BCD20034-G Rev. AD, 11-May-10 Page 1 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Description
The FNP600/850/1000 power factor corrected (PFC) front ends provide (depending on model) either a 12 VDC or a 48 VDC
output for telecom, datacom, and other distributed power applications. Their small 1U by 2U size allows for configurations of
either height in hot-swap redundant systems while their internal fan and cooling design permits wide use with reliable operation.
Status is provided with front panel LEDs, logic signals, and via the I2C management interface bus. In addition, the I2C bus can
enable the power supply, control fan speed, and on the 12 VDC models it allows for adjusting the output voltage from 7 to 12
VDC. This powerful feature allows the same power supply to be used in various applications where bus voltages driving isolated
dc-dc converters and POL regulators may be different.
Also, the FNP850-12R is uniquely designed with airflow from the rear of the power supply to the front. This airflow direction
supports those critical applications where space limitations and/or higher ambient temperatures near the rear of the rack system,
prohibit the discharge of higher temperature airflow from regular front-to-rear cooled power supplies.
The FNP600/850/1000's meet international safety requirements and are CE marked to the Low Voltage Directive (LVD).
Features
· RoHS lead free solder and lead solder exempted
products are available
· High density front-ends 10.5 to 16.1 W/in3
· Universal input voltage range (90-264 VAC) with PFC
· 1U or 2U height configurations
· Droop current share with ORing FETs
· I2C interface status and control
· Standby voltage of 12 VDC @ 0.5 A
· Overtemperature, overload, and overvoltage protection
· Status LEDs: AC OK, DC OK, Overtemperature
· FNP850-12 model has airflow direction from
front-to-rear or from rear-to-front (-12R model)
· ON/OFF Enable switch - shuts OFF Vo1; Vaux and fan
are operational.
Applications
· Telecom
· Datacom
· Distributed power systems
600-to-5000-Watt
Front-End Power Solutions
I
2
C Management Software
: All FNP front-ends
can be controlled via Power-One's GUI-driven I2C
Management software and an I
2
C-to-USB
interface (P/N HZZ02002G). An I2C Programming
Manual describes the complete range of
parameters that can be programmed to these
front-ends. This manual is available by searching
on "FNP600" at www.power-one.com.
(600, 850, or 1000 Watts)
FNR
-
5 Power Shelf
FNR-5-48G Power Shelves provide up to 5000 watts in a 19" rack.
(See the Rack section for power shelf details.)
BCD20034-G Rev. AD, 11-May-10 Page 2 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Model Selection
Model
Nominal
Output
Voltage
(VDC) 1
Adjustment
Range (VDC)
Maximum
Output
Current
(Amps)
Line
Regulation
(%)
Load
Regulation
(%) 2
Ripple &
Noise
pk-pk % 3
Compatible
Shelf
FNP600-12 12
12 (Standby)
7 to 12
N/A
51
0.5
0.17
8
6
8
1
1
FNR-5-12
FNP850-12 12
12 (Standby)
7 to 12
N/A
73
0.5
0.17
8
6
8
1
1
FNR-5-12
FNP850-12R 4 12
12 (Standby)
7 to 12
N/A
73
0.5
0.17
8
6
8
1
1
FNR-5-12
FNP600-48 48
12 (Standby)
44 to 50.5
N/A
12.6
0.5
0.17
8
6
8
1
1
FNR-5-48
FNP1000-48 48
12 (Standby)
44 to 50.5
N/A
21
0.5
0.17
8
6
8
1
1
FNR-5-48
1 Models with 5V and 3.3V standby voltages are also available. (Contact factory.)
2 Primary 12V and 48V outputs have built-in droop regulation.
3 Maximum peak-to-peak noise expressed as a percentage of output voltage; 20 MHz bandwidth.
4 FNP850-12R model has airflow from rear to front.
Ordering Information
Options Suffixes to Add to Part Number
RoHS lead solder exemption No RoHS suffix character required.
RoHS compliant for all 6 substances Add "G" as the last character of the part number.
