100180000 24 Vdc 10 % 13 mA Specification acc. to DIN 43864 (current interface for connection to pulse generator acc. to DIN 43864) Output Output voltage Output current 5...48 Vdc max. 100 mA Voltage proof input-output/mounting rail 4 kVeff Insulation coordination to DIN VDE 0160, Draft 11/94 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances 300 V 6 kV IV 2 5.5 mm Storage temperature Conductor Conductor cross-section Overall width -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 12 mm Accessories End plate Type AP DKT4 Operating temperature without clearances with clearances DKO Schematic circuit diagram Ordering data For TS 32 For TS 35 With combination foot TS 32 / TS 35 Technical data Input Input voltage Input current Reverse polarity protection DKO Cat. No. 8164250000 24 Vdc 20 % 35 mA up to 1 kV available NAMUR-Input (N+ and N-) Switching frequency Switch-on delay Switch-off delay 300 Hz f. pulse duty factor 1:1 approx.45 s approx.450 s Input (E+ and 0) Switch-on point Switch off-point Current consumption Max. switching frequency Switch-on delay Switch-off delay approx.18 V ca 15 V < 5 mA 300 Hz f. pulse duty factor 1:1 approx.20s approx.400 s Output (A+ and A-) Output voltage Output current Switching capacity Internal voltage drop Protective measure 5...30 Vdc max. 100 mA max. 3 W max. 1 V Free-wheel. diode btwn. A+...A- Voltage proof input-output/mounting rail Operating temperature Cat. No. 0687560000 Type Y W Storage temperature Conductor Conductor cross-section Overall width Accessories End plate without clearances with clearances 4 kVeff -25 C...+40 C -25 C...+50 C -40 C...+60 C AWG 22...12 0.5...4 mm2 12 mm Type Cat. No. AP DKT4 0687560000 121 Digital signal processing Opto-couplers DKO S0 signal sensor Opto-coupler in component housing EG Opto-couplers EGO EGO 1 EGO 1 5V EGO 1 5V EGO 1 12 V 24 V For low voltage alternatively positive or negative switching Schematic circuit diagram Switching ratio t1 = t2 1=1:2 Switching ratiott1 = 2 3 * Wiring option Ordering data Type EGO 1, 5 V Rated data Input voltage Rated consumption - (W) Rated consumption ~ (VA) Cat. No. 0266160000 Type EGO 1, 12 V Cat. No. 8011250000 3) Type EGO 1, 12 V Cat. No. 0114260000 Type EGO 1, 24 V 3...5 V-2) 9...45 mW - 3...12 V- 30...280 mW - 12 V0, 10 % 0.35 W 0.45 VA 24 V-, 10 % 0.6 W - 5...48 V-1) <1 V 20 mA 5...48 V-1) <1 V 20 mA 5...48 V-1) <1.6 V 100 mA 5...48 V-1) <1 V 20 mA Impulse loading, max. current (not periodic) 0.2 A/10 ms 0.2 A/10 ms 0.8 A/10 ms 0.2 A/10 ms Max. reverse current (quiescent current) at U = 48 V Switch-on time (cyclic operation) Switching-off time (cyclic operation) Max. switching frequency, DC Max. switching frequency, AC Switching ratio Min. input impulse width Storage temperature Ambient temperature -, rowed on mounting rail without clearances -, rowed with clearances 20 mm Insulation coordination to EN 50 178 Overvoltage category Pollution severity 0.16 mA 12 s 180 s 100 Hz 0.16 mA 22 s 44 s 5000 Hz/5000 Hz 0.16 mA 30 s 100 s 3000 Hz 1:2 -40 C...+60 C 1 : 2/1 : 4 50 s -40 C...+85 C 0.16 mA 6 ms 13 ms 20 Hz <10 Hz 1:2 -40 C...+85 C -40 C...+85 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C III 2 III 2 III 2 III 2 Accessories, dimensions and connection data see Page 306, Fig. I Page 306, Fig. I Page 306, Fig. I Page 306, Fig. I Output supply voltage Voltage drop at max. load current Output current Derating curve a = mounted on rail without clearance b = mounted on rail without clearance 20 mm Continuous current Ambient temperature 1) 2) 122 3) At Ue 5 V, the LED only lights weakly or not at all. Not TTL-compatible Conditionally level-compatible Output switching function is not affected. 1:2 Cat. No. 0558160000 Opto-coupler in component housing EG EGO 1 EGO 2 24 V 115 V0 EGO 2 230 V0 for low voltage * Wiring option Cat. No. 0609860000 Type Cat. No. EGO 2, 115 V0 0131860000 Type Cat. No. EGO 2, 230 V0 0546360000 24 V0, 10 % 0.5 W 0.6 VA 117 V0, 10 % 0.8 W 0.9 VA 230 V0, +5 %-15 % 1.2 W 1.4 VA 5...48 V-1) <1.6 V 100 mA 5...48 V- <1.6 V 100 mA 5...48 V- <1.6 V 100 mA 0.8 A/10 ms 0.8 A/10 ms 0.8 A/10 ms 0.16 mA 2 ms 15 ms 20 Hz <10 Hz 1:2 0.16 mA 5 ms 22 ms 20 Hz < 10 Hz 1:2 0.16 mA 13 ms 10 ms 20 Hz < 10 Hz 1:2 -40 C...+85 C -40 C...+85 C -40 C...+85 C -25 C...+60 C -25 C...+60 C -25 C...+40 C -25 C...+50 C -25 C...+40 C -25 C...+50 C III 2 III 2 III 2 Page 306, Fig. I Page 306, Fig. I Page 306, Fig. I Digital signal processing Type EGO 1, 24 V In the case of inductive or capacitive electrical noise, it is recommended to connect an RC network (DK 4 RC) upstream or to use EGO 3. 123 Opto-coupler in component housing WAVESERIES Opto-couplers WAVESERIES WOS 1 5 VDC WOS 1 3.5-15 VDC WOS 1 12 VUC WOS 1 15-60 VDC negative switching Opto-coupler in WAVEBOX: Independent connection technology - pluggable connection unit optionally available with screw or tension clamp connection technology Fast commissioning and after-sales service - pluggable replacement PCBs Save wiring - cross-connection option at input / output Fast switching - high frequency output, up to 100 kHz Reliable power output - short-circuit and overload proof Space-saving components - 4-channel opto-couplers Schematic circuit diagram Ordering data Screw connection Tension clamp connection Input Input voltage Input current Making threshold Breaking threshold Input frequency Switch-on delay Switch-off delay Status indicator Output Output current range Nominal output current Output voltage Response threshold Residual voltage Protection circuit Voltage supply Short-circuit in output Temperature Operating temperature** Storage temperature Mechanical data Overall width Housing material Approvals Reliable separation according to EN 50 178 Coordination of insulation according to EN 50 178 Opto-coupler according to VDE 0884 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance/creepage path Accessories, dimensions and connection data see * at ambient temperature 20 C/horizontal installation 124 Type WOS 1 5 Vdc WOZ 1 Cat. No. 8275430000 8430030000 4.0 Vdc...5 Vdc...6.0 Vdc 7.5 mA at 4.0 V 13.5 mA at 5.0 V 19.0 mA at 6.0 V approx.2.2 V approx.2.0 V 100 Hz 100 us 1 ms LED green in input Type Cat. No. WOS 1 3.5-15 Vdc 8275390000 WOZ 1 8430040000 3.5 Vdc...15 Vdc 10.5 mA at 3.5.0 V 12.5 mA at 5.0 V 25.0 mA at 15 V approx.2.5 V approx.1.5 V 5 kHz 8 us 35 us LED green in input negative switching Type WOS 1 12 Vuc WOZ 1 Cat. No. 8275500000 8429990000 10 Vdc...12 Vdc...14 Vdc 15.3 mA ac at 12 V 12.4 mA dc at 12 V Type Cat. No. WOS 1 15-60 Vdc 8237730000 WOZ 1 8430090000 10 ms ac and 4 ms dc 20 ms ac and 18 ms dc LED green in output 15 Vdc...60 Vdc1) 1.4 mA at 15 V 2.5 mA at 24 V 4.1 mA at 48 V ...60 V ca.12 V approx.9 V 1 kHz 90 us 250 us LED green in output short-circuit protection 10 m A...0.6 A max. 500 mA 12 Vdc...24 Vdc...28 Vdc typ. 0.7 A ... 1.8 A min.0.7 A; max. 2.4 A 0.5 V at 500 mA Polarity protection, varistor 12 Vdc...24 Vdc...28 Vdc yes / max. 96 h approx.8 V approx.7 V max. 2 A* 18 Vdc...24 Vdc...30 Vdc max. 100 mA 5 Vdc...48 Vdc 300 mV Varistor 1.5 V at 100 mA Varistor, integr. free-wh. diode no no short-circuit protection 10 mA...0.6 A max. 500 mA 12 Vdc...24 Vdc...28 Vdc typ. 0.7 A ... 1.8 A min. 0.7 A; max. 2.4 A 0.5 V, at 500 mA Polarity protection, varistor 12Vdc...24Vdc...28Vdc yes / max. 96 h -25 C...+50 C rowed -40 C...+85 C -25 C...+60 C rowed -40 C...+85 C -25 C...+60 C rowed -40 C...+85 C -25 C...+60 C rowed -40 C...+85 C 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm Page 298 + 308 Page 298 + 308 Page 298 + 308 Page 298 + 308 1) Caution: Cross-connections may only be used for voltages 50 Vdc (extra-low voltage). Opto-coupler in component housing WAVESERIES Opto-couplers WAVESERIES WOS 1 115 VUC WOS 1 230 VUC Schematic circuit diagram WOS 1 230 VUC Mounted horizontally Ansteuerung : 253Vac Control 253 Vdc waagerecht montiert; Output current [A] 0,6 0,5 0,4 mounted clearance 10 mm Abstand>=10mm 0,3 0,2 0,1 0 0 20 40 60 80 100 Umgebungstemperatur Ambient temperature [C] [C] Type Cat. No. WOS 1 115 Vuc 8235180000 WOZ 1 8430100000 Type Cat. No. WOS 1 230 Vuc 8275380000 WOZ 1 8430050000 115 Vuc, max. 130 Vuc 3.1 mA ac at 115 V 2.9 mA dc at 115 V 230 V, max. 250 Vuc 11.5 mA ac at 230 V 1.8 mA dc at 230 V Making threshold Breaking threshold Input frequency Switch-on delay Switch-off delay Status indicator ca.75 V ac and 71 dc ca.70 Vuc 10 ms ac 10 ms dc 15 ms ac 15 ms dc LED green in output ca.170 V ac and 140 V dc ca.130 V ac and 135 V dc 25 ms ac 15 ms dc 25 ms ac 20 ms dc LED green in output Output Output current range Nominal output current Output voltage Response threshold Residual voltage Protection circuit Voltage supply Short-circuit in output short-circuit protection 10 m A...0.6 A max. 500 mA 12 Vdc...24 Vdc...28 Vdc typ. 0.7 A ... 1.8 A min.0.7 A; max. 2.4 A 0.5 V at 500 mA Polarity protection, varistor 12 Vdc...24 Vdc...28 Vdc yes / max. 96 h short-circuit protection 10 mA...0.6 A max. 500 mA 12 Vdc...24 Vdc...28 Vdc typ. 0.7 A ... 1.8 A min.0.7 A; max. 2.4 A 0.5 V at 500 mA Polarity protection, varistor 12 Vdc...24 Vdc...28 Vdc yes / max. 96 h Temperature Operating temperature** Storage temperature -25 C...