 5/3
2CDC110004C0207
5
Analog signal converters
CC range
Serial data converters
ILPH range
Content
Analogue Signal Converters CC-range
Benefi ts and advantages .................................................................................................... 5/ 4
Application ......................................................................................................................... 5/ 5
Approvals and marks ......................................................................................................... 5/ 5
Ordering details
Analog standard signal converters
CC-E/STD, CC-E x/x ................................................................................................. 5/ 6
CC-E I/I ...................................................................................................................... 5/ 7
CC-U/STD ................................................................................................................. 5/ 8
CC-U/STDR ............................................................................................................... 5/ 9
Temperature signal converters for RTD sensors
CC-E/RTD .................................................................................................................. 5/10
CC-U/RTD ................................................................................................................. 5/11
CC-U/RTDR ............................................................................................................... 5/12
Temperature signal converters for thermocouples
CC-E/TC .................................................................................................................... 5/13
CC-U/TC .................................................................................................................... 5/14
CC-U/TCR ................................................................................................................. 5/15
Measuring converters for currents (E/I) and (U/I) and voltages (U/V)
CC-E/I ........................................................................................................................ 5/16
CC-E IAC / ILPO.......................................................................................................... 5/17
CC-U/I ....................................................................................................................... 5/18
CC-U/V ...................................................................................................................... 5/19
Accessories .................................................................................................................. 5/20
Technical data
CC-E/STD, CC-E x/x, CC-E/RTD, CC-E/TC ................................................................ 5/21
CC-E I/I ........................................................................................................................ 5/22
CC-U/STD, CC-U/RTD, CC-U/TC ............................................................................... 5/23
CC-U/STDR, CC-U/RTDR, CC-U/TCR ........................................................................ 5/24
CC-E/I, CC-E IAC / ILPO ............................................................................................... 5/25
CC-U/I, CC-U/V ........................................................................................................... 5/26
Technical diagrams ............................................................................................................. 5/27
Connection diagramms ...................................................................................................... 5/27
Dimensional drawings ........................................................................................................ 5/27
Serial data converters ILPH range
Uses ................................................................................................................................... 5/30
Selection table .................................................................................................................... 5/31
Ordering details .................................................................................................................. 5/32
Technical data .................................................................................................................... 5/32
5/4 
2CDC110004C0207
5
2CDC 285 001 F0b05
2CDC 283 016 F0b03
Analog signal converters
CC range
Benefi ts and advantages
CC-E range
Universally confi gurable devices and single-function devices
Adjustment and operating elements on the front side
Safe operation by electrical 3-way isolation
Unambiguous and clear connecting terminal markings
Conversion, measurement and separation of
standard signals (0-5 V, 0-10 V, 0-20 mA, 4-20 mA)
temperature signals of RTD sensors (PT 100)
thermocouple signals (types J and K)
current measurement signals (0-5 A, 0-20 A AC/DC)
Characteristics of single-function devices
No adjustment or balancing necessary.
Characteristics of universal devices
The required input and output ranges can be confi gured by means
of directly accessible DIP switches positioned on the side
Gain adjustment of ± 5 % by means of an adjustment
potentiometer on the front-side
Offset adjustment of ±5 % by means of adjustment
potentiometers on the front-side
Product range for analog signal processing
CC-U range
8 different standard signal outputs on one device
Input and output side universally confi gurable
Also available with 2 threshold relay outputs
Adjustment and operating elements on the front side
Safe operation by electrical 3-way isolation
Plug-in connecting terminals, unambiguously and clearly
marked
Conversion, measurement and separation of
standard signals
signals of RTD sensors (PT10, PT100, PT1000)
thermocouple signals
RMS values of currents and voltages
Characteristics
The required input and output ranges can be confi gured for all
devices by means of directly accessible DIP switches positioned
on the side.
Due to the wide input range of the gain and offset stages all input
signals between the minimum and the maximum input value can be
universally converted to all common output signals.
Devices for DC or AC (50/60 Hz) supply available.
 5/5
2CDC110004C0207
5
Analog signal converters
CC range
Application, Approvals and marks
Nearly every process includes a control system that receives data
by means of analog signals and then evaluates the data and sets the
respective parameters correspondingly.
When transmitting analog signals numerous problems may arise which
can disturb or even block an ideal behavior of the process.
Below we have listed some processing problems together with the
respective solutions to solve these problems:
Signal conversion
Sometimes the available signals cannot be processed by the controller
or the actuator. In this case, signal converters are required to convert
the input signal (or different input signals) to the desired output signal.
Signal amplifi cation
If long lines or high burdens have to be operated, it may be necessary
to amplify the signal. CC analog signal converters require only low in-
put power and provide high output power.
Thus, there are no restrictions for the converter's position on the line,
i.e. it can be used
for signal refreshing at the end of the line
(low input power)
or for signal amplifi cationat the beginning of the line
(high output power).
Signal fi ltering
Particularly on long lines or in rough industrial environments the signals
are exposed to high electromagnetic interferences. The frequency of
the coupled interference signals may be in the range of the common
mains frequency (50 Hz) or even much higher (in case of frequency
converters). According to the specifi c requirements, analog signal
converters are available which provide reliable suppression of those
interferences by means of an input low-pass fi lter.