Input Specifications
Parameter Conditions/Description Min. Nom. Max. Units
AC Input Voltage Single-phase continuous input range. 90 264 VAC
Input Frequency AC input. 47 63 Hz
Hold-up Time After last AC line peak at full power. At 115 VAC. 201 ms
Input Current At full-rated load. At 90 VAC. 14 A rms
Inrush Surge Current Internally limited. Vin = 230 VAC. 25 ºC 34 A pk
Power Factor Per EN61000-3-2 0.97 W/VA
1 FNP1000-48 model has a hold-up time of 16 ms.
BCD20034-G Rev. AD, 11-May-10 Page 3 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Output Specifications
Parameter Conditions/Description Min. Nom. Max. Units
Efficiency: FNP600-48
FNP1000-48
FNP600-12
FNP850-12
Full rated load at 230 VAC input. 88
88
84
84
89.5
89.5
87
87
%
Minimum Load Minimum loading required to maintain regulation. 0 A
Output Power FNP1000
FNP850
FNP600
1006
856
600
W
Overshoot Output voltage overshoot at turn-on. 3 %
Transient Response Maximum recovery time to within 1% of initial set
point due to a 50% load change, 1A/µs.
12V or 48V output:
Standby output:
Maximum deviation: 12V or 48V output:
Standby output:
400
2
2
4
µs
ms
%
%
Turn-On Delay Time required for initial output voltage stabilization
after application of AC input..
1.5 Sec
Output Regulation See Model Selection table.
Protection
Parameter Conditions/Description Min. Nom. Max. Units
FNP600-12 &
FNP850-12
Latch-style overvoltage protection.
Output adjusted to 12V:
14.4
15
15.6
V
FNP600-12:
FNP850-12:
Latch-style overvoltage protection.
Output adjusted to 7V:
8.75
8.44
9.04
8.75
9.33
9.1
V
Overvoltage
Protection
FNP600-48 &
FNP1000-48
Latch-style overvoltage protection.
Output adjusted to 48V:
571
60
V
FNP600-12 Current limit.12V output:
12V Standby output:
54
0.55
56
0.75
61
1.0 A
FNP850-12 Current limit.12V output:
12V Standby output:
77
0.55
80
0.75
88
1.0 A
FNP600-48 Current limit.48V output:
12V Standby output:
13
0.75
14 16
1.75 A
Overcurrent
Protection
(Power supply
recovers when short
is removed.)
FNP1000-48 Current limit.48V output:
12V Standby output:
22
0.75
23 25
1.75 A
Short-Circuit
Protection
Power supply recovers when short is removed.
Overtemperature/
Fan Failure Warning
FNP 12V or 48V Vo1 supply output will shut down in the event of an overtemperature condition or blocked
fan rotor. Supply's fan and Vaux are active. Power supply will recover when OT condition is removed.
Amber OT LED will turn ON to indicate fault condition.
OT/Fan Fail is an open-collector signal with 20-mA pull-down. High signal indicates a normal operating
condition. Output will go low at least 100 ms before OT condition shuts down the power supply. Internally
pulled up to 5V with a 5.1 k resistor. Note. 2
1 FNP1000-48 overvoltage protection range is 56 V minimum and 60 V maximum.
2 A pull-up to 3.3V can be achieved by terminating the logic signal with a 10 k resistor to logic ground.
BCD20034-G Rev. AD, 11-May-10 Page 4 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Control and Monitoring
Parameter Conditions/Description Min. Nom. Max. Units
DC OK TTL open-collector signal with active
20-mA pull-down. Represents percent
of output voltage where signal is OK.
Below this voltage, a signal high
condition indicates an output which is
out of tolerance. Green DC OK LED on
front panel indicates normal operation.1
Internally pulled up to 5V with a 5.1 k
resistor. Note. 2
90 110 %
Input Power Fail Warning TTL open-collector signal with active
20-mA pull-down. High indicates an
input power fail. Power Fail Warning
will turn OFF green AC OK LED.
Represents the time after warning
signal before Vout drops to 95% due to
loss of input power.1 Internally pulled
up to 5V with a 5.1 k resistor. Note. 2
5 ms
Power Supply Present
Signal
Resistance of connection to logic
ground which allows user to determine
if power supply is present. 1
10
FNP600-12:
Main output only. Difference in current
between two supplies at >10% load
value.
5
FNP850-12: 7
FNP600-48: 2
Current Share
FNP1000-48: 2
A
Remote Sense
Total voltage compensation for cable
losses with respect to the main output.
0.5 V
Output Enable
Open circuit or logic high from ENA pin
to Vo1 RTN shuts OFF Vo1; Vaux and
fan are operational. Logic low (2 mA
sink capability) or jumper will turn ON
Vo1 within 500 ms. Open circuit
voltage on enable pin is 3.3 VDC.