+60 C rowed -40 C...+85 C -25 C...+60 C rowed -40 C...+85 C 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm Page 298 + 308 Page 298 + 308 Ordering data Screw connection Tension clamp connection Input Input voltage Input current Mechanical data Overall width Housing material Approvals Reliable separation according to EN 50 178 Coordination of insulation according to EN 50 178 Opto-coupler according to VDE 0884 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance/creepage path Accessories, dimensions and connection data see Digital signal processing WOS 1 230 VUC * 8275380000 * at ambient temperature 20 C/horizontal installation 125 Opto-coupler in component housing WAVESERIES Opto-couplers WAVESERIES WOS 2 24 VUC WOS 2 115 VUC WOS 2 230 VUC Type WOS 2 115 Vuc WOZ 2 Type WOS 2 230 Vuc WOZ 2 with power output (short-circuit proof and overload proof) Schematic circuit diagram WOS 2 horizontally 230 VUC Mounted Ansteuerung : 253Vac Control 253 Vdc waagerecht montiert; 6 clearance 10 mm Output current [A] 5 Abstand>=10mm mounted 4 3 2 1 0 0 10 20 30 40 50 60 70 Umgebungstemperatur Ambient temperature [C] [C] WOS 2 230 VUC * 8275220000 Ordering data Screw connection Tension clamp connection Input Input voltage Input current Making threshold Breaking threshold Switch-on delay Switch-off delay Status indicator normal operation Status indicator short-circuit, underload, overload Underload Output Output current Closed supply-circuit current (output not switched) Voltage supply Residual voltage Protection circuit Short-circuit in output Temperature Operating temperature** Storage temperature Mechanical data Overall width Housing material Approvals Reliable separation according to EN 50 178 Coordination of insulation according to EN 50 178 Opto-coupler according to VDE 0884 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance/creepage path Accessories, dimensions and connection data see * at ambient temperature 20 C/horizontal installation 126 Type WOS 2 24 Vuc WOZ 2 Cat. No. 8275190000 8430080000 Cat. No. 8296250000 8429980000 Cat. No. 8275220000 8430060000 21.6 V...24 V...26.4 V 16.3 mA ac at 24 V 13.5 mA dc at 24 V 115 V, max. 130 Vuc 3.1 mA ac at 115 V 2.8 mA dc at 115 V 230 V, max. 250 Vuc 12.0 mA ac at 230 V 1.8 mA dc at 230 V ca.16 V ca.11 V 8 ms ac 7 ms dc 25 ms ac 25 ms dc LED green in output LED red in output*1) min. 2 mA...max. 1.5 A at Tb 25 C...150 C min. 2 mA...max. 1.9 A at Tb -40 C...25 C Tb: temperature in module direct at output driver BTS442 short-circuit protection 5 Adc* approx.15 mA at 28.8 V 19.2 Vdc...24 Vdc...28.8 Vdc max. 400 mV Polarity protection, varistor yes / max. 96 h ca.70 V ca.55 V 10 ms ac 15 ms dc 30 ms ac 30 ms dc LED green in output LED red in output*1) min. 2 mA...max. 1.5 A at Tb 25 C...150 C min. 2 mA...max. 1.9 A at Tb -40 C...25 C Tb: temperature in module direct at output driver BTS442 short-circuit protection 5 Adc* approx.15 mA at 28.8 V 19.2 Vdc...24 Vdc...28.8 Vdc max. 400 mV Polarity protection, varistor yes / max. 96 h ca.140 V ca.100 V ca.100 V ca.120 V 10 ms ac 15 ms dc 30 ms ac 30 ms dc LED green in output LED red in output*1) min. 2 mA...max. 1.5 A at Tb 25 C...150 C min. 2 mA...max. 1.9 A at Tb -40 C...25 C Tb: temperature in module direct at output driver BTS442 short-circuit protection 5 Adc* approx.15 mA at 28.8 V 19.2 Vdc...24 Vdc...28.8 Vdc max. 400 mV Polarity protection, varistor yes / max. 96 h -25 C...+50 C rowed -40 C...+85 C -25 C...+50 C rowed -40 C...+85 C -25 C...+50 C rowed -40 C...+85 C 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm Page 298 + 308 Page 298 + 308 Page 298 + 308 *1) LED red: hard short-circuit, LED permanently lit. The output is switched off and does not reset itself. To reset, the output or input must be temporarily disconnected from the supply voltage or input signal. Overload: LED cycles, Rate: approx. 2 sec. on, approx. 30 sec. off. Module resets itself after the overload is removed. Underload: LED permanently lit. When an underload recognised, both LEDs are lit. The output is switched through Opto-coupler in component housing WAVESERIES Opto-coupler WAVESERIES WOS 2 15-60 VUC WOS 2 115 VUC WOS 2 230 VUC with AC voltage output and zero voltage switch Schematic circuit diagram WOS 2 15-60 VUC Mounted horizontally Ansteuerung : Control 253 Vdc waagerecht montiert; 60Vac Output current [A] 3,5 3 clearance 10 mm Abstand>=10mm 2,5 Mounted 2 Zero V. switch 1,5 Zero V. switch Zero V. switch 1 0,5 0 0 20 40 60 80 100 120 Ambient temperature [C] Umgebungstemperatur [C] WOS 2 15-60 VUC * 8275440000 Type Cat. No. WOS 2 15-60 Vuc 8275440000 WOZ 2 8430010000 Type WOS 2 115 Vuc WOZ 2 15 Vuc...60 Vac/66 Vdc 3.3 mA ac at 15 V 3.8 mA dc at 15 V 4.0 mA ac at 24 V 4.6 mA dc at 24 V 5.3 mA ac at 60 V 5.6 mA dc at 60 V approx.11 V dc approx.15 V ac approx.5 V dc approx.14 V ac max. 20 ms max. 20 ms LED green in input 115 Vuc max. 130 Vuc 7.2 mA ac at 115 V 3.8 mA dc at 115 V 230 Vuc max. 250 Vuc 11.8 mA ac at 230 V 3.3 mA dc at 230 V approx.90 V dc approx.90 V ac approx.70 V dc approx.70 V ac max. 20 ms max. 20 ms LED green in input approx.180 V dc approx.200 V ac approx.150 V dc approx.140 V ac max. 25 ms max. 25 ms LED green in input Output Output current Closed supply-circuit current (output not switched) Voltage supply Residual voltage Protection circuit Short-circuit in output Temperature Operating temperature** Storage temperature Mechanical data Overall width Housing material Approvals Reliable separation according to EN 50 178 Coordination of insulation according to EN 50 178 Opto-coupler according to VDE 0884 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance/creepage path AC voltage output max. 230 V/3.5 A ac* 2 mA 24 Vac...250Vac (50Hz-60Hz) max. 1.6 V RC-combination with varistor - AC voltage output max. 230 V/3.5 A ac* 2 mA 24Vac...250 Vac (50Hz-60Hz) max. 1.6 V RC-combination with varistor - AC voltage output max. 230V/3.5A ac* 2 mA 24 Vac..250 Vac (50Hz-60Hz) max. 1.6 V RC-combination with varistor - -25 C...+50 C rowed -40 C...+85 C -25 C...+50 C rowed -40 C...+85 C -25 C...+50 C rowed -40 C...+85 C 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm Accessories, dimensions and connection data see * at ambient temperature 20 C/horizontal installation Page 298 + 308 Page 298 + 308 Page 298 + 308 Input Input voltage Input current Making threshold Breaking threshold Switch-on delay Switch-off delay Status indicator normal operation Cat. No. 8259950000 8430160000 Type Cat. No. WOS 2 230 VUC 8275400000 WOZ 2 8430150000 Digital signal processing Ordering data Screw connection Tension clamp connection 127 Opto-coupler in component housing WAVESERIES Opto-coupler WAVESERIES WOS 2 24 VUC WOS 2 115 VUC WOS 2 230 VUC Type WOS 2 115 Vuc WOZ 2 Type WOS 2 230 Vuc WOZ 2 (4-channel, short-circuit proof) Schematic circuit diagram Mounted horizontally, WOS output current / channel: 500 mA 2 230 VUC waagerecht montiert Control 250 Ansteuerung Vdc Ausgangsstrom/Kanal: 500mA; : 250Vac Output current [A] 0,6 0,5 clearance 10 mm Abstand>=10mm 0,4 0,3 Mounted 0,2 0,1 0 0 10 20 30 40 50 60 Ambient temperature [C] Umgebungstemperatur [C] WOS 2 230 VUC * 8275340000 Ordering data Screw connection Tension clamp connection Input Input voltage Input current Type WOS 2 24 Vuc WOZ 2 Cat. No. 8237720000 8430110000 Cat. No. 8275360000 8430130000 Cat. No. 8275340000 8430140000 18 Vuc ... 30 Vuc 2.8 mA ac at 24 V 3.7 mA dc at 24 V 115 Vuc, max. 130 Vuc 1.4 mA ac at 115 V 2.0 mA dc at 115 V 230 V, max. 250 V 1.4 mA ac at 230 V 2.0 mA dc at 230 V Making threshold Breaking threshold Switch-on delay Switch-off delay Status indicator normal operation Status indicator short-circuit, underload, overload ca.13 V dc ca.14 V ac ca.10 V dc ca.13 V ac 20 ms ac 7.0 ms dc 46 ms ac 50 ms dc LED green in output LED red in output* ca.60 V dc ca.60 V ac ca.50 V dc ca.50 V ac 40 ms ac 15 ms dc 60 ms ac 70 ms dc LED green in output LED red in output* ca.150 V dc ca.120 V ac ca.110 V dc ca.110 V ac 40 ms ac 14 ms dc 95 ms ac 140 ms dc LED green in output LED red in output* * LED red, one LED for all channels Output1) Output current short-circuit protection max. 500 mA per channel short-circuit protection max. 500 mA per channel short-circuit protection max. 500 mA per channel Output total current Voltage supply Response threshold max. 2 A 12 Vdc...24 Vdc...28 Vdc typ. 0.9 A min. 0.65 A, max. 1.2 A, RL2 0.65 V, at 500 mA Polarity protection, varistor 100 % max. 3 W max. 2 A 12 Vdc...24 Vdc...28 Vdc typ. 0.9 A min. 0.65 A, max. 1.2 A, RL2 0.65 V, at 500 mA Polarity protection, varistor 100 % max. 3 W max. 2 A 12 Vdc...24 Vdc...28 Vdc typ. 0.9 A min. 0.65 A, max. 1.2 A, RL2 0.65 V, at 500 mA Polarity protection, varistor 100 % max. 3 W -25 C...+50 C rowed -40 C...+85 C -25 C...+50 C rowed -40 C...+85 C -25 C...+50 C rowed -40 C...