JAC series(6-30A)
Three phase input type(1-stage filter)
JAC -30 -683 -O
Ordering information
1 Model Name
2 Rated Current
3 Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code Leakage Current
(Input 250/500V 60Hz)
Line to ground
capacitor
(nominal value)
103 0.5mA/1.0 mA max 10,000pF
223 1.0mA/2.0 mA max 22,000pF
683 2.5mA/5.0 mA max 68,000pF
*When the line to ground capacitor code is
different, the attenuation characteristic is
different.
*Please contact us about ultra high attenuation
type for EU (Wye type with neutral earth
system).
4 Option
D:DIN rail installation type
*
The dimensions change when the option is set.
Refer to External view.
H:Ultra high-attenuation type
1 2 3 4
Features of JAC series
Circuit Diagram Derating Curve
Compact and low profile , common mode EMI/EMC filters in 150kHz to 1MHz(1-
stage filter)
- Three Phase 500 VAC
- Push down type terminal block
R
Specifications
No. Items JAC-06-683 JAC-10-683 JAC-20-683 JAC-30-683
1Rated Voltage[V] AC Three Phase 500 (voltage range:528 max) 50/60Hz
2 Rated Current[A] 6 10 20 30
3 Test Voltage (Terminal-Mounting Plate) 2,500 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MW min at room temperature and humidity
5 Leakage current 250/500V 60Hz 2.5mA/5.0mA max
6 DC resistance 100mW max 45mW max 15mW max 8mW max
7 Safety agency approval temperatures -25 to +85C (Refer to Derating Curve)
8 Operating temperature -40 to +85C (Refer to Derating Curve)
9 Operating humidity 20 to 95%RH (Non condensing)
10 Storage temperature/humidity -40 to +85C/20 to 95%RH (Non condensing)
11 Vibration 10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact 196.1m/s2 (20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
14 Case size (without projection) 63X44X132 mm (WXHXD) (Option: -D refer to external view)
[2.48X1.73X5.20 inches] (WXHXD)
15 Weight 440g max
NE
1
2
3
LOAD
4
5
6
CY
CXCXCXCXCXCX
CY
CY : Line to ground
capacitor
CX : Line to line
capacitor
70 80 90-20 40 50 60
20
10
0
-40 -30
100
80
70
60
40
Ambient Temperature [ ]
Load Factor [%]
DIN rail installation type is optionThe terminal cover is retracted inside the unit
JAC-1