Externally applied voltage to the enable
pin should NOT exceed 7 VDC. Signal
is referred to as Logic Return (LRTN).
1 Also available on I2C data line.
2 A pull-up to 3.3V can be achieved by terminating the logic signal with a 10 k resistor to logic ground.
I2C Bus Management Interface
Static Includes static information such as: part number and revision level, output rating, serial number, date code,
and manufacturing location.
Status
(Logic 1 or 0)
Power Supply OK.
AC Input OK.
DC Output OK.
Power Supply Seated.
Overtemperature.
Overcurrent.
Fan OK.
Real-Time Monitoring Output voltage (main output) 0.1V LSD.
Output current (main output) 0.1A LSD.
Time in service.
Control Signals Enable for main output.
Output voltage to: (0.01V resolution on 12V supplies;
0.05V resolution on all 48V supplies).
Fan speed level.
BCD20034-G Rev. AD, 11-May-10 Page 5 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Safety, Regulatory, and EMI Specifications
Parameter Conditions/Description Min. Nom. Max. Units
Agency Approvals UL60950-1 (UL), CSA C22.2 60950-1 (cUL), EN60950-1 (TUV), IEC60950-1 and CE (LVD)
Electromagnetic
Interference
FCC CFR title 47 Part 15
Sub-Part B, Conducted:
EN55022/CISPR 22. Radiated:
B
A
Class
Harmonics Per IEC61000-3-2. A Class
Voltage Fluctuation
and Flicker
Per IEC61000-3-3. Pass
ESD Susceptability Per EN61000-4-2, Level 4. Criterion B 8 . kV
Radiated
Susceptability
Per EN 61000-4-3, Level 3. Criterion A 10 . V/M
EFT/Burst Per EN 61000-4-4, Level 4. Criterion B ±4 . kV
Input Transient
Protection
Per EN 61000-4-5, Class 3. Criterion B Line-to-Line:
Line-to-Ground:
1
2
. kV
RF Conducted
Disturbances
Per EN 61000-4-6, Level 3. Criterion A 10 . V
Voltage Interruptions Per EN 61000-4-11, performance criterion B 30%.
Per EN 61000-4-11, performance criterion C 60%.
Per EN 61000-4-11, performance criterion C 95%.
10
100
5
. ms
ms
Sec
Voltage Sag Immunity Per SEMI F47-0999 > 100 VAC.
No output voltage interruption.
.
Leakage Current Per EN60950-1. At 240 VAC: 3.5 mA
Environmental Specifications
Parameter Conditions/Description Min. Nom. Max. Units
Altitude Operating.
Non-Operating.
10K
40K ASL ft
ASL ft
FNP600-12:
FNP850-12:
FNP600-48:
FNP1000-48:
Internal DC fan for cooling. At 100% load:
At 50% load:
0
0
50
70
ºC
Operating Temperature
FNP850-12R: Internal DC fan for cooling. At 100% load:
At 94% load:
At 50% load:
0
0
0
40
50
70
ºC
Storage Temperature -40 85 ºC
Temperature Coefficient 0 ºC to 70 ºC (after 15-minute warm-up). 0.02 %/ºC
Relative Humidity Non-condensing 95 %RH
Shock Operating: half-sine, 10 ms, 3-axis.
Non-Operating: half-sine, 10 ms, 3-axis.
+20
+40
Gpk
Gpk
Vibration Operating: swept sine 5-2000-5 Hz, 5-32
Hz, 0.02îDA, 32-2000 Hz.
Non-operating: random 10-2000 Hz.
1
6.15
Gpk
Grms
Reliability
Parameter Conditions/Description Min. Nom. Max. Units
MTBF (Calculated) MILHDBK 217F Ground Benign.
Demonstrated.
Useful Life.