+85 C 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 150 V 2.5 kV III 2 3 mm 150 V 2.5 kV III 2 3 mm 300 V 4 kV III 2 5.5 mm Page 298 + 308 Page 298 + 308 Page 298 + 308 Residual voltage Protection circuit Synchronisation factor Lamp load Temperature Operating temperature Storage temperature Mechanical data Overall width Housing material Approvals Reliable separation according to EN 50 178 Coordination of insulation according to EN 50 178 Opto-coupler according to VDE 0884 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance/creepage path Accessories, dimensions and connection data see 1) Protection circuit for output load necessary, page 107 128 Opto-coupler in component housing WAVESERIES Opto-coupler WAVESERIES WOS 1 5 VTTL 50 kHz with high switching frequency WOS 1 12-28 VDC 100 kHz Schematic circuit diagram WOS 1 5Vhorizontally TTL 50 kHZ Mounted waagerecht montiert Control: 5.25 V; cross-connection current: 4 A mounted Ansteuerung : 5,25V; QV-Strom: 4A eng angereihte Montage in rows Output current [A] 0,06 Abstand>=10mm clearance 10 mm 0,05 Mounted 0,04 0,03 0,02 0,01 0 0 20 40 60 80 100 Umgebungstemperatur [C] Ambient temperature [C] Ordering data Screw connection Tension clamp connection Input Input voltage Input current Supply voltage Input resistance Making threshold Breaking threshold Input frequency Switch-on delay Switch-off delay Status indicator normal operation Type Cat. No. WOS 1 5 VTTL 50 kHz 8275210000 WOZ 2 8430070000 Type Cat. No. WOS 1 12-28 Vdc/100 kHz 8275450000 WOZ 2 8430000000 5 VTTL 11.8 mA at 4.75 V 13.6 mA at 5 Vdc 15.5 mA at 5.25 Vdc 12V dc...28 Vdc 5.5 mA at 12 Vdc 7.9 mA at 24 Vdc 8.8 mA at 28 Vdc Digital signal processing WOS 1 5 VTTL 50 kHz * 8275210000 4.75 Vdc ... 5.25 Vdc 110 K 50 kHz at Rload = 470 1 s 7 s LED green in input circuit approx.5 V dc approx.4 V dc 100 kHz at Rload = 470 1 s 3 s LED green in input circuit 21.6 Vdc...24 Vdc...26.4 Vdc approx.5.4 mA, output not switched 50 mA 1.5 V at 50 mA Polarity protection, varistor 21.6 Vdc...24 Vdc...26.4 Vdc approx.5.4 mA, output not switched 50 mA 1.5 V at 50 mA Polarity protection, varistor -25 C...+60 C rowed -40 C...+85 C -25 C...+60 C rowed -40 C...+85 C 22.5 mm Polyamide PA 66 UL/CSA 22.5 mm Polyamide PA 66 UL/CSA 300 V 4 kV III 2 5.5 mm 300 V 4 kV III 2 5.5 mm Page 298 + 308 Page 298 + 308 Output Voltage supply Supply nominal current Output current Residual voltage Protection circuit Temperature Operating temperature Storage temperature Mechanical data Overall width Housing material Approvals Reliable separation according to EN 50 178 Coordination of insulation according to EN 50 178 Opto-coupler according to VDE 0884 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance/creepage path Accessories, dimensions and connection data see 129 Opto-coupler in component housing EG5 power opto-couplers EGO 5 PKR 24 Vac/dc With "online" check-back indication of the load ratio * Power opto-couplers for load currents up to 4 A. * Short-circuit proof * Patented "online" load indication and check-back indication - optical indication status indication via 3-coloured LEDs - electrical indication 2-bit "online" data signal for check-back indication of the load performance to a PLC or similar * Module fulfils protective separation in accordance with VDE 0106 Part 101 and EN 50 178 (rated voltage 300 V) * Internal opto-coupler according to with DIN VDE 0884 * Insulation voltage 4 kVeff * Clearance and creepage distances 8 mm Schematic circuit diagram Indication and check-back indication of load ratio Input Low High High High Load Indication xxx Normal Error1) Open Load2) LI 1 L L H H LI 2 L H L H LED off green red yellow Output low high low high Ordering data Rated data Input Input voltage Input current (at UN) Rated input consumption Max. input frequency dc Typ. switch-on delay Typ. switch-off delay Max. input frequency ac Output Supply voltage Max. output current Reverse polarity protection Short-circuit conditions Thermal short-circuit Load Indication LI 1, LI 2 Supply voltage Max. current Max. voltage drop Storage temperature Ambient temperature - rowed on mounting rail without clearances - rowed with clearances Insulation coordination EN 50 178 Overvoltage category Pollution severity Type EGO 5 PKR Cat. No. 8220870000 Screw connection 0.5...4 mm2 24 Vac/dc, min 20 Vac/dc, max 30 Vac/dc 12 mA (24 Vdc) 13 mA (24 Vac) 195 mW, 220 mVA 30 Hz, switching ratio 1 : 2 2 ms 7 ms 10 Hz Screw connection 0.5...4 mm2 20...30 Vdc 4A present short-circuit-protected (switches output off immediately; auto switch-on when short-circuit eliminated) 12 A. output switches off and on again automatically after certain time. 5...48 Vdc 100 mA 1.6 V -40 C...+60 C -20 C...+40 C -20 C...+50 C IV 2 Accessories, dimensions and connection data see Page 307, Fig. VII 1) 2) Error: short-circuit, overload, over- or under voltage at output, overtemperature in the module 130 Open load: Underload recognition at active input: type 500 mA (max. 1.5 A) at 25 C. Open load wil be indicated at ILoad 500 mA depending on switching status. Opto-coupler in component housing EG7 power opto-couplers OST EG7 2A - Pluggable on socket RS EG 7 with combination foot TS 32, 35 - Overall width 10 mm * Short circuit protected and over load-safe output * 3-colour status-LED for output current indication * Reliable separation acc. to DIN VDE 0884 OST EG7 4A OST EG 7 OST EG 7 RS EG 7 RS EG 7 Schematic circuit diagram Ordering data Puggable opto-coupler, without socket Type OST EG7 2 A Cat. No. 8269050000 Type OST EG7 4 A Cat. No. 8281720000 socket for pluggable opto-coupler with combin. foot TS 32, 35 RS EG7 8193830000 RS EG7 8193830000 Cat. No. Lugs for socket RS EG7 24 Vac/dc 20 % dc: 5.5 mA ac: 6 mA dc: 132 mW ac: 145 mW 19.2 V 2.4 V LED green, yellow, red 12 ms 17 ms 100 Hz (resistive load/2 A/ Switching ratio 1 : 2) Input voltage Input current Input power Relaibly switched on Reliably switched off Status indicator Reverse polarity protection Switch-on delay Switch-off delay Max. Switching frequency Output supply voltage Switching current Voltage drop at max. load current Status indicator: Green LED Yellow LED Red LED LED off Storage temperature Operating temperature - rowed on mounting rail without clearances - rowed with clearances Insulation coordination to EN 50 178 Reliable separation Overvoltage category Pollution severity Accessories, dimensions and connection data see 8193830000 Cat. No. Lugs for socket RS EG7 21.6 Vdc 10.5 mA 230 mW 21.6 V 2V LED green present typ. 10 s typ. 45 s 100 Hz (resistive load/4 A/ 24 Vdc 11.2 mA 270 mW 8193830000 26.4 Vdc 12.0 mA 320 mW Switching ratio 1 : 2) 24 Vdc 30 % 2A 0.2 V, short-circuit proof and overload proof 21.6...26.4 Vdc 4A 0.2 V, not short-circuit proof and not overload proof output set normal function, 500 mA...2 A output set, no activity, < 500 mA output set, short-circuit output not set - 25...+ 60 C output set normal function 0...+ 40 C 0...+ 50 C 0...+ 40 C 0...+ 50 C according to DIN VDE 0884 III 2 III 2 Page 304 Page 304 - 25...+ 60 C 131 Digital signal processing Rated data Conductor connection Opto-coupler in component housing EG7 Opto-couplers - With combination foot for TS 15, TS 32 or TS 35 - Pluggable on socket RS EG 7 with combination foot TS 32, 35 - Overall width 10 mm - Reliable separation according to DIN VDE 0884 EGO EG 7 OST EG 7 RS EG 7 OST EG 7 RS EG 7 EGO EG 7 5 V- 12 V0 24 V0 48 V0 Schematic circuit diagram Ordering data Combination foot for TS 15, TS 32, TS 35 Type EGO EG7 Cat. No. 8092490000 Type EGO EG7 Cat. No. 8092510000 Type EGO EG7 Best.-EGO 8092530000 Type EGO EG7 Cat. No. 8092550000 Plug-in opto-coupler, without engagement socket Engage. socket for opto-coupler with combin. foot TS 32, 35 Rated data Input voltage Switch-on current Making threshold,typical OST EG7 RS EG7 8234560000 8193830000 OST EG7 RS EG7 8234570000 8193830000 OST EG7 RS EG7 8234580000 8193830000 OST EG7 RS EG7 8234590000 8193830000 5 V- 20 % 5...48 V- 100 mA 300 mA 12 V0 20 % 12 V/4.5 mA for max. 10 ms 6.5 V- 7.5 V~ 3 mA 33.5 mA 40 mW/50 mVA 5...48 V- 100 mA 300 mA 24 V0 20 % 12 V/4.5 mA for max. 10 ms 15.5 V- 16.5 V~ 2.8 mA 3.4 mA 70 mW/90 mVA 5...48 V- 100 mA 300 mA 48 V0 20 % 12 V/4.5 mA for max. 10 ms 31.5 V- 45 V~ 2.8 mA 3.2 mA 135 mW/155 mVA 5...48 V- 100 mA 300 mA Switch-on time (first time) Switch-off time Switching frequency 6 ms for UN = 5 V- 12 ms for UN = 5 V- 15 Hzdc 6 ms for UN = 12 V- 12 ms for UN = 12 V- 15 Hzdc 5 ms for UN = 24 V- 15 ms for UN = 24 V- 15 Hzdc 5 ms for UN = 48 V- 15 ms for UN = 48 V- 15 Hzdc Storage temperature Ambient temperature Connection -40...+60 C -25...+60 C -40...+60 C -25...+60 C -40...+60 C -25...+60 C -40...+60 C -25...