Applications for analog signal processing and
correct solution using CC-E and CC-U
converters
Signal separation
Protection against overvoltage
The increased use of micro-electronics make controls much more
sensitive against overvoltages, resulting from lightning discharges
or switching processes. Suppression diodes are incorporated in
the input of the CC analog signal converters which enable the
converters to arrest overvoltages with low energy level (resulting
from switching processes) by themselves. The products further-
more provide electrical isolation between input, output and sup-
ply circuit for protection of the controller connected to the output.
Protection against ground loops
If components are used which refer to ground, the measuring
signals can be falsifi ed by a so-called ground loop. In this case,
certain parts of the signal are transmitted via earth and not via the
analog transmission line, thus causing incorrect evaluation of the
signal. The electrical isolation between the input and the output
disconnects these ground loops and thus enables correct signal
transmission.
existing
existing for some devices
pending
Approvals
CC-E/STD
CC-E I/I
CC-U/STD
CC-U/STDR
CC-E/RTD
CC-U/RTD
CC-U/RTDR
CC-E/TC
CC-U/TC
CC-U/TCR
CC-E/I
CC-E IAC/ILPO
CC-U/I
CC-U/V
AUL 508, CAN/CSA C22.2 No.14 쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍
AUL 1604 (Class I, Div 2, hazardous locations),
CAN/CSA C22.2 No.213 왖쐍 왖쐍
KCB scheme 쐍쐍쐍
ECCC 쐍쐍쐍
Marks
aCE 쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍
bC-Tick 쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍쐍
0-10 V0-10 V
100 m 0-20 mA 100 m 4-20 mA
2CDC 282 013 F0206
Controller
e.g. AC500
Measuring sensor
Actuator
1.
Analog signal converter
(e.g. CC-E or CC-U)
2.
Analog signal converter
(e.g. CC-E or CC-U)
5/6 
2CDC110004C0207
5
CC-E/STD
2CDC 281 001 F0t03
CC-E V/V
2CDC 281 014 F0t04
Analog standard signal converters
CC-E/STD, CC-E x/x
Ordering details
CC-E/STD analog signal converter with 3-way electrical isolation
2 universally confi gurable devices (type CC-E/STD)
2x10 single-function devices
"Plug and Work", no adjustment of single-function devices required
U: green LED -
supply voltage
Gain adjustment
Offset adjustment
DIP switch for input and
output confi guration
(only available on
universal devices)
Supply voltage: 24 V DC
universal
CC-E/STD
0-5 V, 0-10 V
0-20 mA, 4-20 mA
0-5 V, 0-10 V
0-20 mA, 4-20 mA 1SVR 011 700 R00001) 1
single-function
CC-E V/V
CC-E V/I
CC-E V/I
0-10 V
0-10 V
0-20 mA
4-20 mA
1SVR 011 710 R2100
1SVR 011 711 R1600
1SVR 011 712 R1700
1
1
1
CC-E I/V
CC-E I/I
CC-E I/I
0-20 mA
0-10 V
0-20 mA
4-20 mA
1SVR 011 713 R1000
1SVR 011 714 R1100
1SVR 011 715 R1200
1
1
1
CC-E I/V
CC-E I/I
CC-E I/I
4-20 mA
0-10 V
0-20 mA
4-20 mA
1SVR 011 716 R1300
1SVR 011 717 R1400
1SVR 011 718 R2500
1
1
1
CC-E V/V -10...+10 V -10...+10 V 1SVR 011 719 R2600 1
Supply voltage: 110-240 V AC
universal
CC-E/STD
0-5 V, 0-10 V
0-20 mA, 4-20 mA
0-5 V, 0-10 V
0-20 mA, 4-20 mA 1SVR 011 705 R2100 1
single-function
CC-E V/V
CC-E V/I
CC-E V/I
0-10 V
0-10 V
0-20 mA
4-20 mA
1SVR 011 720 R2300
1SVR 011 721 R1000
1SVR 011 722 R1100
1
1
1
CC-E I/V
CC-E I/I
CC-E I/I
0-20 mA
0-10 V
0-20 mA
4-20 mA
1SVR 011 723 R1200
1SVR 011 724 R1300
1SVR 011 725 R1400
1
1
1
CC-E I/V
CC-E I/I
CC-E I/I
4-20 mA
0-10 V
0-20 mA
4-20 mA
1SVR 011 726 R1500
1SVR 011 727 R1600
1SVR 011 728 R2700
1
1
1
CC-E V/V -10...+10 V -10...+10 V 1SVR 011 729 R2000 1
1)
B 1604 Class I, Div.2
(universal device)
Type Input signal Output signal Order code Pack. unit
piece
Price
1 piece
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
2CDC 282 006 F0206
Burden
R 1.0 k
Burden
R 500
supply
812 43 567
0...5 V
0...10 V
0...20 mA
4...20 mA
0...5 V
0...10 V
0...20 mA
4...20 mA
0...5 V
0...10 V
0...20 mA
4...20 mA
0...5 V
0...10 V
0...20 mA
4...20 mA
0...5 V
0...10 V
0...20 mA
4...20 mA
2CDC 282 001 F0204
Input Output Switch
2CDC 282 002 F0204
ON
Legend
OFF
DIP switch settings (universal devices)Wiring instruction
 5/7
2CDC110004C0207
5
CC-E I/I-1
2CDC 281 001 F0b06
CC-E I/I-2
2CDC 281 041 F0b03
CC-E I/I-2
CC-E I/I-1
Loop-powered current/current isolator without external power supply for analog
current signals of 0-20 mA and 4-20 mA
