86 Series - Timer modules Features 86.00 Timer modules for use in conjunction with relay & socket. 86.00 - Multi-function & multi-voltage timer module *Timer module for 90 and 92 series sockets *Wide supply voltage range (12 - 240 V) *LED indicator Time scale: from 0.05s to 100 h Multi-function * Plug-in for use with 90.02, 90.03 and 92.03 sockets * 81.1 35.5 20.4 * BE: Signal OFF delay CE: Signal ON & OFF delay DE: Signal ON pulse EE: Signal OFF pulse FE: Signal ON delay + OFF pulse 4 21.6 AI: ON delay DI: ON pulse SW: Symmetrical recycling: ON start 26.9 90.03 + 60.13 + 86.00 33.5 38 relay +socket relay +socket A2 A2 A1 B1 A1 B1 54 S U U N/- wiring diagram without signal START 10,5 6,3 86.00 N/- L/+ L/+ wiring diagram with signal START Contact specification Contact configuration Rated current/Maximum peak current A Rated voltage/Maximum switching voltage V AC Rated load AC1 VA Rated load AC15 (230 V AC) VA see 60 and 62 series relays kW Note: Do not use with relays 62.3x.x012.x300 and 62.3x.x012.x600 Single phase motor rating (230 V AC) Breaking capacity DC1: 30/110/220 V Minimum switching load A 86 mW (V/mA) Standard contact material Supply specification Nominal voltage (UN) V AC (50/60 Hz) 12...240 V DC 12...240 Rated power AC/DC Operating range W 1.2 V AC (50/60 Hz) 10.2...265 DC 10.2...265 Technical data (0.05...1)s, (0.5...10)s, (5...100)s, (0.5...10)min, (5...100)min, (0.5...10)h, (5...100)h Specified time range % 1 Recovery time ms 50 Minimun control impulse ms 50 % 5 Repeatability Setting accuracy full range Electrical life at rated load in AC1 Ambient temperature range Protection category cycles C see 60 and 62 series relays -20...+50 IP 20 Approvals (according to type) 181 86 Series - Timer modules Features 86.10 86.20 Timer modules for use in conjunction with relay & socket. 86.10 - ON delay timer module 86.20 - ON pulse timer module * Timer module for 90, 92, 94 and 95 series sockets * LED indicator * 76 60.9 * * * Mono-function Plug-in for use with 90.02, 90.03, 92.03, 94.02, 94.03, 94.04, 95.03, 95.05 sockets = 32 Mono-function Plug-in for use with 90.02, 90.03, 92.03, 94.02, 94.03, 94.04, 95.03, 95.05 sockets DI: ON pulse relay +socket relay +socket = 35.4 AI: ON delay 32 95.05 + 40.52 + 86.10 A2 15.8 A1 A2 L/+ N/- A1 10.5 U U L/+ 34 N/- 86.10 , 86.20 wiring diagram without signal START wiring diagram without signal START see 40, 44, 55, 60 and 62 series relays see 40, 44, 55, 60 and 62 series relays 12...24 12...24 V DC 12...24 (non polarized) 12...24 (non polarized) mW 150 150 AC (0.8...1.1)UN (0.8...1.1)UN DC (0.8...1.1)UN (0.8...1.1)UN (1.5...15)s,(6...60)s,(0.8...8)min,(6.4...64)min (1.5...15)s,(6...60)s,(0.8...8)min,(6.4...64)min Contact specification Contact configuration Rated current/Maximum peak current A Rated voltage/Maximum switching voltage V AC Rated load AC1 VA Rated load AC15 (230 V AC) VA Single phase motor rating (230 V AC) Breaking capacity DC1: 30/110/220 V 86 Minimum switching load kW A mW (V/mA) Standard contact material Supply specification Nominal voltage (UN) V AC (50/60 Hz) Rated power AC/DC Operating range Technical data Specified time range Repeatability % 1 1 Recovery time ms 150 150 Minimum control impulse ms -- -- Setting accuracy-full range Electrical life at rated load in AC1 Ambient temperature range Protection category Approvals (according to type) 182 % cycles C 5 5 see 40, 44, 55, 60 and 62 series relays see 40, 44, 55, 60 and 62 series relays 0...