+60 C Insulation coordination to EN 50 178 Protective separation Clearances and creepage distances Rated impulse voltage Overvoltage category Pollution severity Accessories Cross connection comb 16-pole acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 Further accesories, dimensions and connection data see Page 304 Page 304 Page 304 Page 304 Rated input current DC Rated input current AC Rated input consumption Output supply voltage Output current Max. output current 132 3 V- - 6.8 mA - Opto-coupler in component housing EG7 EGO EG 7 Opto-couplers for long control cables EGO EG 7 RC/ OST EG 7 RC - with combination foot for TS 15, TS 32 or TS 35 - plugs onto locking socket RS EG 7 with combination TS 32, 35 - overall width 10 mm - protective separation acc. to DIN VDE 0884 - RC-input for suppressing noise signals - reliable switching performance by interference on the control side EGO EG 7 115 V0 230 V9 230 Vdc OST EG 7 RC RS EG 7 RC 115 V0 230 V9 Schematic circuit diagram OST EG7 RS EG7 Cat. No. 8092570000 8234600000 8193830000 Type EGO EG7 OST EG7 RS EG7 Cat. No. 8092590000 8234610000 8193830000 115 V0 20 % 115 V/90 mA for 5 ms 70 V- 72 V~ 3.3 mA 5.5 mA 400 mW/500 mVA 5...48 V- 100 mA 300 mA 230 V~ 20 % 230 V/110 mA for 2 ms 140 V~ - 3.8 mA - 836 mVA 5...48 V- 100 mA 300 mA 5 ms for UN = 115 V- 18 ms for UN = 115 V- 15 Hzdc 5 ms for UN = 230 V- 18 ms for UN = 230 V- 12 Hz -40...+60 C -25...+60 C -40...+60 C -25...+60 C Type OST EG7 Cat. No. 8621190000 230 Vdc 20 % 230 V~ /110 mA for 2 ms 140 V~ (for testing only) - 1.8 mA - 100 mA 300 mA -40...+60 C -25...+60 C Screw connection 0.5...1.5mm2, AWG 22...16 acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 Page 304 Page 304 Page 304 Ordering data Combination foot for TS 15, TS 32, TS 35 Pluggable opto-coupler, without locking socket Locking socket for pluggable opto-coupler with combin. foot TS 32, 35 Rated data Input voltage Switch-on current Making threshold,typ, Type Cat. No. Type Cat. No. EGO EG7 8397420000 EGO EG7 8387580000 OST EG7 8315590000 OST EG7 8394990000 RS EG7 8193830000 RS EG7 8193830000 115 V0 20 % 115 V/90 mA for 5 ms 70 V- 72 V~ 3.3 mA 9 mA/90 mA (5 ms) 400 mW/500 mVA 5...48 V- 100 mA 300 mA 230 V~ 20 % 230 V/110 mA for 2 ms 140 V~ - 14 mA/110 mA (2 ms) - 836 mVA 5...48 V- 100 mA 300 mA 9 ms for UN = 115 V- 15 ms for UN = 230 V- 25 ms for UN = 115 V- 12 Hzdc 15 ms for UN = 230 V- 12 Hz Storage temperature Ambient temperature Insulation coordination to Reliable separation Clearances / creepage distances Rated impulse voltage Overvoltage category Pollution severity Accessories Cross connec. comb 16-pole -40...+60 C -25...+60 C EN 50 178 acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 -40...+60 C -25...+60 C Futher Accessories, dimensions and connection data see Page 304 Page 304 Rated input current DC Rated input current AC Rated input consumption Output supply voltage Output current Max. output current Switch-on time (first time) Switch-off time Switching frequency acc. to DIN VDE 0884 5.5 mm 6 kV III 2 Type Cat. No. QB 16/10.16 1650330000 133 Digital signal processing Type EGO EG7 Solid State relay on locking socket PLUGSERIES DC version Complete module Accessories SSR Standard AC version Type/Version Screw connection POS 24Vdc/24Vdc 2.5A POS 24Vdc/230Vac 2A POS 24Vdc/24Vuc 1A POS 24Vdc/24Vdc 5A POS 24Vdc/230Vac 4A Cat. No. 8610840000 8610860000 8610890000 8610900000 8610910000 Tension clamp connection POZ 24Vdc/24Vdc 2.5A POZ 24Vdc/230Vac 2A POZ 24Vdc/24Vuc 1A POZ 24Vdc/24Vdc 5A POZ 24Vdc/230Vac 4A 8610920000 8610930000 8610960000 8610970000 8610980000 Type/Version Screw connection POS 24Vac/24Vdc 2.5A POS 24Vac/24Vdc 5A POS 24Vac/230Vac 4A Cat. No. 8615600000 8615620000 8615590000 Tension clamp connection POZ 24Vac/24Vdc 2.5A POZ 24Vac/24Vdc 5A POZ 24Vac/230Vac 4A 8615640000 8615650000 8615630000 Dimensions 12,7 5,1 25,4 29 Compact dimensions (29 x 25.4 x 12.7) Ordering data Combines with PLUGSERIES socket PXS / PXZ, LED indicator PLED and PRC holding clamp to a complete functioning unit. Fully compatible with electromechanical relays in standard design Control voltage 24 VAC / DC Rated switching current 24 VDC, 24 VAC/DC, or 230 VAC Up to 5 A continuous current Mounts onto PCB or socket High mounting density possible DC version Cat. No. SSR 24 VUC/24VDC 5A 8576350000 Technical data Input (typical values at 20 C) Input voltage min. AC/DC Input voltage max. AC/DC Input current min. AC/DC Input current max. AC/DC Drop-out voltage AC/DC Resistance Output max. switching current DC max. switching current AC DC Version 15 V 30 V 6.1 mA 12 mA 2.5 V 2.100 Type Cat. No. SSR 24 VUC/230VAC 4A 8576360000 AC Version 15 V 30 V 6.1 mA 12 mA 2.5 V 2.100 5A 3 A (4 A at 20 C) min. switching current DC min. switching current AC 1 mA Rated switching voltage DC Rated switching voltage AC 24 V Switch voltage range DC Switch voltage range AC 0...30 V max. forward anode voltage at max. switching current DC max. forward anode voltage at max. switching current AC 0.3 V max. switch-on time DC max. switch-on time AC (50 Hz) 2 ms max. switch-off time DC max. switch-off time AC (50 Hz) 18 ms 50 mA 230 V ~ 12...275 V 21 A1 A2 14 1.1 V * load * Free-wheel diode for inductive loads AC version 12-275 VAC N L1 134 Type A1 21 A2 14 Load Insulation Test voltage control circuit - switching circuit DC Test voltage control circuit - switching circuit AC Further data Operating temperature range Weight Approvals Celduc Further accessories, dimensions and connection data 12 ms 20 ms 2.5 kVeff 4 kVeff -40 C...+50 C approx.18 g cUL, UL recognized SPD07505 see page 83 -40 C...+50 C approx.18 g cUL, UL recognized SPA07420 see page 83 Solid State relay on locking socket PLUGSERIES Accessories SSR / RT Dimensions 12,7 5,1 15,7 29 Ordering data Combines with PLUGSERIES socket PXS / PXZ, LED indicator PLED and PRC holding clamp to a complete functioning unit. Fully compatible with standard electromechanical relays RT Control voltage 24 VAC / DC Rated switching current 24 VDC, 24 VAC/DC, or 230 VAC Up to 5 A continuous current Mounts onto PCB or socket High mounting density possible AC version 12-275 VAC A1 21 A2 14 14 * * Free-wheel diode for inductive loads AC/DC version max. 30 VAC/DC L1 A1 15 V 30 V 6.1 mA 12 mA 2.5 V 2.100 15 V 30 V 6.1 mA 12 mA 2.5 V 2.100 2.5 A 2A 1A 1mA Rated switching voltage DC Rated switching voltage AC Rated switching voltage AC/DC 24 V Switch voltage range DC Switch voltage range AC Switch voltage range AC/DC 0...30 V 50mA 1mA 230 V 24 V 12...275 V 0...30 V N forward anode voltage at switching current DC forward anode voltage at switching current AC forward anode voltage at switching current AC/DC 0.5 V 1V 0.9 V max. switch-on time DC max. switch-on time AC (50 Hz) max. switch-on time AC/DC (50 Hz) 2 ms max. switch-off time DC max. switch-off time AC (50 Hz) max. switch-off time AC/DC (50 Hz) 18 ms Insulation Test voltage control circuit switching circuit DC Test voltage control circuit switching circuit AC Test voltage control circuit switching circuit AC/DC 12 ms 5 ms 20 ms 12 ms 2.5 kVeff 4 kVeff 4 kVeff 21 Load STN A2 15 V 30 V 6.1 mA 12 mA 2.5 V 2.100 min. switching current DC min. switching current AC min. switching current AC/DC max. max. max. max. max. max. 21 Load Type Cat. No. SSR 24 VUC/24VUC 1A 8576380000 AC/DC Version Load DC version A2 Output max. switching current DC max. switching current AC max. switching current AC/DC Type Cat. No. SSR 24 VUC/230VAC 2A 8576370000 AC Version N L1 A1 Technical data Input (typical values at 20 C) Input voltage min. AC/DC Input voltage max. AC/DC Input current min. AC/DC Input current max. AC/DC Drop-out voltage AC/DC Resistancs Type Cat. No. SSR 24 VUC/24VDC 2.5A 8576340000 DC Version Digital signal processing Compact dimensions (29 x 15.7 x 12.7) 14 Further data Operating temperature range Weight Approvals Celduc Further accessories, dimensions and connection data -40 C...+50 C approx.11 g cUL, UL recognized STD07205 -40 C...+50 C approx.11 g cUL, UL recognized STA07220 -40 C...+50 C approx.11 g cUL, UL recognized STN07105 see page 83 see page 83 see page 83 135 Opto-coupler on locking socket profile RS 40 Opto-couplers for signal input RS 40 Rated data Input voltage Rated consumption - (W) Rated consumption ~ (VA) 5 V-2) 0.045 W 12 V0 10 % 0.25 W 0.32 VA 24 V- 10 % 0.51 W 24 V0 10 % 0.34 W 0.5 VA 48 V0 10 % 0.55 W 0.65 VA 115 V0, +5%-15% 230 V~, +5%-15% 0.33 W 0.65 VA 0.52 VA Output supply voltage Voltage drop at max. load current Output current 5...48 V-1) < 0.9 V 20 mA 5...48 V-1) < 1.6 V 100 mA 5...48 V-1) < 0.9 V 20 mA 5...48 V-1) < 1.6 V 100 mA 5...48 V-1) < 1.6 V 100 mA 5...48 V-1) < 1.5 V 100 mA 5...48 V-1) < 1.5 V 100 mA Derating curve a = rowed on mounting rail without clearances b = rowed with clearances 20 mm 20 or 100 20 or 100 Continuous current Ambient temperature Pulse duration, limiting overload current (not periodic) 0.2 A/10 ms 0.8 A/10 ms 0.2 A/10 ms 0.8 A/10 ms 0.8 A/10 ms 0.8 A/10 ms 0.8 A/10 ms Sperrstrom (Ruhestrom), max. at U = 48 V Switch-on time (cyclic operation) Switch-off time (cyclic operation) Max. switching frequency DC voltage Max. switching frequency AC voltage Switching ratio 0.16 mA 12 s 15 s 3 kHz 0.16 mA 30 s 60 s 3 kHz 0.16 mA 2 ms 15 ms 20 Hz 0.16 mA 6 ms 18 ms 1:2 10 Hz 1 : 1 0.16 mA 5 ms 20 ms < 20 Hz < 10 Hz 10 Hz 1 : 1 0.16 mA 10 ms 23 ms 10 Hz 1:2 0.16 mA 6 ms 13 ms 20 Hz < 10 Hz 10 Hz 1 : 2 10 Hz 1 : 1 10 Hz 1 : 1 300 V 6 kV IV 2 5.5 mm according to DIN VDE 0884 according to DIN VDE 0884 non-destructive test 1 kV acc. to IEC 801-4 severity 4 300 V 6 kV IV 2 5.5 mm according to DIN VDE 0884 according to DIN VDE 0884 non-destructive test 1 kV acc. to IEC 801-4 severity 4 300 V 6 kV IV 2 5.5 mm according to DIN VDE 0884 according to DIN VDE 0884 non-destructive test 1 kV acc. to IEC 801-4 severity 4 300 V 6 kV III 2 5.5 mm according to DIN VDE 0884 according to DIN VDE 0884 non-destructive test 1 kV acc. to IEC 801-4 severity 4 300 V 6 kV IV 2 5.5 mm according to DIN VDE 0884 according to DIN VDE 0884 non-destructive test 1 kV acc. to IEC 801-4 severity 4 300 V 6 kV IV 2 5.5 mm according to DIN VDE 0884 according to DIN VDE 0884 non-destructive test 1 kV acc. to IEC 801-4 severity 4 300 V 6 kV IV 2 5.5 mm according to DIN VDE 0884 according to DIN VDE 0884 non-destructive test 1 kV acc. to IEC 801-4 severity 4 Insulation coordination to EN 50 178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearances and creepage distances Opto-coupler Test voltage (corresponds 100% module test) Module is immune to interference Insulation voltage Input - output/mounting rail Storage temperature Ambient temperature -, rowed on mounting rail without clearances -, rowed with clearances 20 mm 4 kV~eff 1 min. 4 kV~eff 1 min. -40 C...