338 1-717-217-2299 www.lumberg-automationusa.com
DIN Valve Connectors - VAD 1A/1B Series
VAD 1A / VAD 1B VAD 1A VAD 1B
VAD 1A
VAD 1B
Actuator cordset, single-ended, valve connector
according to DIN EN 175301-803, form A,
with LED function indicator, varistor voltage
protection, connected protective earth
VAD 1A-1-3: 24 V AC
VAD 1A-2-3: 110 V AC
VAD 1A-3-3: 230 V AC
VAD 1A
VAD 1B
Actuator cordset, single-ended, valve connector
according to DIN EN 175301-803, form A, with
LED function indicator, suppressor diode voltage
protection, connected protective earth
Pin Assignments Wiring Diagram
1 = brown
2 = blue
= green/yellow
339www.lumberg-automationusa.com 1-717-217-2299
Be Certain with Belden
DIN Valve Connectors - VAD 1A/1B Series
VAD 1A-X-3-XXX and VAD 1B-1-3-XXX
Technical Data
Environmental
Degree of protection IP 67
Operating temperature range -25°C / +80°C
Mechanical
Housing / Molded body TPU, self-extinguishing
Insert PBT
Contact CuZn, nickel-plated and tin-plated
Electrical
Contact resistance 5 mΩ
Nominal current at 40°C 4 A
Nominal voltage VAD 1A-1-3: 24 V
VAD 1A-2-3: 110 V
VAD 1A-3-3: 230 V
Rated voltage 32 V
Insulation resistance > 109 Ω
Pollution degree 3
Varistor data (VAD 1A – 24 V AC)
Nominal voltage 47 V at 0.1 mA
Typ. limiting voltage 110 V at 5 A
Max. pulse energy
(standard impulse 10/1000us) 0.9 Ws
Max. continuous power loss 0.01 W
Supressor diode data (VAD 1B)
Nominal voltage 47 V at 1 mA
Max. limiting voltage 68 V at 8.9 A
Typ. limiting voltage 60 V at 5 A
Max. pulse current
(pulse shape 10/1000us) 8.9 A
Max. pulse power
(pulse shape 10/1000us) 600 W
Max. continuous power loss 0.5 W
Accessories (incl.) Attachable label
Screw (fitted)
Standard lengths: 2 M / 5 M / 10 M
Other cable lengths or cable specifications available upon request.
Part Number Poles Outer Jacket Characteristics
VAD 1A-1-3-212/... M VAD 1B-1-3-212/... M PVC
VAD 1A-2-3-212/... M PVC
VAD 1A-3-3-212/... M 2 + PVC
VAD 1A-1-3-226/... M VAD 1B-1-3-226/... M PUR halogen free
VAD 1A-2-3-226/... M PUR halogen free
VAD 1A-3-3-226/... M PUR halogen free
The application of these products in harsh environments should always be checked before use.