MODEL FCA50F-24
MAX OUTPUT WATTAGE[W] 50(Peak 160)
DC OUTPUT 24V 2.1(Peak 6.7)A
SPECIFICATIONS
MODEL FCA50F-24
INPUT
VOLTAGE[V] AC187 - 528 1for DC265 - 746
CURRENT[A]
ACIN 240V
0.55typ
ACIN 480V
0.30typ
FREQUENCY[Hz] 50/60 (47-63
)
EFFICIENCY[%]
ACIN 240V
82typ
ACIN 480V
78typ
INRUSH CURRENT[A]
ACIN 240V
25typ (At cold start)(
At Room Temperature)
ACIN 480V
50typ (At cold start)(
At Room Temperature)
LEAKAGE CURRENT[mA] 0.75max (60Hz,According to IEC60950)
OUTPUT
VOLTAGE[V] 24
CURRENT[A]
*1
2.1 (Peak 6.7)
LINE REGULATION[mV] 96max
LOAD REGULATION[mV]
0 - 2.1A
150max
0 - 6.7A
480max
RIPPLE[mVp-p]
0to+50
C
*2
240max
-10-0
C
*2
320max
RIPPLE NOISE[mVp-p]
0to+50
C
*2
680max
-10-0
C
*2
720max
TEMPERATURE REGULATION[mV]
-10 to +50C
600max
DRIFT[mV]
*5
100max
START-UP TIME[ms] 800max (ACIN 240V,Io=100%)
HOLD-UP TIME[ms] 10typ (ACIN 240V,Io=100%)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
21.6 - 26.4
PROTECTION
CIRCUIT AND
OTHERS
OVERCURRENT PROTECTION
Works over 105% of peak current and recovers automatically
OVERVOLTAGE PROTECTION
Works at 115 - 140% of rating
OPERATING INDICATION LED (Green)
ISOLATION
INPUT-OUTPUT AC3,000V 1minute,Cutoff current = 10mA,DC500V 50MWmin (At Room Temperature)
INPUT-FG AC2,000V 1minute,Cutoff current = 10mA,DC500V 50MWmin (At Room Temperature)
OUTPUT-FG AC500V 1minute,Cutoff current = 100mA,DC500V 50MWmin (At Room Temperature)
ENVIRONMENT
OPERATING TEMP.,HUMID.AND ALTITUDE
-10 to +70C,20 - 90%RH (Non condensing)(
Refer to DERATING CURVE), 3,000m (10,000feet)max
STORAGE TEMP.,HUMID.AND ALTITUDE
-20 to +75C,20 - 90%RH (Non condensing), 9,000m (30,000feet)max
VIBRATION
*3
10 - 55Hz,19.6m/s2(2G), 3minutes period,60minutes each along X,Y and Z axis
IMPACT
*3
196.1m/s2(20G), 11ms,once each X,Y and Z axis
SAFETY AND
NOISE
REGULATIONS
AGENCY APPROVALS UL60950-1,C-UL,EN60950-1
CONDUCTED NOISE Complies with FCC-A,CISPR11-A,EN55011-A
OTHERS CASE SIZE/WEIGHT
*4
50X125X124mm (WXHXD)/ 640g max
COOLING METHOD Convection
*1Peak current for 150ms in a 30seconds period is acceptable.
*2In case of rated input/output(ACIN240-480v/2.1A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used.
*3Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual).
*4Depth of power supply is 132mm with DIN rail attachment.
*5Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output.
*6Please contact us about safety approvals for the model with option.
FCA50F
AC-DC Power Supplies Enclosed type
FCA 50 F -24 -O
Ordering information
1Series name
2Output wattage
3Universal input
4Output voltage
5Optional *6
N1
:with DIN rail attach-
ment
R
12345
FCA
FCA-2