+85 C -40 C...+70 C -25 C...+60 C -25 C...+60 C -25 C...+40 C -25 C...+45 C 1) 2) 136 Not TTL-compatible Conditionally level-compatible Opto-coupler on locking socket profile RS 40 RS 40 Connection data Insulation stripping length Conductor cross-section Dimensions Mounting width Length (perpendicular to mounting rail) Height TS/TS 35 x 7.5 1) 2) Input voltage 5 V2) Function indicator Yellow LED Screw connection (GSE) 1118861001 Disconnect plug with screw connection (BL/SL) 1161560000 12 V0 Green LED 1118761001 1161660000 24 V- Yellow LED 24 V0 Yellow LED Green LED 1117461001 8065031001 1119460000 48 V0 Green LED 1161061001 1161860000 115 V0 Green LED 1161161001 1161960000 230 V~ Green LED 1161461001 1162060000 230 V~ Red LED 0.5...2.5 mm2 1160961001 1161760000 11778600001) Digital signal processing Ordering data Connection method 8182690000 7 mm 0.5...1.5 mm2 AWG 26...14 6 mm AWG 26...16 11.2 mm 70 mm 56 mm/51.5 mm 11.2 mm 74 mm 56 mm/51.5 mm Output 5 VTTL-compatible Conditionally level-compatible 137 Opto coupler on locking socket with multiple interface RSM (Opto-couplers) RSM 4 OS RSM 8 OS 4 opto-couplers 8 opto-couplers Note! During operation and maintenance please observe the relevant ESD measures. (ESD endangered area) Also available as relay coupler, see page 84/85 Schematic circuit diagram Opto coupler 24 Vdc / 2A RSM 16: 1 RSM 8: 1 RSM 4: 1 + 2 2 2 + max. 2A GND 11 14 3 3 3 + max. 2A +24V GND 21 12 24 GND 31 22 34 + GND +24V 41 32 44 max. 2A max. 2A max. 2A +24V 16 19/ 20/ 2 9 10 2 + + - 8 8 4 4 4 + max. 2A +24V DC voltage/positive switching (joint negative) Standard Opto coupler 5...48 Vdc / 100 mA 42 Rated data Input voltage Rated consumption - (W) Rated consumption ~ (VA) GND 81 84 +24V GND 82 +24V 161 164 162 5 V-1) 10 % 60 mW - 24 V- 10 % 400 mW - 24 V0 10 % 300 mW 0.35 VA 24 V- +10 % 288 mW - 5...48 V1) <1.6 V 0.1 A 5...48 V1) <1.6 V 0.1 A 5...48 V1) <1.6 V 0.1 A 24 V 10 % 0.4 V 2A Pulse duration, limiting overload current (not periodic) 0.8 A/10 ms 0.8 A/10 ms 0.8 A/10 ms 12 A/10 ms Max. reverse current (static current), at U 0.16 mA 100 Hz -40 C...+85 C 0.16 mA 100 Hz -40 C...+85 C 0.16 mA 20 Hz -40 C...+85 C 12 mA max. 100 Hz -40 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C -25 C...+60 C 75 mm 145 mm 285 mm 87 mm 75 mm 145 mm 285 mm 87 mm 75 mm 145 mm 285 mm 87 mm 75 mm 145 mm 285 mm 87 mm Output operating voltage Voltage drop at max. load current Output current Derating curve a = Continous operation b = Switching mode Continuous current Ambient temperature Switching frequency Storage temperature Ambient temperature -, rowed on mounting rail without clearances -, rowed with clearances x 20 mm Dimensions Mounting width RSM 4 RSM 8 RSM 16 Length (perpendicular to mounting rail) 1) 138 Not TTL-compatible Opto coupler on locking socket with multiple interface RSM RSM 16 OS 16 Opto couplers Ordering data Conn. method Input/output Screw/ Input voltage RSM 4 OS w/o. optocoupl. DC/AC voltage 4 optocoupl. RSM 8 OS w/o. optocoupl. 8 optocoupl. RSM 16 OS w/o. optocoupl. 16 optocoupl. Positive switching3) Negative switching4) 5 V-2) * * 24 V- * * * 24 V0 * Cat. No. 1123661001 1124061001 1124461001 8017581001 1123861001 1123761001 8003671001 8021391001 1124261001 8018221001 8082471001 1124661001 1125161001 Mount. width (mm) 75 145 285 75 75 75 145 145 145 285 285 285 75 1125261001 145 * equipped as standard with opto-coupler 5...48 Vdc / 100 mA Connection data Insulation stripping length Conductor cross-section Replacement opto-c. Type OS OS OS OS OS OS OS 7 mm 0.5...2.5 mm2/AWG 26...14 Input voltage 5 V-5) 10 % 12 V-5) 10 % 12 V0 10 % 24 V-5) 10 % 24 V-5) 10 % 24 V-5) 10 % 24 V0 10 % 2) 3) Output voltage 24 V- 20 % 5...48 V- 5...48 V- 5...48 V- 24 V- +10 % 250 V~ 5...48 V- 5 V TTL Input voltage on request Common negative potential, positive is switched Output current 0.1 A 0.1 A 0.1 A 0.1 A 2.0 A 0.1 A 0.1 A 4) 5) Cat. No. 1121100000 1124800000 1121200000 1124900000 1170200000 1153200000 1121300000 Common positive potential, negative is switched Not suitable for DC/AC version 139 Digital signal processing DC/negative switching (common positive) Opto coupler, locking socket for semi-conductor relays Single and multiple socket interfaceunit RS 1 HR RSM 4 HR RSM 8 HR RSM 8 HR-100 RSM 16 HR-100 Type RSM 4 HR Type RSM 8 HR Type Cat. No. RSM 8 HR-100 11662610013) Type Cat. No. RSM 16 HR-100* 11672610013) Advantages of semiconductor relays: * Wear-free switching also with high switching frequencies * Bounce-free switching * No electomagnetic interferences * High insulation-voltage between load and control circuit Note! The relevant ESD measures are to be observed during commissioning and maintenance (ESD endangered area) Schematic circuit diagram Ordering data Rated data (with inpu module)1) Input voltage, max. Input current (per channel) Max. output voltage Output current (per channel), max. Rated data (with output module)1) Input voltage, max.: Input current (per channel) Max. output supply voltage Max. output current (per channel) Auxilary voltage Status indicator Fuse Storage temperature Ambient temperature Connection data Conductor cross-section Screw connection Male connect. block DIN 416512) Sub-D"-connection2) Type RS 1 HR Cat. No. 11670610013) Cat. No. 11671610013) 250 V~ 25 mA 24 V0 250 V~ 25 mA 24 V0 250 V~ 25 mA 24 V0 250 V~ 25 mA 24 V0 250 V~ 25 mA 24 V0 Depending on module Depending on module Depending on module Depending on module Depending on module 24 V0 Depending on module 250 V 24 V0 Depending on module 250 V 24 V0 Depending on module 250 V 24 V0 Depending on module 250 V 24 V0 Depending on module 250 V Depending on module Depending on module Depending on module Depending on module Depending on module 24 V- 10 % LED red 5x20, 5 A quick -40 C...+70 C -25 C...+70 C Dependent on semiconductor relay used 24 V- 10 % LED red 5x20, 5 A quick -40 C...+70 C -25 C...+70 C Dependent on semiconductor relay used 24 V- 10 % LED red 5x20, 5 A quick -40 C...+70 C -25 C...+70 C Dependent on semiconductor relay used 24 V- 10 % LED red 5x20, 5 A quick -40 C...+70 C -25 C...+70 C Dependent on semiconductor relay used 24 V- 10 % LED red 5x20, 5 A quick -40 C...+70 C -25 C...+70 C Dependent on semiconductor relay used 0.5...2.5 mm2 - - 0.5...2.5 mm2 - - 0.5...2.5 mm2 10-pole 15-pole 0.5...2.5 mm2 10-pole 15-pole 0.5...2.5 mm2 20-pole 25-pole Dimensions Mounting width Length (perpendicular (to mounting rail) 1) 2) 140 Cat. No. 1166961001 35 mm 130 mm 249 mm 156 mm 305 mm 87 mm 87 mm 87 mm 109 mm 109 mm The rating data depend on the used module on request 3) Mixed placement of input and output modules is not valid. Semi-conductor relays Solid state relays for signal input and output Input module HRE 24 Input module HRE 115/HRE 230 AC/DC DC/DC Output module HRA 230 Output module HRA 60 DC/AC DC/DC Schematic circuit diagram Ordering data Rated data Input voltage Input current at max. V Input resistance Switch-on voltage Switch-off voltage Max. output operating voltage Voltage drop at max. load current Max. output current (Continous test) Derating curve a = self-cooling b = mounted on 2 k/W heat sink Continuous current Ambient temperature Min. Load current Leakage current in offcondition at rated load voltage Surge current Switch-on time Switch-off time Input impulse Storage temperature Ambient temperature 1) Type HRE 24 Cat. No. 117440000 Type HRE 115 Cat. No. 1174500000 Type HRE 230 Cat. No. 1174600000 Type HRA 230 Cat. No. 1174100000 Amp. Type HRA 60 Cat. No. 1174300000 10...32 V- (process) 21.33 mA 90...140 V0 (process) 10 mA 180 V...280 V0 (process) 6.4 mA 18...32 V- (Logic) - 18...32 V- (Logic) - 1.5 k - - 14 k - - 44 k - - 2.2 k 3V 1V 2.2 k 3V 1V 18...32 V (Logic)1) 18...32 V (Logic)1) 18...32 V (Logic)1) 24...250 V~1)2) (process) 5...60 V~1)2) ( process) 0.4 V 0.4 V 0.4 V - - 100 mA 100 mA 100 mA 3A 3 A, resistive load - - - 20 mA - max. 100 A - 5 ms 5 ms - max. 100 A - 20 ms 20 ms - max. 100 A - 20 ms 20 ms - 6 mA 75 A/20 ms 1/2 Period 1/2 Period unlimited, tmin 100 s 1 mA 5 A/1 s 100 s 750 s unlimited, tmin 100 s -40 C...+100 C -20 C...+ 70 C -40 C...+100 C -25 C...+ 70 C -40 C...