%BUB4IFFU
3-line sine-wave EMC output filters
for converters and power electronics
SineFormer
520 V AC, 11 ... 320 A, 40 °C
Series/type: B84143V*R127
Date: November 2007
© EPCOS AG 2007. Reproduc tion, publ icati on and dis semination of this publi catio n and the infor-
mation contained therein without EPCOS’ prior express consent is prohibited.
207/07
3-li ne f ilters
Sine-wave EMC output filters
SineFormer B84143V*R127
Please read Cautions and warnings and
Important notes at the end of this doc um ent.
Filters for converters and power electronics
Rated voltage 520 V AC, 50/60 Hz
Rated current 11 to 320 A
Construction
3-line sine-wave EMC output filter
Metal case
Features
Supersede shielded motor cables
Motor noise reduction
Reduction of bearing current
dv/dt reduction
Easy to install
Compact design
Degree of protection: IP 201)
Design complies with EN 60939, UL 1283, CSA 22.2 No.8
Optimized for long motor cables (up to 1000 m) and
operation under full load
No integrated forced ventilation (maintenance-free)
Connection to converter DC-link is not necessary
Reducing eddy current losses
Applications
Frequency converters for motor drives, e.g.
–elevators
pumps
traction and conveyer systems
HVAC systems (heating, ventilation and air conditioning)
Terminals
Line side (to converter): shielded cable up to 180 A;
copper bus bars for the 320-A filter
Load side (to motor): Finger-safe terminal blocks up to 180 A;
copper bus bars for the 320-A filter
Marking
Marking on component:
Manufacturer’s logo, ordering code, rated voltage,
rated current, rated motor frequency, rated switch frequency,
rated temperature, climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code, date code, quantity
1
)
To IEC 60529:2001
307/07
3-line filters B84143V*R 127
Sine-wave EMC output filters

SineFormer
Please read Cautions and warnings and
Important notes at the end of this doc um ent.
Typical circuit diagram
Technical data and measuring conditions
Rated voltage VR520 V AC, 50/60 Hz
320-A type: 600 V AC
Rated current IRReferred to 40 °C ambient temperature
Test voltage Vtest 2100 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case)
Frequency Motor
Pulse (switch) 0 ... 100 Hz
4 ... 8 kHz (320-A type: 2.5 ... 3.0 kHz)
Overload capability (thermal) 1.5 · IR for 1 min per hour
Max. dv/dt on filter input 5 kV/μs
Convection distance to other devices See next page
Vibration (sine) 10 cycles, 1 oct./min, 3 ... 13 Hz: 3 mm, 3 ... 200 Hz: 1 g
Shock (half sine) 15 g, 11 ms, 3 axis, 3 shocks per direction, 18 total
(to IEC 60 068-2-6)
Current (IR) derating depending on altitude From 1000 ... 4000 m: 5%/1000 m
Current (IR) derating depending on
am bient te mperatu re From 40 ... 60 °C: 10%/5 °C
Temperature Inside iron choke: approx. 130 °C
Housing: approx. 70 °C
Noise Approx. 72 dB (A)
Climatic category (IEC 60068-1) 25/100/21 (–25 °C/+100 °C/21 days damp heat test)
U1
W1
Converter
SSB2260-B
V1 V2
W2
U2
Motor
407/07
3-li ne f ilters
Sine-wave EMC output filters
SineFormer B84143V*R127
Please read Cautions and warnings and
Important notes at the end of this document.
Characteristics and ordering codes
× = approval granted
Convection space (cabinet fan recommended)
VR
AC IRTerminal
cross
section
Voltage
drop Losses
at
100 Hz
Rtyp Approx.
weight Ordering code Approvals
VAmm
2%WmΩkg
520 11 4 5 50 46 9 B84143V0011R127 ××
16 6 7 70 32 11 B84143V0016R127 ××
33 10 8 120 20 24 B84143V0033R127 ××
66 25 8 180 15 47 B84143V0066R127 ××
95 50 10 250 8 99 B84143V0095R127 ××
180 150 10 400 6 125 B84143V0180R127 ××
600 320 see dim.
drawing 10 750 4 195 B84143V0320R127 −−
SSB2257-R
>200 mm >200 mm
>100 mm
>100 mm
SSB2258-Z
>200 mm
507/07
3-line filters B84143V*R 127
Sine-wave EMC output filters