Electrical isolation between input and output
Very low internal voltage drop 2.5 V
Available with one or two independent channels
Width only 18 mm (1 and 2 channels)
Current/current isolator
CC-E I/I-1 and CC-E I/I-2
Ordering details
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
100   RL 500
UL
C
D
F
E
IN
IN
OUT
OUT
2CDC 282 003 F0205
Channel 1
input
0-20 mA or
4-20 mA
Channel 1
output
0-20 mA or
4-20 mA
100   RL 500
100   RL 500
UL
UL
C
D
F
E
A
B
H
G
IN
IN
IN
IN
OUT
OUT
OUT
OUT
2CDC 282 004 F0205
Channel 1
input
0-20 mA or
4-20 mA
Channel 2
input
0-20 mA or
4-20 mA
Channel 1
output
0-20 mA or
4-20 mA
Chanel 2
output
0-20 mA or
4-20 mA
Wiring instructions
Type Input signal Output signal Order code Pack. unit
piece
Price
1 piece
1 channel
CC-E I/I-1 0-20 mA, 4-20 mA 0-20 mA, 4-20 mA 1SVR 010 200 R1600 1
2 channel
CC-E I/I-2 0-20 mA, 4-20 mA 0-20 mA, 4-20 mA 1SVR 010 201 R0300 1
5/8 
2CDC110004C0207
5
CC-U/STD
2CDC 281 002 F0t03
Analog standard signal converter
CC-U/STD
Ordering details
Plug-in terminals
Gain: Coarse adjustment
Gain: Fine adjustment
Offset adjustment
U: green LED -
supply voltage
Marker label
CC-U/STD universal signal converter with 3-way electrical isolation
More than 120 confi gurations possible
Confi gurable output signal response on input voltage signal interruption (low fail safe / high fail safe)
Adjustment and operating elements on the front
Short-circuit proof signal outputs
Plug-in connecting terminals for inputs, outputs and supply
Very fast signal transmission enables use in control systems
Type Rated supply voltage Order code Pack. unit
pieces
Price
1 piece
Continuously variable adjustment range:
Example :
Input confi guration: 0...10 V
Output confi guration: -5...5 V
*) Detection of input voltage signal interruptions:
If the input signal circuit is interrupted, the output signal changes to the
adjusted minimum value (low fail safe) or maximum value (high fail safe).
If "No fail safe" is confi gured, input signal interruptions are not detected.
CC-U/STD 24-48 V DC
110-240 V AC
1SVR 040 000 R1700
1SVR 040 001 R0400
1
1
• Accessories ........................................................................... 5/20
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
Pot.
G
H
J
2CDC 282 015 F0206
Burden
R 4.7 k
Burden
R 600
supply
+ 2.5 V
43215876
0...8 V
0...20 mA
4...20 mA
10...50 mA
20...4 mA
20...0 mA
0...50 mV
0...100 mV
0...250 mV
0...500 mV
0...1 V
0...5 V
-10...+10 V
0...125 mV
1...5 V
0...10 V
2... 10 V
-11...+11 V
10...0 V
100...0 mV
0...1 mA
-55...+55 mA
3...4
2...4
4...5
0...1
4...5
4...2
A...D
4...5
0...1
7...9
3...4
5...7
0
3...4
7...9
2
2...4
0
2
4...5
A...D
4...6
3
3
4
1
4
3
C
5
1
8
3
6
0
3
8
2
3
0
2
5
B
5
6
4
0
0
D
D
0
0
B...F
5...7
3...4
-
-
-
-
-
-
B...F
2CDC 282 019 F0203
Switch 1
Input
2.5...7.5 V
3.33...9.99 V
High fail safe *)
Gain Coarse
Type
Potentiometer
0...2.5 V
-22.5...+22.5 mV
-0.45...+0.45 mA
Low faile safe *)
No fail safe *)
12 4356
-10...-2 V
-5...-1 V
-8...0 V
-4...0 V
0...1 mA
0...20 mA
4...20 mA
0...10 mA
0...800 μA
0...8 mA
0...400 μA
125...625 μA
166...833 μA
2...10 mA
100...500 μA
0...666 μA
0...16 mA
0...5 V
0...10 V
1...5 V
2...10 V
-10...+10 V
-5...+5 V
-10...0 V
-5...0 V
0...8 V
0...4 V
2CDC 282 020 F0203
Switch 2
Output
1.25...6.25 V
0...6.66 V
-10...+3.33 V
-5...+1.66 V
-7.5...+2.5 V
-3.75...+1.25 V
1.66...8.33 V
-6.66...+6.66 V
-3.33...+3.33 V
0...0.5 mA
0...13.33 mA
2.5...12.5 mA
3.33...16.66 mA
0.2...1 mA
OUT [%]
IN [%]
SW1.4 = +100 %
SW1.5 = +50 %
100
90
80
70
60
50
40
30
20
10
10 20 30 40 50 60 70 80 90 100
2CDC 282 018 F0203
Offset remote poti
SW1.6 = +22.5 %
Gain
“gain-coarse”
und
“gain-fine”
2CDC 282 003 F0204
OFF
Legend
no influence
ON
Wiring instruction
Adjustment range
DIP switch settings
 5/9
2CDC110004C0207
5
CC-U/STDR
2CDC 281 003 F0t03
Analog standard signal converter
CC-U/STDR with relay output
Ordering details
CC-U/STDR universal signal converter for standard signals, with 2 threshold relay
outputs and with 3-way electrical isolation
Standard signal converter with 7 setting ranges
2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be
adjusted independently from each other)
Open-circuit or closed-circuit principle confi gurable by means of a DIP switch