+100 C -25 C...+ 70 C -40 C...+100 C -25 C...+ 70 C -40 C...+100 C -25 C...+ 70 C 250 V max. in connection with HR modules. Only negative-switching when used on HR-socket! 2) Digital signal processing Zero V. switch For inductive loads the module must be protected with diode or varistor. 141 Timers 142 Timers The IT product family of electronic delay timers from Weidmuller are the optimum solution for industrial tasks. The product family IT offers: Time ranges and supply voltages of delay timer relays The modules' functions for 4 or 7 time can be precisely selected via the rotary button. * Response delay (ITR) * Wiping contact without control input (ITWo) * Wiping contact with control input (ITWw) * Turn-off delay without control input (ITTo) * Turn off delay without control input (ITTw) Product ITR ITWo, ITTT ITTw ITWw ITMF, ITM ITTo The multiple voltage ranges of the supply voltage allow for a wide area of use in industry (see table). Time 0.1s - 100h Range 0.1 s - 1 s 1 s - 10 s 0.1 min - 1 min 10 h - 100 h 1 min - 10 min 0.1 h - 1 h 1 h- 10 h 0.06 s - 160 s 0.06 s - 0.6 s 0.25 s - 2.5 s 2 s - 20 s 16 s - 160 s Voltage supply 24 VDC/24...24UVAC 24 V - 240 VAC 24 VDC * Pulse generator (ITTT) * Multifunction (ITM) * Multifunction (ITMF) Output of the timing relays Characteristic data of output contacts Designation of types: The load in every module is switched by a changeover relay (250 V, 8 A). The multifunction module (ITM) switches both changeover relays immediately or, one changeover relay immediately and the other changeover relay delayed. Limit values by resistive load Service life of contacts by resistive load I = Industry T = Timer R = Response Delay Wo = Wiping contact relay without control input Switching operations Ww = Wiping contact relay with control input To = Turn -off delay without control input Tw = Turn-off delay with control input ITTo TT = Two Times MF = Multifunction Four Digital signal processing M = Multifunction Switching capacity (kVA) Load ITR, ITP, ITWo, ITWw, ITTw,ITTT, ITMF Current Control contact Load ITM Voltage 143 Functions of the Timers Response delay ITR timer relay As soon as the operating voltage is applied, the preset delay period T begins. After time period T has expired, output R connects the load. Wiping contact timer relay without control input ITWo When the operating voltage is applied, output R connects the load immediately. After the preset delay period T has expired, output R disconnects the load. Multifunction ITM/ITMF Function A: Response delay As soon as the operating voltage is applied, the preset delay period T begins. After time period T has expired, output R connects the load. Function Ac: Response delay and turn-off delay Wiping contact timer relay with control input ITWw As soon as the operating voltage is applied, a pulse (e. g. 50 ms) or a voltage is applied to control input Y1. Output R connects the load immediately. After the preset delay period T has expired, output R disconnects the load. Turn-off delay timer relay without control input ITTo As soon as the operating voltage is applied, output R connects the load. Delay period T does not begin until the operating voltage is switched off. After delay period T has expired, output R disconnects the load. As soon as operating voltage has been applied and control input Y1 has closed, delay period T begins. After time period T has expired, output R connects the load (delayed response). When control input Y1 is opened, the output disconnects the load after the preset time period has expired (delayed turn-off). Function At: Additive response delay Pulse generator ITTT The repeat cycles starts with two individually adjustable times after applying the supply voltage. There is a different starting state for each delay. As soon as the operating voltage has been applied and control input Y1 has been activated, output R connects the load for an indefinite period of time. When the control input is opened and after the preset time period T has expired, the output disconnects the load. Function D: Pulse generator (begins in the zero position) As soon as the operating voltage has been applied, output R simultaneously switches the load alternately between the zero position and operating position for the period of the preset time T. With this function, the cycle begins at the zero position. Function Di: Pulse generator (begins in the operating position) Turn-off delay timer relay with control input ITTw After the operating voltage has been applied and control input Y1 has been activated, output R connects the load for an indefinite period of time. When the control input is opened and after the preset time period T has expired, the output disconnects the load. Function C: Turn-off delay with control input As soon as the operating voltage has been applied and delay period T has expired, output R connects the load. At control input Y1 the contact break intervals are accumulated (additive process). As soon as the operating voltage is switched off, the load at output R is disconnected. Function B: Wiping contact with control input As soon as the operating voltage has been applied, a pulse (min 50 ms) or a voltage can be applied to control input Y1. Output R connects the load immediately. After delay period T has expired, output R disconnects the load. As soon as the operating voltage has been applied, output R simultaneously switches the load alternately between the zero position and operating position for the period of the preset time T. With this function, the cycle begins at the operating position. Function H: Wiping contact without control input As soon as the operating voltage is applied, output R connects the load immediately. After delay period T has expired, output R disconnects the load. Function Ht: Wiping contact, additive Function Bw: Wiping function The operating voltage must be applied. As soon as a voltage is applied to control input Y1, output R connects the load for the prest time T. After time period T has expired, output R disconnects the load. As soon as the control input is opened, output R once more connects the load for the duration of time period T. After time period T has expired, output R disconnects the load. As soon as the operating voltage is applied, output R connects the load immediately. At control input Y1 the contact break intervals are accumulated (additive process) and when the preset delay period has expired, output R disconnects the load. U = Operating voltage R = Output relay or load T = Delay Y1 = Control input 144 Timers Status LED Approvals and standards Two LED's show the status of the modules: This relay has a high resistance to interference. The housing material is self-extinguishing (UL94/V0). - green LED = supply voltage connected Manufacturing to IEC/VDE and UL/CSA approvals permit worldwide usage. - yellow LED = relay output active (not for ITTO) * IEC 255 static measuring relays * IEC529 testers and test procedures * IEC 664 regulations for high-voltage fuses for motor circuits Marking Marking is done on a removable tag or on the marking area. The function is printed on the front of the module. * IEC 801 EMC compatibility * VDE 0110 insulation coordination for low-voltage electrical equipment * VDE 0435 relays with fixed times Control lamp for verifying contact A control lamp can be wired parallel to input Y1 to show the status of control input. Assembly Mount direct onto DIN TS 35 mounting rails. Connection technology Dimensions IT Clamping yoke has the following capacities: * 2 x 1.5 mm2 with ferrule * 2 x 2.5 mm2 without ferrule * 1 x 4 mm2 without ferrule Digital signal processing on DIN rail on panel using M4 screws 145 Multifunctional Timers * Response delay * Response delay and turn-off delay * Additive response delay * Wiping contact with control input * Wiping function * Turn-off delay with control input * Pulse generator (begins in the zero position) * Pulse generator (begins in the operating position) * Wiping contact without control input * Wiping contact, additive ITM Function A: Response delay Function C: Turn-off delay with control input Multifunctional timer relay As soon as the operating voltage is applied, the preset delay period T begins. After time period T has expired, output R connects the load. Function Ac: Response delay and turn-off delay As soon as operating voltage has been applied and control input Y1 has closed, delay period T begins. After time period T has expired, output R connects the load (delayed response). When control input Y1 is opened, the output disconnects the load after the preset time period has expired (delayed turn-off). Schematic circuit diagram Function At: Additive response delay As soon as the operating voltage has been applied and control input Y1 has been activated, output R connects the load for an indefinite period of time. When the control input is opened and after the preset time period T has expired, the output disconnects the load. Function D: Pulse generator (begins in the zero position) As soon as the operating voltage has been applied, output R simultaneously