+50 0...+50 IP 20 IP 20 86 Series - Timer modules Ordering information Example: 86 series multi-function timer module, (12...240)V AC/DC supply voltage. 8 6 . 0 0 . 0 . 2 4 0 . 0 0 0 0 Supply voltage 024 = (12...24)V AC/DC (86.10/20 only) 240 = (12...240)V AC/DC (86.00 only) Series Type 0 = Multi-function (AI, DI, SW, BE, CE, DE, EE, FE) 1 = Mono-function (AI) 2 = Mono-function (DI) Supply version 0 = AC (50/60 Hz)/DC No. of poles see 40, 44, 55, 60 and 62 series relays Poles for chosesen relay/socket combination according to chart below Combinations Number of poles 1 1 2 2 2 2 3 3 3 4 Relay type 40.31 40.61 40.52/44.52/44.62 55.32 60.12 62.32 55.33 60.13 62.33 55.34 Socket type 95.03 95.05 95.05 94.02 90.02 92.03 94.03 90.03 92.03 94.04 Timer module 86.10/86.20 86.10/86.20 86.10/86.20 86.10/86.20 86.00/86.10/86.20 86.00/86.10/86.20 86.10/86.20 86.00/86.10/86.20 86.00/86.10/86.20 86.10/86.20 Technical data EMC specifications Type of test Reference standard 86.00 86.10/20 contact discharge EN 61000-4-2 4 kV n.a. air discharge EN 61000-4-2 8 kV 8 kV Radio-frequency electromagnetic field (80 / 1000 MHz) EN 61000-4-3 10 V/m 10 V/m Electrostatic discharge Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 2 kV 2 kV Surges (1.2/50 s) on Supply terminals common mode EN 61000-4-5 2 kV 2 kV differential mode EN 61000-4-5 1 kV -- EN 61000-4-6 10 V 10 V EN 55022 class B class B 86.00 86.10, 86.20 Radio-frequency common mode (0.15 / 80 MHz) 86 on Supply terminals Radiated and conducted emission Other data Current absorption on signal control (B1) Power lost to the environment mA 1 -- without contact current W 0.1 (12 V) - 1 (230 V) 0.2 with rated current see 40, 44, 55, 60, 62 series relays see 60 and 62 series relays Time scales Type 86.00 1 2 3 (0.05...1)s 1 2 3 (0.5...10)s 1 2 3 (5...100)s 1 2 3 (0.5...10)min 1 2 3 (5...100)min 1 2 3 (0.5...10)h 1 2 3 (5...100)h Type 86.10 Type 86.20 (1.5...15)s (6...60)s (0.8...8)min (6.4...64)min NOTE: time scales and functions must be set before energising the timer. 183 86 Series - Timer modules Functions U = Supply Voltage S = Signal switch LED Type 86.00 LED Type 86.10/20 = Output Contact Supply voltage NO output contact OFF Open ON Open ON Open (timing in progress) ON Closed Without signal Start= Start via contact in supply line (A1). With signal Start = Start via contact into control terminal (B1). Wiring diagram Type 86.00 Without signal START 4 5 6 U t10 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12). 