100 000
250 000
10
hrs
hrs
yrs
BCD20034-G Rev. AD, 11-May-10 Page 6 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Mechanical Drawings
BCD20034-G Rev. AD, 11-May-10 Page 7 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
BCD20034-G Rev. AD, 11-May-10 Page 8 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Connector Information
Power Supply:
Input - IEC 320 input (Male) standard line cord connection
Output - P/N FCI 51732-020LF
Mating Connections:
Input - IEC 320 output (Socket) Standard line cord (15A)
Output - P/N: FCI 51742-10602000AALF (Backplane)
P/N: FCI 51762-10602000AALF (Right Angle)
Input IEC Connector
Input Location
Chassis (Safety) Ground Ground
Line 1 (Line) L
Line 2 (Neutral) N
BCD20034-G Rev. AD, 11-May-10 Page 9 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Output Pin Assignments
Signal Pin Location Ground Reference Note
Over Temperature / Fan Fail U1 Logic Ground (LRTN) Open collector 20mA,int.pull-up 5.11kΩ to 5V DC
AC Power Fail Warning U2 Logic Ground (LRTN) Open collector 20mA,int.pull-up 5.11kΩ to 5V DC
Power Supply Present U3 Logic Ground (LRTN) 10Ω resistance int. connected to LRTN
Output Voltage Fault U4 Logic Ground (LRTN) Open collector 20mA,int.pull-up 5.11kΩ to 5V DC
Internal Ground U5 Internal Ground (SRTN) 2
ADDR0, I2C Address Bus T1 Internal Ground (SRTN)
ADDR1, I2C Address Bus T2 Internal Ground (SRTN)
ADDR2, I2C Address Bus T3 Internal Ground (SRTN)
ADDR3, I2C Address Bus T4 Internal Ground (SRTN)
ADDR4, I2C Address Bus T5 Internal Ground (SRTN)
DATA, I2C Data Line S1 Logic Ground (LRTN)
CLOCK, I2C Clock Line S2 Logic Ground (LRTN)
Auxiliary Power +12V S3 Aux Ground
Auxiliary Power Ground S4 Aux Ground
Logic Ground S5 Logic Ground (LRTN)
Output Enable 1 R1 Logic Ground (LRTN) Open circuit or High” to LRTN shuts OFF Vo1
Vsense+ R2 Vsense-
Vsense- R3 Vsense-
Output Margin R4 Internal Ground (SRTN) OPTIONAL; External resistance needed to adjust
Vo1 lower than it is set originally
Active Current share R5 Internal Ground (SRTN) OPTIONAL
Vout+ P1, P2, P3 Vsense-
Vout- P4, P5, P6 Vsense-
1 Short pin length
2 SRTN (Internal Ground) is internally connected to Vout-
BCD20034-G Rev. AD, 11-May-10 Page 10 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Racks
(FNR-5-12G and FNR-5-48G Power Shelves)
Each rack (power shelf) is 1U high with backplane and designed for up to five front-end models in parallel or in n+1 operation.
Each power shelf has:
· Output terminals with two M4-screws on each power tab.
· Two fast-on contacts for system earthing.
· Address coding over five pole DIP switch on each unit, 37-pin D-Sub connector with I
2
C-lines, monitoring signals and
support functions.
· Provides a start-up synchronization circuit and EMV filters.
FNR-5-12G and FNR-5-48G Power Shelf Front View
Overall Mechanical Dimensions (FNR-5-12G and FNR-5-48G Power Shelves)
FNR-5-12 & FNR-5-48 Mechanical Data (W, H, D) 17.68” (449 mm) x 1.72” (43.6 mm) x 13.05 (331.5 mm)
BCD20034-G Rev. AD, 11-May-10 Page 11 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Output Connector Descriptions (FNR-5-12G & FNR-5-48G)
Location Description
A 5-Bit DIP switch for I2C addressing of PSU 1
B 5-Bit DIP switch for I2C addressing of PSU 2
C 37-pin SUB-D connector, controlling and auxiliary power (output 2)
D 5-Bit DIP switch for I2C addressing of PSU 3
E Output 1 minus
F Output 1 plus
G 5-Bit DIP switch for I2C addressing of PSU 4
H Earth connection
I 5-Bit DIP switch for I2C addressing of PSU 5
Mechanical Data (FNR-5-12G and FNR-5-48G Power Shelves)
A
B
C
D
E
F
G
H
I
BCD20034-G Rev. AD, 11-May-10 Page 12 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
SUB-D Output Connector Pinout and Signal Specification
Output Connector
Description
Pin
Location
Type Low level
High level
V max
I max
Overtemperature /
Fan Fail PSU1 1 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
Power Supply Present
PSU 1 2 Resistor 10 connected to logic GND Open
Pull up
10 V
10 mA
Power Supply Present
PSU 2 3 Resistor 10 connected to logic GND Open
Pull up
10 V
10 mA
Open 4