switches the load alternately between the zero position and operating position for the period of the preset time T. With this function, the cycle begins at the zero position. Function Di: Pulse generator (begins in the operating position) Ordering data Contact Time periods Repeat accuracy (const. parameter) Accuracy of indication acc. to IEC 1812-1 Input Input voltage Voltage tolerance Duty factor Rated power consumption Min pulse duration type Max. reset time at voltage interruption Protection against voltage interruption Output Contact Contact material Service life - mechanical - electrical Switching current - max. - min. Max. switching voltage Switching current Status indicators Voltage applied Relay output active Approvals Standards Temperature - Storage temperature - Operating temperature Clearance/creepage path. acc. to IEC 664/VDE 0110 Protection category IEC 529 - Terminal block - Front Mounting Installation category to IEC 664 Connection - with ferrule - without ferrule Type ITM changeover 0.1 s - 100 h 1 s, 10 s, 1 min 1 h, 10 h, 100 h 0.5% 10% (25 C) Cat. No. 8362550000 12 V...240 Vac/dc / 50...60 Hz 85 - 110% UN 100 % 7 VA / 230 V~ 50 ms 100 ms > 10 ms Relay output 2 changeover AgCdO 5 x 106 switching operations 105 switching operations at 2000 VA resistive load 8 A0 / changeover contact 100 mA0 250 V0 2000 VA / 80 W green LED yellow LED UL / CSA IEC 529 / IEC 664 / IEC 801 / IEC 255 VDE 0435/ VDE 0110 -30C...+70C -20C...+60C 4 kV IP 20 IP 50 DIN rail 35 mm Category III 2 x 1.5 mm2 2 x 2.5 mm2 / 1 x 4 mm2 As soon as the operating voltage has been applied and delay period T has expired, output R connects the load. At control input Y1 the contact break intervals are accumulated (additive process). As soon as the operating voltage is switched off, the load at output R is disconnected. Function B: Wiping contact with control input As soon as the operating voltage has been applied, a pulse (min 50 ms) or a voltage can be applied to control input Y1. Output R connects the load immediately. After delay period T has expired, output R disconnects the load. As soon as the operating voltage has been applied, output R simultaneously switches the load alternately between the zero position and operating position for the period of the preset time T. With this function, the cycle begins at the operating position. Function H: Wiping contact without control input As soon as the operating voltage is applied, output R connects the load immediately. After delay period T has expired, output R disconnects the load. Function Ht: Wiping contact, additive Function Bw: Wiping function The operating voltage must be applied. As soon as a voltage is applied to control input Y1, output R connects the load for the prest time T. After time period T has expired, output R disconnects the load. As soon as the control input is opened, output R once more connects the load for the duration of time period T. After time period T has expired, output R disconnects the load. As soon as the operating voltage is applied, output R connects the load immediately. At control input Y1 the contact break intervals are accumulated (additive process) and when the preset delay period has expired, output R disconnects the load. U = Operating voltage R = Output relay or load T = Delay Enclosure material Weight, typ. 146 self extinguishing 110 g Y1 = Control input Timers ITTo ITTw Turn-off delay timer relay without control input Turn-off delay timer relay with control input Type ITTo Changeover 0.6 s -160 s (0.06 s - 0.6 s, 0,25 s - 2.5 s, 2 s - 20 s, 16 s - 160 s) 0.5% 10% (25 C) Type ITTw Changeover 0.1 s -100 h (0.1 s - 1 s, 1 s -10 s, 0.1 min - 1 min, 1 min - 10 min, 0.1 h - 1 h, 1 h - 10h) 0.5% 10% (25 C) Schematic circuit diagram Contact Time periods Repeat accuracy (const. parameter) Anzeigegenauigkeit gema IEC 1812-1 Input Input voltage Voltage tolerance Duty factor Rated power consumption Min. switch-on time for the supply Min pulse duration type Max. reset time at voltage interruption Protection against voltage interruption Output Contact Contact material Service life - mechanical - electrical Switching current - max. - min. Max. switching voltage Switching current Status indicators Voltage applied Relay output active Approvals Standards Temperature - Storage temperature - Operating temperature Clearance/creepage path. acc. to IEC 664/VDE 0110 Protection category IEC 529 - Terminal block - Front Mounting Installation category to IEC 664 Connection - with ferrule - without ferrule Enclosure material Weight, typ. 24 Vdc/ 24...240 Vac / 50...60 Hz 85 - 110% UN 100 % 0.5 W / 30 VA / 230 V~ _ 50 ms 100 ms > 10 ms Relay output 2 changeover AgCdO 5 x 106 switching operations 105 switching operations at 1250 VA resistive load 8 A0 / changeover contact 100 mA0 250 V0 1250 VA / 80 W green LED Cat. No. 8362600000 Cat. No. 8362610000 24 Vdc/ 24...240 Vac / 50...60 Hz 85 - 115% UN (110% for 240 V) 100 % 0.5 W / 24 V- / 1 W / 48 V- / 2 VA / 48 V~ 1.5 VA / 24 V~ 12 VA / 230 V~ 50 ms 100 ms > 10 ms Relay output 1 changeover AgCdO 5 x 106 switching operations 105 switching operations at 2000 VA resistive load 8 A0 100 mA0 250 V0 2000 VA / 80 W UL / CSA IEC 529 / IEC 664 / IEC 801 / IEC 255 VDE 0435/ VDE 0110 -30C...+70C -20C...+60C 4 kV / 2 IP 20 IP 50 DIN rail 35 mm Category III green LED yellow LED UL / CSA IEC 529 / IEC 664 / IEC 801 / IEC 255 VDE 0435/ VDE 0110 -30C...+70C -20C...+60C 4 kV / 2 IP 20 IP 50 DIN rail 35 mm Category III 2 x 1.5 mm2 2 x 2.5 mm2 / 1 x 4 mm2 2 x 1.5 mm2 2 x 2.5 mm2 / 1 x 4 mm2 self extinguishing 100 g self extinguishing 100 g Digital signal processing Ordering data 147 Timers ITWo ITWw Wiping contact timer relay without control input Wiping contact timer relay with control input Type ITWo Changeover 0.1 s - 100 h (0.1 - 1 s, 1 s - 10 s, 0.1 min. - 1 min., 1 min. - 10 min., 0.1 h - 1 h, 1 h - 10 h, 100 h) 0.5% 10% (25 C) Type ITWw Changeover 0.1 s - 100 h (0.1 - 1 s, 1 s - 10 s, 0.1 min. - 1 min., 1 min. - 10 min., 0.1 h - 1 h, 1 h - 10 h, 100 h) 0.5% 10% (25 C) Schematic circuit diagram Ordering data Contact Time periods Repeat accuracy (const. parameter) Accuracy of indication acc. to IEC 1812-1 Input Input voltage Voltage tolerance Duty factor Rated power consumption Min pulse duration type Max. reset time at voltage interruption Protection against voltage interruption Output Contact Contact material Service life - mechanical - electrical Switching current - max. - min. Max. switching voltage Switching current Status indicators Voltage applied Relay output active Approvals Standards Temperature - Storage temperature - Operating temperature Clearance/creepage path. acc. to IEC 664/VDE 0110 Protection category IEC 529 - Terminal block - Front Mounting Installation category to IEC 664 Connection - with ferrule - without ferrule Enclosure material Weight, typ. 148 Cat. No. 8362580000 24 Vdc/ 24...240 Vac / 50...60 Hz 85 - 115% UN (110% for 240 V) 100 % 0.5 W / 24 V1.5 VA / 24 V~ 12 VA / 230 V~ 50 ms 100 ms > 10 ms Relay output 1 changeover AgCdO 5 x 106 switching operations 105 switching operations at 2000 VA resistive load 8 A0 100 mA0 250 V0 2000 VA / 80 W 24 Vdc/ 24...240 Vac / 50...60 Hz 85 - 115% UN (110% for 240 V) 100 % 0.5 W / 24 V- / 1 W / 48 V- / 2 VA / 48 V~ 1.5 VA / 24 V~ 12 VA / 230 V~ 50 ms 100 ms > 10 ms Relay output 1 changeover AgCdO 5 x 106 switching operations 105 switching operations at 2000 VA resistive load 8 A0 100 mA0 250 V0 2000 VA / 80 W green LED yellow LED UL / CSA IEC 529 / IEC 664 / IEC 801 / IEC 255 VDE 0435/ VDE 0110 -30C...+70C -20C...+60C 4 kV / 2 IP 20 IP 50 DIN rail 35 mm Category III green LED yellow LED UL / CSA IEC 529 / IEC 664 / IEC 801 / IEC 255 VDE 0435/ VDE 0110 -30C...+70C -20C...+60C 4 kV / 2 IP 20 IP 50 DIN rail 35 mm Category III 2 x 1.5 mm2 2 x 2.5 mm2 / 1 x 4 mm2 2 x 1.5 mm2 2 x 2.5 mm2 / 1 x 4 mm2 self extinguishing 100 g self extinguishing 100 g Cat. No. 8362590000 Timers ITTT ITMF Pulse generator Multifunction - timer relay Schematic circuit diagram Contact Time periods Repeat accuracy (const. parameter) Accuracy of indication acc. to IEC 1812-1 Input Input voltage Voltage tolerance Duty factor Rated power consumption Min pulse duration type Max. reset time at voltage interruption Protection against voltage interruption Output Contact Contact material Service life - mechanical - electrical Switching current - max. - min. Max. switching voltage Switching current Status indicators Voltage applied Relay output active Approvals Standards Temperature - Storage temperature - Operating temperature Clearance/creepage path. acc. to IEC 664/VDE 0110 Protection category IEC 529 - Terminal block - Front Mounting Installation category to IEC 664 Connection - with ferrule - without ferrule Enclosure material Weight, typ. Type ITTT Changeover 0.1 s - 100 h (0.1 - 1 s, 1 s - 10 s, 0.1 min. - 1 min., 1 min. - 10 min., 0.1 h - 1 h, 1 h - 10 h, 100 h) 0.5% 10% (25 C) Cat. No. 8324050000 Type ITMF Changeover 0.1 s - 100 h (0.1 - 1 s, 1 s - 10 s, 0.1 min. - 1 min., 1 min. - 10 min., 0.1 h - 1 h, 1 h - 10 h, 100 h) 0.5% 10% (25 C) 24 Vdc/ 24...240 Vac / 50...60 Hz 85 - 115% UN (110% for 240 V) 100 % 0.5 W / 24 V1.5 VA / 24 V~ 12 VA / 230 V~ 50 ms 100 ms > 10 ms Relay output 1 changeover AgCdO 5 x 106 switching operations 105 switching operations at 2000 VA resistive load 8 A0 100 mA0 250 V0 2000 VA / 80 W 24 Vdc/ 24...240 Vac / 50...60 Hz 85 - 115% UN (110% for 240 V) 100 % 0.5 W / 24 V- / 1 W / 48 V1.5 VA / 24 V~ / 2 VA / 48 V~ 12 VA / 230 V~ 50 ms 100 ms > 10 ms Relay output 1 changeover AgCdO 5 x 106 switching operations 105 switching operations at 2000 VA resistive load 8 A0 100 mA0 250 V0 2000 VA / 80 W green LED yellow LED UL / CSA IEC 529 / IEC 664 / IEC 801 / IEC 255 VDE 0435/ VDE 0110 -30C...