76 60.9 32 COM 21 11 COM 14 NO 24 14 NO 12 NC 22 12 NC 28.3 A2 A1 A2 COIL 95.03 A1 COIL 95.05 15.8 35.4 O 3.2 28.3 O 3.2 = 78.6 78.6 = 11 15.8 32 8-way jumper link for 95.03 and 95.05 sockets 095.18 Rated values 10 A - 250 V 86 110.5 3.3 095.18 15 15.8 15.8 15.8 15.8 15.8 15 10.3 7 5.1 185 86 Series - Sockets and accessories Screw terminal (Box clamp) socket 94.02 94.02.0 94.03 94.03.0 94.04 94.04.0 panel or 35 mm rail (EN 50022) mount Blue Black Black Black For relay type 55.32 Blue 55.33 Blue 55.32, 55.34 Accessories 94.04 Approvals (according to type): Metal retaining clip 094.71 Plastic retaining and release clip 094.01 (supplied with socket - packaging code SPA) 6-way jumper link 094.06 094.06.0 094.06 Identification tag 094.06.0 094.06 094.00.4 Timer modules 86.10, 86.20 Sheet of marker tags for retaining and release clip 094.01 060.72 plastic, 72 tags, 6x12 mm Technical data 094.01 Rated values 10 A - 250 V Dielectric strength 2 kV AC Protection category IP 20 Ambient temperature C -40...+70 Screw torque Nm 0.5 Wire strip length mm 8 Max. wire size for 94.02/03/04 sockets solid wire 060.72 mm 2 stranded wire 1x6 / 2x2.5 1x4 / 2x2.5 AWG 1x10 / 2x14 41 12 11 9 COM 31 9 21 8 11 7 COM 41 12 31 11 21 10 11 9 COM 44 8 14 5 NO 34 6 24 5 14 4 NO 44 8 34 7 24 6 14 5 NO 42 4 12 1 NC 32 3 22 2 12 1 NC 42 4 32 3 22 2 12 1 NC A2 14 A1 13 A2 14 A1 13 A2 14 COIL COIL 27 COIL 25.9 27 60.9 17.5 17.5 35.6 76 18.9 34.9 86 O3 34.9 76 O3 34.9 76 O3 O 3.2 O 3.2 O 3.2 21.5 27 A1 13 1x12 / 2x14 32 35.5 94.02 94.04 94.03 6-way jumper link for 94.02, 94.03 and 94.04 sockets 094.06 Rated values 10 A - 250 V 135 3.3 094.06 10.3 7 5.1 0.75 186 26.25 27 27 27 26.25 094.06.0 86 Series - Sockets and accessories Screw terminal (Box clamp) socket panel or 35 mm rail (EN 50022) mount For relay type Accessories Metal retaining clip 6-way jumper link Identification tag Timer module Technical data Double terminal A1 (for easy start connection) Rated values Dielectric strength Protection category Ambient temperature Screw torque Wire strip length Max. wire size for 90.02 and 90.03 sockets Approvals (according to type): 90.03 Blue 60.13 90.03.0 Black 090.33 090.06 090.00.2 86.00, 86.10, 86.20 C Nm mm mm2 AWG 10 A - 250 V 2 kV AC IP 20 -40...+70 0.6 10 solid wire 1x6 / 2x2.5 1x10 / 2x14 stranded wire 1x4 / 2x2.5 1x12 / 2x14 38 NO NC NO NC NO NC 24 6 22 5 12 4 14 3 34 9 32 8 24 7 22 5 14 3 12 4 A2 7 21 8 11 1 A1 2 A2 10 31 11 21 6 A1 2 11 1 A1 2 81.1 77.5 COIL COM COIL COM COIL 34.8 34.8 3.2 3.2 35.5 NO 77.5 NC 20.4 38 NO NC COIL COM COM START COM COIL 90.02 4 A1 2 90.02.0 Black 21.6 90.03 90.02 Blue 60.12 90.03 30.5 30.5 26.9 33.5 6-way jumper link for 90.02 and 90.03 sockets Rated values 090.06 38 38 0.7 49.5 15 23 15 23 15 49.5 2.7 38 11 38 13.7 38 090.06 10 A - 250 V 12.8 Approvals (according to type): 86 187 86 Series - Sockets and accessories 92.03 Approvals (according to type): Screw terminal (Box clamp) socket panel or 35 mm rail (EN 50022) mount For relay type Accessories Metal retaining clip (supplied with socket - packaging code SMA) Identification tag Timer modules Technical data Rated values Insulation Protection category Ambient temperature C Screw torque Nm Wire strip length mm Max. wire size for 92.03 socket mm2 AWG NO 3 32 2 22 1 12 NC 34.3 COM 4 14 3.2 7 11 5 24 B A2 A A1 COIL 21.6 46.3 35.4 91.3 8 21 6 34 30.25 27 32 86 188 92.03.0 (black) 62.32, 62.33 092.71 092.00.2 86.00, 86.10, 86.20 16 A - 250 V 6 kV (1.2/50 s) between coil and contacts IP 20 -40...+70 0.8 10 solid wire stranded wire 1x10 / 2x4 1x6 / 2x4 1x8 / 2x12 1x10 / 2x12 78.5 60.9 40 35.5 27 9 31 92.03 (blue)