2 yellow LEDs for clear status indication of the output relays
Plug-in connecting terminals for inputs, outputs and supply
CC-U/STDR 24-48 V DC
110-240 V AC
1SVR 040 010 R0000
1SVR 040 011 R2500
1
1
Plug-in connecting
terminals
Threshold value for R1
Hysteresis for R1
Threshold value for R2
Hysteresis for R2
U: green LED -
supply voltage
R2: yellow LED -
Relay 2 energized
R1: yellow LED -
Relay 1 energized
Marker label
Switching points of the output relay depending on the input range,
confi guration open-circuit principle
Type Rated supply voltage Order code Pack. unit
pieces
Price
1 piece
• Accessories ........................................................................... 5/20 • Technical data ........................................................................ 5/21
• Technical diagrams ............................................................... 5/27 • Dimensional drawings ............................................................ 5/27
Function diagrams
DIP switch settings
Wiring instruction
2CDC 282 016 F0206
Value R1
Value R2
Threshold Hysteresis
supply
2CDC 282 003 F0204
OFF
Legend
no influence
ON
21-24
21-22
11-14
11-12
R2
R1
2CDC 282 044 F0203
R1 Threshold value
R1 Hysteresis
R2 Hysteresis
R2 Threshold value
Temperature
Closed-circuit principle
21-24
21-22
11-14
11-12
R2
R1
2CDC 282 046 F0203
R1 Threshold value
R1 Hysteresis
R2 Hysteresis
R2 Threshold value
Temperature
Open-circuit principle
12 4356
0...0 V
0...5 V
0...1 V
-10...+10 V
1...5 V
0...20 mA
4...20 mA
2CDC 282 005 F0204
Switch
Input
Output
Closed-circuit principle
Open-circuit principle
OUT
11-14
11-12
21-24
21-22
R1
R2
IN [%]
100
90
80
70
60
50
40
30
20
10
0
2CDC 282 021 F0203
Hysteresis R1
5-50 % of
threshold
value R1
Threshold value R1
2-100 %
of input range
Threshold value R2
2-100 %
of input range
Hysteresis R2
5-50 % of
threshold
value R2
Actual value
Switching points
5/10 
2CDC110004C0207
5
CC-E/RTD
2CDC 281 004 F0t03
Temperature signal converter for RTD sensors
CC-E/RTD
Ordering details
Gain adjustment
Offset adjustment
U: green LED -
supply voltage
DIP switch for input
and output confi guration
(only available on universal
devices)
CC-E/RTD temperature signal converter for RTD sensors, linearized with 3-way
electrical isolation
2 universally confi gurable devices (type CC-E/RTD)
2x12 single-function devices
"Plug and Work", no adjustment of single-function devices required
Temperature signal converter for PT100 sensors
2- or 3-wire connection
Supply voltage: 24 V DC
universal
CC-E/RTD refer to table 0-10 V, 0-20 mA,
4-20 mA 1SVR 011 701 R25001) 1
single-function
CC-E RTD/V
CC-E RTD/I
CC-E RTD/I
PT100
0...100 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 730 R2500
1SVR 011 731 R1200
1SVR 011 732 R1300
1
1
1
CC-E RTD/V
CC-E RTD/I
CC-E RTD/I
PT100
-50...+50 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 733 R1400
1SVR 011 734 R1500
1SVR 011 735 R1600
1
1
1
CC-E RTD/V
CC-E RTD/I
CC-E RTD/I
PT100
0...300 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 736 R1700
1SVR 011 737 R1000
1SVR 011 738 R2100
1
1
1
CC-E RTD/V
CC-E RTD/I
CC-E RTD/I
PT100
-50...+250 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 739 R2200
1SVR 011 740 R0700
1SVR 011 741 R2400
1
1
1
Supply voltage: 110-240 V AC
universal
CC-E/RTD refer to table 0-10 V, 0-20 mA,
4-20 mA 1SVR 011 706 R2200 1
single-function
CC-E RTD/V
CC-E RTD/I
CC-E RTD/I
PT100
0...100 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 788 R2400
1SVR 011 789 R2500
1SVR 011 790 R2200
1
1
1
CC-E RTD/V
CC-E RTD/I
CC-E RTD/I
PT100
-50...+50 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 791 R1700
1SVR 011 792 R1000
1SVR 011 793 R1100
1
1
1
CC-E RTD/V
CC-E RTD/I
CC-E RTD/I
PT100
0...300 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 794 R1200
1SVR 011 795 R1300
1SVR 011 796 R1400
1
1
1
CC-E RTD/V
CC-E RTD/I
CC-E RTD/I
PT100
-50...+250 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 797 R1500
1SVR 011 798 R2600
1SVR 011 799 R2700
1
1
1
1)
B 1604 Class I, Div.2
(universal device)
Type Input signal Output signal Order code Pack. unit
piece
Price
1 piece
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
2CDC 282 003 F0204
OFF
Legend
no influence
