VOLUME 1
Fuse terminal blocks with a width of 6.2 mm/0.244 in
can be assembled adjacent to each other.
At the end of an assembly, if there is no adjacent fuse
or disconnect terminal block, an end plate for fuse
terminal blocks must be used.
When selecting miniature metric fuses, the maximum
power loss listed below should not be exceeded. The
power loss is determined according to IEC or EN
60947-7-3/VDE 0611-6 at 23°C. The temperature
rise of the terminal blocks must be checked according
to their application and mounting. Higher ambient tem-
peratures represent an additional impact on miniature
metric fuses. Therefore, in such applications the rated
current must be reduced if necessary.
More details from the manufacturer.
Appropriate marker systems:
WMB/Marker Strips/WMB Inline (see Full Line Catalog W4, Volume 1, Section 14)
0.25 — 2.5 (4) mm2
AWG 22 — 12
250 V/6 kV/3 ➊
6.3 A ➋
Terminal block width 6.2 mm / 0.244 in
L 10 — 12 mm / 0.43 in
0.25 — 2.5 (4) mm2
AWG 22 — 12
250 V/6 kV/3 ➊
6.3 A ➋
Terminal block width 6.2 mm / 0.244 in
L 10 — 12 mm / 0.43 in
4-conductor fuse terminal block with end plate,
without blown fuse indication
gray 2002-1811 50
4-conductor fuse terminal blocks with end plate,
with blown fuse indication by LED
gray 12 — 30 V ≃
➌
2002-1811/1000-541
50
gray 30 — 65 V ≃
➌
2002-1811/1000-542
50
gray 110 — 250 V ≃
2002-1811/1000-836
50
Item no. Pack. unit Item no. Pack. unit
End plate for fuse terminal blocks, 2 mm/0.079 in thick
gray 2002-991 100 (4x25)
orange 2002-992 100 (4x25)
End plate for fuse terminal blocks, 2 mm/0.079 in thick
gray 2002-991 100 (4x25)
orange 2002-992 100 (4x25)
Protective warning marker and insulation stop
must be singularized.
Due to the 6.2 mm/0.244 in width of the
fuse terminal blocks with pivotable fuse holder,
2004 Series jumpers must be used.
Insulation stop, 5 pcs/strip 200 strips
light gray 2002-171 0.25-0.5 mm2
dark gray 2002-172 0.75-1 mm2
must be singularized
Protective warning marker, with high voltage symbol, black,
for 5 terminal blocks
yellow 2002-115 100 (4 x 25)
must be singularized
Push-in type jumper bars, light gray, insulated, IN 25 A
2-way 2004-402 200 (8 x 25)
3-way 2004-403 200 (8 x 25)
4-way 2004-404 200 (8 x 25)
5-way 2004-405 100 (4 x 25)
: :
10-way 2004-410 100 (4 x 25)
Push-in type jumper bars, light gray, insulated, IN 25 A
1 - 3 2004-433 200 (8 x 25)
1 - 4 2004-434 200 (8 x 25)
1 - 5 2004-435 100 (4 x 25)
: :
1 - 10 2004-440 100 (4 x 25)
Test plug, with cable 500 mm/1’7.7’’, Ø 2 mm/0.079 in Ø
red 210-136 50 (5 x 10)
Insulation stop, 5 pcs/strip 200 strips
light gray 2002-171 0.25-0.5 mm2
dark gray 2002-172 0.75-1 mm2
must be singularized
Protective warning marker, with high voltage symbol, black,
for 5 terminal blocks
yellow 2002-115 100 (4 x 25)
must be singularized
Push-in type jumper bars, light gray, insulated, IN 25 A
2-way 2004-402 200 (8 x 25)
3-way 2004-403 200 (8 x 25)
4-way 2004-404 200 (8 x 25)
5-way 2004-405 100 (4 x 25)
: :
10-way 2004-410 100 (4 x 25)
Push-in type jumper bars, light gray, insulated, IN 25 A
1 - 3 2004-433 200 (8 x 25)
1 - 4 2004-434 200 (8 x 25)
1 - 5 2004-435 100 (4 x 25)
: :
1 - 10 2004-440 100 (4 x 25)
Test plug, with cable 500 mm/1’7.7’’, Ø 2 mm/0.079 in Ø
red 210-136 50 (5 x 10)
Miniature metric fuses 5 x 20
Series
Item No.
Overload and
short circuit protection Short circuit
protection only
2002-1611
2002-1811
Individual
arrangement Group
arrangement
Individual
arrangement Group
arrangement
Fuse terminal blocks
1.6 W 1.6 W 2.5 W 2.5 W
2002-1811/....-....
2002-1611/....-.... 1.6 W 1.6 W 2.5 W 2.5 W
Application notes