Overtemperature /
Fan Fail PSU 3 5 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
AC Fail /
Power down warning
PSU 3
6 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
Power Supply Present
PSU 3 7 Resistor 10 connected to logic GND Open
Pull up
10 V
10 mA
DC Fail /
Output voltage fault
PSU 3
8 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
Overtemperature /
Fan Fail PSU 2 9 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
NC 10, 11
Output inhibit
PSU 1-5 12
Active low (DC-DC stage off when pin is open or on
high potential)
Referenced to logic GND
<0.8 V
>2.0 V
10 V
3.5 mA
V sense + 13 Open or connected to Vo1+ at the load
Internally (PSU) connected to Vo1+ over 100 Ω
dU < 3 Vpp
30 mA
V sense - 14 Open or connected to Vo1- at the load
Internally (PSU) connected to Vo1- over 100 Ω
dU < 3 Vpp
30 mA
NC 15
AC Fail/
Power-down warning
PSU 4
16 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
DC Fail/
Output voltage fault
PSU 4
17 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
AC Fail/
Power-down warning
PSU 5
18 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
DC Fail/
Output voltage fault
PSU 5
19 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
AC Fail/
Power-down warning
PSU 1
20 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
DC Fail/
Output voltage fault
PSU 1
21 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
BCD20034-G Rev. AD, 11-May-10 Page 13 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
SUB-D Output Connector Pinout and Signal Specification (continued)
Output Connector
Description
Pin
Location
Type Low level
High level
V max
I max
AC Fail/
Power-down warning
PSU 2
22 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
DC Fail/
Output voltage fault
PSU 2
23 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
DATA, I2C data line 24 I2C compatible signal
referenced to logic GND
5 V or 3.3 V
logic
-
CLOCK, I2C clock line
25 I2C compatible signal
referenced to logic GND
5 V or 3.3 V
logic
-
Auxiliary power +12 V
(Output 2) 26 Vo2+ Aux output, insulated from main output - -
Auxiliary power
ground
(Output 2)
27 Vo2- Aux output, insulated from main output
- -
Logic Gnd 28
Auxiliary GND, Need to be external connected Vo2-,.
Wire separately from auxiliary and main output GND
to minimize noise and avoid voltage drops on signal-
and I2C return. Leave open if not used.
- -
Output margin PSU 1 29 Open or connected to V sense-
V sense- (+8 % Vo1) or V sense+ (-8 % Vo1)
-
-
60V
-
Output margin PSU 2 30 Open or connected to V sense-
V sense- (+8 % Vo1) or V sense+ (-8 % Vo1)
-
-
60V
-
Output margin PSU 3 31 Open or connected to V sense-
V sense- (+8 % Vo1) or V sense+ (-8 % Vo1)
-
-
60V
-
Output margin PSU 4 32 Open or connected to V sense-
V sense- (+8 % Vo1) or V sense+ (-8 % Vo1)
-
-
60V
-
Output margin PSU 5 33 Open or connected to V sense-
V sense- (+8 % Vo1) or V sense+ (-8 % Vo1)
-
-
60V
-
Overtemperature /
Fan Fail PSU 4 34 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
Power Supply Present
PSU 4 35 Resistor 10 connected to logic GND Open
Pull up
10 V
10 mA
Overtemperature /
Fan Fail PSU 5 36 OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
<0.4 V @ 20
mA
Pull up
15 V
20 mA
Power Supply Present
PSU 5 37 Resistor 10 connected to logic GND Open
Pull up
10 V
10 mA
BCD20034-G Rev. AD, 11-May-10 Page 14 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
Accessories:
Center Angular Brackets are set in the middle for shelf mounting:
Center Angular Bracket sets can be ordered: Power-One part no.: HZZ01222
Note: Each Center Angular Bracket set contains 2 brackets and 8 screws.
BCD20034-G Rev. AD, 11-May-10 Page 15 of 15 www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
I2C to USB Interface Demonstration Kit HZZ02002G:
An I2C to USB Interface Demonstration Kit can be ordered: Power-One part no.: HZZ02002G
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
I
2
C <to>USB
Interface
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Bel Power Solutions:
FNP600-12G FNP600-48G FNP1000-48G FNR-5-48G FNR-5-12G