ON
12 4356
0...300 °C
0...100 °C
0...500 °C
-50...+50 °C
-50...+250 °C
-50...+450 °C
High fail safe
Low fail safe
0...10 V
0-20 mA
4-20 mA
0-10 V
0-20 mA
4-20 mA
0-10 V
0-20 mA
4-20 mA
0-10 V
0-20 mA
4-20 mA
0-10 V
0-20 mA
4-20 mA
0-10 V
0-20 mA
4-20 mA
2CDC 282 006 F0208
Input Output Switch
J
H
G
2CDC 282 007 F0206
Burden
R 1.0 k
Burden
R 500
supply
DIP switch settings (universal devices)
Wiring instruction
 5/11
2CDC110004C0207
5
CC-U/RTD
2CDC 281 005 F0t03
Temperature signal converter for RTD sensors
CC-U/RTD
Ordering details
CC-U/RTD universal signal converter for PT10, PT100, PT1000 temperature sensors
(acc. to IEC 751 and JIS C 16041), linearized with 3-way electrical isolation
Plug-in connecting
terminals
Gain: Coarse adjustment
Gain: Fine adjustment
Offset adjustment
U: green LED -
supply voltage
Marker label
Resistance of PT10, PT100 and PT1000 sensors depending on the temperature
Confi gurable output signal response on
input signal interruption (low / high fail safe)
Adjustment and operating elements on
the front-side
Short-circuit proof signal outputs
Plug-in connecting terminals for inputs,
outputs and supply
2- or 3-wire connection
*) Detection of input signal interruptions:
If the input signal circuit is interrupted, the output signal changes
to the adjusted minimum value (low fail safe) or maximum value
(high fail safe).
1) Japanese standard
CC-U/RTD 24-48 V DC
110-240 V AC
1SVR 040 002 R0500
1SVR 040 003 R0600
1
1
Type Rated supply voltage Order code Pack. unit
pieces
Price
1 piece
• Accessories ........................................................................... 5/20
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
PT1000
PT100
PT10
2CDC 282 022 F0203
Resistance []
Temperature [°C]
Wiring instruction
J
H
G
2CDC 282 017 F0206
Burden
R 4.7 k
Burden
R 600
supply
DIP switch settings
Characteristic curves
2CDC 282 003 F0204
OFF
Legend
no influence
ON
12 4356124356
PT10
PT100
PT1000
0...500 °C
0...550 °C
0...600 °C
0...650 °C
0...700 °C
0...750 °C
0...800 °C
0...850 °C
0...50 °C
0...60 °C
0...70 °C
0...80 °C
0...90 °C
0...100 °C
0...200 °C
0...400 °C
0...300 °C
0...500 °C
0...10 °C
0...20 °C
0...30 °C
0...40 °C
0...50 °C
0...60 °C
F
E
D
C
B
A
9
8
F
E
B
A
9
8
3
1
2
0
8
3
2
1
0
0
-
-
2CDC 282 023 F0203
Type Range
Switch 1 Switch 2
Input
Low fail safe *)
High fail safe *)
Gain
Coarse
12 4356
-10...-2 V
-5...-1 V
-8...0 V
-4...0 V
0...1 mA
0...20 mA
4...20 mA
0...10 mA
0...800 μA
0...8 mA
0...400 μA
125...625 μA
166...833 μA
2...10 mA
100...500 μA
0...666 μA
0...16 mA
0...5 V
0...10 V
1...5 V
2...10 V
-10...+10 V
-5...+5 V
-10...0 V
-5...0 V
0...8 V
0...4 V
2CDC 282 024 F0203
Switch 3
Output
1.25...6.25 V
0...6.66 V
-10...+3.33 V
-5...+1.66 V
-7.5...+2.5 V
-3.75...+1.25 V
1.66...8.33 V
-6.66...+6.66 V
-3.33...+3.33 V
0...0.5 mA
0...13.33 mA
2.5...12.5 mA
3.33...16.66 mA
0.2...1 mA
5/12 
2CDC110004C0207
5
CC-U/RTDR
2CDC 281 006 F0t03
Temperature signal converter for RTD sensors
CC-U/RTDR with relay output
Ordering details
Plug-in connecting
terminals
Threshold value for R1
Hysteresis for R1
Threshold value for R2
Hysteresis for R2
U: green LED -
supply voltage
R2: yellow LED -
Relay 2 energized
R1: yellow LED -
Relay 1 energized
Marker label
CC-U/RTDR universal signal converter for temperature and resistance signals,
with 2 threshold relay outputs and 3-way electrical isolation
Temperature signal converter for PT100 signals (5 ranges up to 800 °C) and variable resistances from
0-380
2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be
adjusted independently from each other)
Open-circuit or closed-circuit principle confi gurable by means of a DIP switch
2 yellow LEDs for clear status indication of the output relays
Plug-in connecting terminals for inputs, outputs and supply
2- or 3-wire connection
Switching points of the output relay depending on the input range,
confi guration open-circuit principle
CC-U/RTDR 24-48 V DC
110-240 V AC
1SVR 040 012 R2600
1SVR 040 013 R2700
1
1
Type Rated supply voltage Order code Pack. unit
pieces
Price
1 piece
• Accessories ........................................................................... 5/20 • Technical data ........................................................................ 5/21