+70C -20C...+60C 4 kV / 2 IP 20 IP 50 DIN rail 35 mm Category III green LED yellow LED UL / CSA IEC 529 / IEC 664 / IEC 801 / IEC 255 VDE 0435/ VDE 0110 -30C...+70C -20C...+60C 4 kV / 2 IP 20 IP 50 DIN rail 35 mm Category III 2 x 1.5 mm2 2 x 2.5 mm2 / 1 x 4 mm2 2 x 1.5 mm2 2 x 2.5 mm2 / 1 x 4 mm2 self extinguishing 100 g self extinguishing 100 g Cat. No. 8287770000 Digital signal processing Ordering data 149 Timers ITR Response delay timer relay Schematic circuit diagram Ordering data Contact Time periods Repeat accuracy (const. parameter) Accuracy of indication acc. to IEC 1812-1 Input Input voltage Voltage tolerance Duty factor Rated power consumption Min pulse duration type Max. reset time at voltage interruption Protection against voltage interruption Output Contact Contact material Service life - mechanical - electrical Switching current - max. - min. Max. switching voltage Switching current Status indicators Voltage applied Relay output active Approvals Standards Temperature - Storage temperature - Operating temperature Clearance/creepage path. acc. to IEC 664/VDE 0110 Protection category IEC 529 - Terminal block - Front Mounting Installation category to IEC 664 Connection - with ferrule - without ferrule Enclosure material Weight, typ. 150 Type ITR Changeover 0.1 s - 100 h (0.1 - 1 s, 1 s - 10 s, 0.1 min. - 1 min., 1 min. - 10 min., 0.1 h - 1 h, 1 h - 10 h, 100 h) 0.5% 10% (25 C) 24 Vdc/ 24...240 Vac / 50...60 Hz 85 - 115% UN (110% for 240 V) 100 % 0.5 W / 24 V1.5 VA / 24 V~ 12 VA / 230 V~ 50 ms 100 ms > 10 ms Relay output 1 changeover AgCdO 5 x 106 switching operations 105 switching operations at 2000 VA resistive load 8 A0 100 mA0 250 V0 2000 VA / 80 W green LED yellow LED UL / CSA IEC 529 / IEC 664 / IEC 801 / IEC 255 VDE 0435/ VDE 0110 -30C...+70C -20C...+60C 4 kV / 2 IP 20 IP 50 DIN rail 35 mm Category III 2 x 1.5 mm2 2 x 2.5 mm2 / 1 x 4 mm2 self extinguishing 100 g Cat. No. 8362570000 Timers Signal conditioning DKZ/DKZA timer modules * Components for extending short pulses * Provides PLC versions with switch-on/off delay * Fixed times DKZ DKZA DKZ 24 Vac/dc DKZA 24 Vac/dc DKZA 24 Vac/dc Type Cat. No. DKZ 24 Vac/dc 328008130000 DKZ 24 Vac/dc 35 8008190000 Type Cat. No. DKZA 24 Vdc 32 8008120000 DKZA 24 Vdc 35 8008180000 Type Cat. No. DKZA 24 Vdc 32 8020990000 DKZA 24 Vdc 35 8022110000 24 Vac/dc 10 % 5.1 mAdc/6.1 mAac 10 % 24 Vdc 18 % 6.7 mA 10 % 200 mA 10 % 160 mW 10 % 24 Vdc 10 % 6.7 mA 10 % 200 mA 10 % 160 mW 50 ms 2 ms 150 ms 2.5 ms Ordering data For TS 32 For TS 35 Y W Technical data Input Input voltage Input nominal current Input current (at first-time power-up) Input power Switch-on delay Switch-off delay Min. pulse duration of input voltage 130 mW 10 %/150 mVA 10 % 1s 0.7 ms Digital signal processing Schematic circuit diagram Output Max. output voltage Max. output voltage Reverse current, max. (closed-circuit current) Max. voltage drop at max. load current Max. switching frequency 5...48 Vdc 20 mA 0,16 mA (at 48 V) 1V 0.9 Hz 5...48 Vdc 20 mA 0,16 mA (at 48 V) 1.6 V 20 Hz 5...48 Vdc 20 mA 0,16 mA (at 48 V) 1.6 V 20 Hz Isolation coordinates acc. to DIN VDE 0160, Draft11/94 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance and creepage distances Voltage proof, input/output-TS Operating temperature without clearances with clearances Storage temperature Total width Conductor Conductor cross-section Reverse polarity protection 300 V 4 kV III 2 4 mm 4 kVeff -25 C...+50 C -25 C...+50 C -40 C...+85 C 6 mm AWG 22...12 0.5...4 mm2 ja 300 V 4 kV III 2 4 mm 4 kVeff -25 C...+50 C -25 C...+50 C -40 C...+85 C 6 mm AWG 22...12 0.5...4 mm2 ja 300 V 4 kV III 2 4 mm 4 kVeff -25 C...+50 C -25 C...+50 C -40 C...+85 C 6 mm AWG 22...12 0.5...4 mm2 ja Accessories End plate Type AP DKT4 Dimensions see Page 305 Cat. No. 0687560000 Type AP DKT4 Page 305 Cat. No. 0687560000 Type AP DKT4 Cat. No. 0687560000 Page 305 151 Timers Pulse conditioning DKZ/DKZA timer modules DKZ DKZA DKZ DK5 DKZ DK5 DKZ DK5 Schematic circuit diagram Ordering data For TS 32 For TS 35 With combi foot TS32/TS 35 Technical data Input Supply voltage Supply current Control voltage Control input current Type DKZ DK5 Cat. No. 8228680000 Type DKZ DK5 Cat. No. 8243780000 Type DKZ DK5 Cat. No. 8019650000 24 Vdc 20 % ca. 12 mA 24 Vdc 20 % ca. 12 mA 24 Vdc 20 % ca. 12 mA Output Output voltage Max. output current Internal voltage drop Range of switch-on delay 5...48 Vdc 100 mA 1.6 V 10...100 ms (adjustable) 5...48 Vdc 100 mA 1.6 V 100 ms...1 s (adjustable) 5...48 Vdc 100 mA 1.6 V 1...100 s (adjustable) Isolation coordinates acc. to DIN VDE 0160, Draft11/94 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance and creepage distances Voltage proof, input/output-TS Operating temperature without clearances with clearances Storage temperature Total width Conductor Conductor cross-section 300 V 6 kV IV 2 5.5 mm 4 kVeff -25 C...+40 C -25 C...+50 C -40 C...+85 C 6 mm AWG 22...12 0.5...4 mm2 300 V 6 kV IV 2 5.5 mm 4 kVeff -25 C...+40 C -25 C...+50 C -40 C...+85 C 6 mm AWG 22...12 0.5...4 mm2 300 V 6 kV IV 2 5.5 mm 4 kVeff -25 C...+40 C -25 C...+50 C -40 C...+85 C 6 mm AWG 22...12 0.5...4 mm2 Accessories End plate Type AP DK5 Dimensions see Page 305 152 Cat. No. 8268870000 Type AP DK5 Page 305 Cat. No. 8268870000 Type AP DK5 Page 305 Cat. No. 8268870000 Timers Signal conditioning DKZA timer modules * Components for extending short pulses * Provides PLC versions with switch-on/off delay * Fixed times DKZA DK5 DKA DK5 DKZA DK5 Schematic circuit diagram Type DKZA DK5 Cat. No. 8228690000 Type DKZA DK5 Cat. No. 8243770000 Type DKZA DK5 Cat. No. 8019630000 24 Vdc 20 % ca. 11 mA 24 Vdc 20 % ca. 0.5 mA 2 ms 24 Vdc 20 % ca. 11 mA 24 Vdc 20 % ca. 0.5 mA 2 ms 24 Vdc 20 % ca. 11 mA 24 Vdc 20 % ca. 0.5 mA 2 ms 5...48 Vdc 100 mA 1.6 V 10...100 ms (adjustable) 5...48 Vdc 100 mA 1.6 V 100 ms...1s (adjustable) 5...48 Vdc 100 mA 1.6 V 1...100 s (adjustable) Isolation coordinates acc. to DIN VDE 0160, Draft11/94 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance and creepage distances Voltage proof input/output-TS Storage temperature Operating temperature without clearances with clearances Total width Conductor Conductor cross-section 300 V 6 kV IV 2 5.5 mm 4 kVeff -25 C...+40 C -25 C...+50 C -40 C...+85 C 6 mm AWG 22...12 0.5...4 mm2 300 V 4 kVeff IV 2 5.5 mm 6 kV -40...+85 C -25...+40 C -25...+50 C 6 mm AWG 22...12 0.5...4 mm2 300 V 4 kVeff IV 2 5.5 mm 6 kV -40...+85 C -25...+40 C -25...+50 C 6 mm AWG 22...12 0.5...4 mm2 Accessories End plate Type AP DK5 Dimensions see Page 305 Cat. No. 8268870000 Type AP DK5 Page 305 Cat. No. 8268870000 Type AP DK5 Digital signal processing Ordering data For TS 32 For TS 35 With combi foot TS 32/TS 35 Technical data Input: Supply voltage Supply current Control voltage Control input curren Min. pulse duration of input voltage Output: Output voltage Max. output current Internal voltage drop Range of switch-off delay Cat. No. 8268870000 Page 305 153 Timers Turn off delay module MCZ TO MCZ TO 24 Vdc turn-off delay 50 ms MCZ TO 24 Vdc turn-off delay 150 ms Ordering data For TS 35 Type MCZ TO 24 Vdc turn-off delay 50 ms Type MCZ TO 24 Vdc turn-off delay 150 ms Technical data Input Input voltage Min. pulse duration Power consupmtion Input power Power consumption when pulse applied 24 Vdc 10 % 2 ms 6.7 mA 10 % 160 mW 200 mA Output Output voltage Max. output current Max. voltage drop at max. load Impulse loading/limiting overload current Reverse current at 48 V (static current) Switch-off delay Switching frequency dc 5...48 Vdc 20 mA 1.6 V 200 mA max. 0,16 mA 50 ms 20 Hz Insulation coordination/safe disconnection to EN 50178 Rated voltage Rated impulse voltage Overvoltage category Pollution severity Clearance and creepage distances Voltage proof, input/output mounting rail 300 V 6 kV III 2 5.5 mm 4 kVeff / 1 min 300 V 6 kV III 2 5.5 mm 4 kVeff / 1 min Opto coupler to VDE 0884 to VDE 0884 Ambient temperature Storage temperature Conductor Conductor cross-section Approvals Total width -25 C...+50 C -40 C...+85 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm -25 C...+50 C -40 C...+85 C AWG 22...12 1.5 mm2 CE, UL, CSA 6 mm tv = var The timer module can be used for extending short pulses and fixed times. Provides PLC versions with switch off delay. Schematic circuit diagram 154 Cat. No. 8324590000 24 Vdc 10 % 2.5 ms 6.7 mA 10 % 160 mW 200 mA 5...48 Vdc 20 mA 1.6 V 200 mA max. 0,16 mA 150 ms 5 Hz Cat. No. 8286410000 155 Digital signal processing