SineFormer
Please read Cautions and warnings and
Important notes at the end of this doc um ent.
Dimensional drawings
B84143V0011R127 ... B84143V0095R127 (11 ... 95 A)
Dimensions (mm)
Filter
B84143... abcdef hgk
V0011R127 120 100 335 280 260 700 160 6.6 14
V0016R127 120 100 375 320 300 900 190 6.6 16
V0033R127 150 120 470 380 360 900 240 6.6 20
V0066R127 210 160 650 530 500 1500 280 8.6 30
V0095R127 250 200 780 650 620 1600 360 11 43
Filter l m r Terminal blocks Threaded bolt Q
B84143... mm2Nm PE Nm mm2
V0011R127 −− 4 0.6 ... 0.8 M5×9.5 2±0.1 2.5
V0016R127 −− 6 1.5 ... 1.8 M5×9.5 2±0.1 4
V0033R127 −−10 1.5 ... 1.8 M5×12.5 2±0.1 6
V0066R127 545 122 165 25 4 ... 4.5 M6×16.5 3±0.15 16
V0095R127 665 163 200 50 6 ... 8 M6×15.5 3±0.15 35
SSB2259-8-E
Q (Cross section of the wire end)
PE
Terminal blocks
øk
r
12
ø25
ø45
mh
g
f
b
a
e
dc
l
only for
66-A and
95-A filters
Ring bolt
607/07
3-li ne f ilters
Sine-wave EMC output filters
SineFormer B84143V*R127
Please read Cautions and warnings and
Important notes at the end of this doc um ent.
B84143V0180R127 (180 A)
SSB2261-J-E
375
4.5 60193
PE M8 x 30
Tightening torque 6±0.3 Nm
Terminal blocks 150 mm
Tightening torque 12 ... 15 Nm
Cable clamp for cable ø55
Shielded cable 70 mm
2
15 880
2700+10
240
310
30 800 65
910 1130
11
(4 x)
140
220
2
(like DIN 46228)
Wire end ferrule
A70-25 (4x)
707/07
3-line filters B84143V*R 127
Sine-wave EMC output filters

SineFormer
Please read Cautions and warnings and
Important notes at the end of this doc um ent.
B84143V0320R127 (320 A)
SSB2262-S-E
(471.5)
200
2 x 65 = 130
98
12 Cable gland MS-SC 36
(232)
PE M12 x 19.5
Tightening torque 15.5±1.5 Nm
ø25
ø45
163
200 2 x 65 = 130
(358.5)
424.5
3
446
ø12
(10 x)
660
71.5 910
953
405±1 405±1
980±1
1010
2 x 65 = 130
300±0.5
470±1
500
2 x 65 = 130 320
443
Tightening torque 10±1 Nm
PE M10 x 32.5
Tightening torque 10±1 Nm
PE M10 x 36
DIN 580-M10
Ring bolt
Converter
Motor
807/07
3-li ne f ilters
Sine-wave EMC output filters
SineFormer B84143V*R127
Please read Cautions and warnings and
Important notes at the end of this doc um ent.
Cautions and warnings
Please note the advices in our data book “EMC Filters” (latest edition). Attention should be paid
to the chapter “General safety notes”.
It shall be ensure d that only qualifi ed person s (elec tricit y spec iali sts) are enga ged on wo rk such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. SineFormer contain components th at store an electric charge. Danger-
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the SineFormer is installed
and the last to be disconnected. Depending on the magnitude of the leakage currents, the par-
ticular specifications for making the protective-earth connection must be observed.
Impermissible overloading of the SineFormer, such as with circuits able to cause resonances,
impermissible voltages at higher frequencies etc. can lead to bodily injury and death as well as
cause substantial material damages (e.g. destruction of the filter housing).
SineFormer must be protected in the application against impermissible exceeding of the rated
currents by overcurrent protective.
In case of leakage currents >3.5 mA you shall mount the PE conductor stationary with the re-
quired cross section before beginning of operation and save it against disconnecting. For leak-
age currents IL1) <10 mA the PE conductor must have a KU value2) of 4.5; for leakage currents
IL 10 mA the PE conductor must have a KU value of 6.
The information, specifications and values contained in this data sheet are based on our know-
lege of typical requirements that are often placed on SineFormer. It is incumbent on the customer
to check and decide whether this SineFormer is suitable for use in a particular application.
In particular the values with regard to “temperature” and “noise” have to be observed.
1) IL = leak age cur ren t
2) The KU value (symbol KU) is a cla ssi fica tion parame ter of sa fety-re ferre d fail ur e type s design ed t o ensur e prote c-
tion against hazardous body currents and excessive heating.
A value of KU = 4.5 with respect to interruptions is attained:
with a permanently connected protective earth circuit 1.5 mm2
with a protective earth circuit 2.5 mm2 connec ted vi a shro ud co nnec tor s (IEC 6030 9-2).
KU = 6 with respect to interruptions is achieved for fixed-connection lines 10 mm2 where the type of connection
and line layout correspond to the requirements for PEN conductors as specified in relevant standards.
907/07
Important no tes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. Thes e state ments are based on our knowledge of typica l requi re-
ments that are oft en placed on our produc ts in t he areas of applicati on concerne d. We neverth e-
less expressly point out that such statements cannot be regarded as binding statements
about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with
them than the cu stomers themselves. For these reasons , it is always ultimate ly incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic compone nts
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications re-
quiring a very high level of operational safety an d especially in customer applications in which the
malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suit-
able design of the custo mer applic ation or oth er action t aken by the custom er (e.g. ins tallation o f
protective circuitry or redundancy) that no injury or damage is sustained by third parties in the
event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to sa tisfy certain technical req uirements, some of the products described in this pub-
lication may contain substances subject to restrictions in certain jurisdictions (e.g. be-
cause they are classed as “hazardous”). Useful information on this will be found in our Material
Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed
questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We a lso reserve the right to discontinue production and delivery of products. Consequent-
ly, we cannot guarantee that all products named in this publication will always be available.
The aforementioned does not apply in t he case of individual agreements deviati ng from the fore-
going for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu -X, CeraDiode, CSSP, MiniBlue, MKK, MLSC, MotorCap,
PCC, PhaseCap, PhaseMod, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SIMID,
SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are trademarks registered or pend-
ing in Europe and in other countries. Further in formation will be found on the Internet at www.ep-
cos.com/trademarks.