• Technical diagrams ............................................................... 5/27 • Dimensional drawings ............................................................ 5/27
Function diagrams
21-24
21-22
11-14
11-12
R2
R1
2CDC 282 044 F0203
R1 Threshold value
R1 Hysteresis
R2 Hysteresis
R2 Threshold value
Temperature
Closed-circuit principle
21-24
21-22
11-14
11-12
R2
R1
2CDC 282 046 F0203
R1 Threshold value
R1 Hysteresis
R2 Hysteresis
R2 Threshold value
Temperature
Open-circuit principle
Wiring instruction
DIP switch settings
υ
G
J
H
KM
B (22)
C (21)
A (24)
E (12)
F (11)
D (14)
R1
R2
2CDC 282 045 F0203
Value R1
Value R2
Threshold Hysteresis
supply
2CDC 282 003 F0204
OFF
Legend
no influence
ON
12 4356
0...100 °C
0...200 °C
0...400 °C
0...600 °C
0...800 °C
2CDC 282 007 F0204
Switch
Input PT100
Output
Closed-circuit principle
Open-circuit principle
OUT
11-14
11-12
21-24
21-22
R1
R2
100
90
80
70
60
50
40
30
20
10
0
IN [%]
800
700
600
500
400
300
200
100
50 100 150 200 250 300 350 400
2CDC 282 025 F0203
Resistance []
Temperature υ [°C]
Hysteresis R1
5-50 % of
threshold
value R1
Threshold value R1
2-100 %
of input range
Threshold value R2
2-100 %
of input range
Hysteresis R2
5-50 % of
threshold
value R2
Actual value
Switching points
 5/13
2CDC110004C0207
5
CC-E/TC
2CDC 281 007 F0t03
Temperature signal converter for thermocouples
CC-E/TC
Ordering details
CC-E/TC analog signal converter for thermocouple signals of the types J and K
with 3-way electrical isolation
2 universally confi gurable devices (type CC-E/TC)
2x6 single-function devices
"Plug and Work", no adjustment of single-function devices required
Supply voltage: 24 V DC
universal
CC-E/TC thermocouple
types J and K
0-10 V, 0-20 mA,
4-20 mA 1SVR 011 702 R26001) 1
single-function
CC-E TC/V
CC-E TC/I
CC-E TC/I
type J
0...600 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 750 R0100
1SVR 011 751 R2600
1SVR 011 752 R2700
1
1
1
CC-E TC/V
CC-E TC/I
CC-E TC/I
type K
0...1000 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 753 R2000
1SVR 011 754 R2100
1SVR 011 755 R2200
1
1
1
Supply voltage: 110-240 V AC
universal
CC-E/TC thermocouple
types J and K
0-10 V, 0-20 mA,
4-20 mA 1SVR 011 707 R2300 1
single-function
CC-E TC/V
CC-E TC/I
CC-E TC/I
type J
0...600 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 760 R0300
1SVR 011 761 R2000
1SVR 011 762 R2100
1
1
1
CC-E TC/V
CC-E TC/I
CC-E TC/I
type K
0...1000 °C
0-10 V
0-20 mA
4-20 mA
1SVR 011 763 R2200
1SVR 011 764 R2300
1SVR 011 765 R2400
1
1
1
Gain adjustment
Offset adjustment
U: green LED -
supply voltage
DIP switch for input
and output confi guration
(only available on universal
devices)
1)
B 1604 Class I, Div.2
(universal device)
Type Input signal Output signal Order code Pack. unit
piece
Price
1 piece
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
Wiring instruction DIP switch settings (universal devices)
2CDC 282 008 F0206
Burden
R 1.0 k
Burden
R 500
supply
2CDC 282 003 F0204
OFF
Legend
no influence
ON
12 4356
TC-J:
0...600 °C
TC-K:
0...1000 °C
High fail safe
Low fail safe
0...10 V
0...20 mA
4...20 mA
0...10 V
0...20 mA
4...20 mA
2CDC 282 007 F0208
Input Output Switch
5/14 
2CDC110004C0207
5
CC-U/TC
2CDC 281 008 F0t03
1)
Temperature signal converter for thermo-
couples of the types K, J, T, S, E, N, R, B
Continuously adjustable voltage signal input
0-10 mV and 0-50 mV
Differential temperature meas. possible 1)
Confi gurable output signal response on input
signal interruption (low fail safe / high fail safe)
Adjustment and operating elements on the
front-side
Short-circuit proof signal outputs
Plug-in connecting terminals for inputs,
outputs and supply
Temperature signal converter for thermocouples
CC-U/TC
Ordering details
CC-U/TC universal signal converter for thermocouples with 3-way electrical isolation
Plug-in connecting
terminals
Gain: Coarse adjustment
Gain: Fine adjustment
Offset adjustment
U: green LED -
supply voltage
Marker label
Thermocouple voltages depending on the temperature
*) Detection of input signal
interruptions:
If the input signal circuit is inter-
rupted, the output signal changes
to the adjusted minimum value
(low fail safe) or maximum value
(high fail safe).
Type Rated supply voltage Order code Pack. unit
pieces
Price
1 piece
CC-U/TC 24-48 V DC
110-240 V AC
1SVR 040 004 R0700
1SVR 040 005 R0000
1
1
• Accessories ........................................................................... 5/20
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
Wiring instruction
DIP switch settings
2CDC 282 019 F0206
without cold-junction compensation:
switch SW2.2 = OFF
2CDC 282 018 F0206
Burden
R 4.7 k
Burden
R 600
supply
12 4356
-10...-2 V
-5...-1 V
-8...0 V
-4...0 V
0...1 mA
0...20 mA
4...20 mA
0...10 mA
0...800 μA
0...8 mA
0...400 μA
125...625 μA
166...833 μA
2...10 mA
100...500 μA
0...666 μA
0...16 mA
0...5 V
0...10 V
1...5 V
2...10 V
-10...+10 V
-5...+5 V
-10...0 V
-5...0 V
0...8 V
0...4 V
2CDC 282 017 F0208
Switch 3
Output
1.25...6.25 V
0...6.66 V
-10...+3.33 V
-5...+1.66 V
-7.5...+2.5 V
-3.75...+1.25 V
1.66...8.33 V
-6.66...+6.66 V
-3.33...+3.33 V
0...0.5 mA
0...13.33 mA
2.5...12.5 mA
3.33...16.66 mA
0.2...1 mA
2CDC 282 003 F0204
OFF
Legend
no influence
ON
12 4356124356
R
B
mV
N
K
J
T
S
E
0-100...900 °C
0-250...1350 °C
0-100...750 °C
0-100...400 °C
-150-0...400 °C
0-250...1550 °C
0-100...700 °C
0-200...1000 °C
0-100...650 °C
0-200...1300 °C
0-250...1350 °C
0-450...1700 °C
0-700...1750 °C
0-2...10 mV
0-10...50 mV
2CDC 282 010 F0204
Type Range
Switch 1 Switch 2
Input
Low fail safe *)
High fail safe *)
Typ T
Typ N
Typ K
Typ J
Typ E
Typ R
Typ S
Typ B
-250
-200
-150
-100
-50
0
50
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
80000
75000
70000
65000
60000
55000
50000
45000
40000
35000
30000
25000
20000
15000
10000
5000
0
-5000
-10000
-15000
2CDC 282 026 F0103
Temperatur [°C]
Thermoelement-Spannung [μV]
Characteristic curves
 5/15
2CDC110004C0207
5
CC-U/TCR
2CDC 281 009 F0t03
Temperature signal converter for thermocouples
CC-U/TCR with relay output
Ordering details
CC-U/TCR universal signal converter for thermocouples, with 2 threshold relay
outputs and 3-way electrical isolation
Temperature signal converter for thermocouples of the types K, J, T, S
2 threshold relay outputs with one change-over contact each (threshold and respective hysteresis can
be adjusted independently from each other)
Open-circuit or closed-circuit principle confi gurable by means of a DIP switch
2 yellow LEDs for clear status indication of the output relays
Plug-in connecting terminals for inputs, outputs and supply
Plug-in connecting
terminals
Threshold value for R1
Hysteresis for R1
Threshold value for R2
Hysteresis for R2
U: green LED -
supply voltage
R2: yellow LED -
Relay 2 energized
R1: yellow LED -
Relay 1 energized
Marker label
Switching points of the output relay depending on the input range,
confi guration open-circuit principle
Type Rated supply voltage Order code Pack. unit
pieces
Price
1 piece
CC-U/TCR 24-48 V DC
110-240 V AC
1SVR 040 014 R2000
1SVR 040 015 R2100
1
1
• Accessories ........................................................................... 5/20 • Technical data ........................................................................ 5/21
• Technical diagrams ............................................................... 5/27 • Dimensional drawings ............................................................ 5/27
Function diagrams
21-24
21-22
11-14
11-12
R2
R1
2CDC 282 044 F0203
R1 Threshold value
R1 Hysteresis
R2 Hysteresis
R2 Threshold value
Temperature
Closed-circuit principle
21-24
21-22
11-14
11-12
R2
R1
2CDC 282 046 F0203
R1 Threshold value
R1 Hysteresis
R2 Hysteresis
R2 Threshold value
Temperature
Open-circuit principle
Wiring instruction
DIP switch settings
2CDC 282 020 F0206
Value R1
Value R2
Threshold Hysteresis
supply
2CDC 282 003 F0204
OFF
Legend
no influence
ON
Typ T
Typ J
Typ K
Typ S
IN [%]
100
0OUT
11-14
11-12
21-24
21-22
R1
R2
7000
6500
6000
5500
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
-500
-1000
-1500
-275
-175
-75
25
125
225
325
425
525
625
725
825
925
1025
1125
1225
1325
1425
1525
1625
1725
1825
2CDC 282 027 F0203
Temperature [°C]
Thermocouple voltage [μV]
Threshold value
R2 = 400 °C
Release hysteresis
Threshold value
R1 = 1000 °C
Release hysteresis
12 4356
S
J
K
T
0...240 °C
0...480 °C
0...1200 °C
0...250 °C
0...500 °C
0...1350 °C
-150...+120 °C
0...220 °C
0...400 °C
0...210 °C
0...380 °C
0...860 °C
0...1550 °C
2CDC 282 004 F0204
Type Range
Switch
Input
Output
Closed-circuit principle
Open-circuit principle
Switching points
5/16 
2CDC110004C0207
5
CC-E/I
2CDC 281 010 F0t03
Measuring converter for sinusoidal and DC
currents CC-E/I
Ordering details
CC-E/I measuring converter for current signals 0-5 A, 0-20 A, AC/DC
with 3-way electrical isolation
2 universally confi gurable devices (type CC-E/I)
2x6 single-function devices
"Plug and Work", no adjustment of single-function devices required
Gain adjustment
Offset adjustment
U: green LED -
supply voltage
DIP switch for input
and output confi guration
(only available on
universal devices)
1)
B 1604 Class I, Div.2
(universal device)
Type Input signal Output signal Order code Pack. unit
pieces
Price
1 piece
Supply voltage: 24 V DC
universal
CC-E/I 0-5 A,
0-20 A, AC/DC
0-10 V, 0-20 mA,
4-20 mA 1SVR 011 703 R27001) 1
single-function
CC-E IAC/V
CC-E IAC/I
CC-E IAC/I
0-5 A, 0-20 A, AC
0-10 V
0-20 mA
4-20 mA
1SVR 011 770 R0500
1SVR 011 771 R2200
1SVR 011 772 R2300
1
1
1
CC-E IDC/V
CC-E IDC/I
CC-E IDC/I
0-5 A, 0-20 A, DC
0-10 V
0-20 mA
4-20 mA
1SVR 011 773 R2400
1SVR 011 774 R2500
1SVR 011 775 R2600
1
1
1
Supply voltage: 110-240 V AC
universal
CC-E/I 0-5 A,
0-20 A, AC/DC
0-10 V, 0-20 mA,
4-20 mA 1SVR 011 708 R0400 1
single-function
CC-E IAC/V
CC-E IAC/I
CC-E IAC/I
0-5 A, 0-20 A, AC
0-10 V
0-20 mA
4-20 mA
1SVR 011 780 R1100
1SVR 011 781 R0600
1SVR 011 782 R0700
1
1
1
CC-E IDC/V
CC-E IDC/I
CC-E IDC/I
0-5 A, 0-20 A, DC
0-10 V
0-20 mA
4-20 mA
1SVR 011 783 R0000
1SVR 011 784 R0100
1SVR 011 785 R1100
1
1
1
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
Wiring instruction
DIP switch settings (universal devices)
2CDC 282 011 F0204
Select input range by terminals
Input range 5 A
Connected lines
Used terminals
Terminal marking
Input range 20 A
Connected lines
Used terminals
Terminal marking
J
H
G
20 A
5 A
A
C
D
F
V
I
K
-
M
+
+
-
+
-
IN OUT
I
2CDC 282 008 F0208
Burden
R 1.0 k
Burden
R 500
supply
2CDC 282 002 F0204
ON
Legend
OFF
12 4356
I - DC
I - AC
I - AC
I - DC
I - AC
I - DC
0...10 V
0...20 mA
4...20 mA
2CDC 282 005 F0208
Input Output Switch
Input range selection
 5/17
2CDC110004C0207
5
2CDC 282 010 F0b06
CC-E IAC/ILPO
2CDC 281 018 F0t04
Measuring converter for sinusoidal currents
CC-E IAC/ILPO
Ordering details
CC-E IAC/ILPO measuring converter without auxiliary power for sinusoidal currents
0-1 A, 0-5 A, output 4-20 mA
Measuring converter for sinusoidal currents (0-1 A, 0-5 A)
Measuring range selection by front-face sliding switch
4-20 mA output current in proportion to input current
no additional power supply required
CC-E IAC/ILPO
0-1 A, 0-5 A, AC 1SVR 010 203 R0500 1
Type Input signal Order code Pack. unit
pieces
Price
1 piece
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
Gain adjustment
Offset adjustment
Selection of measuring
range
Wiring instruction
5/18 
2CDC110004C0207
5
CC-U/I
2CDC 281 012 F0t03
Measuring converter for current RMS values
CC-U/I
Ordering details
CC-U/I universal measuring converter for RMS values of 0-1 A and 0-5 A,
with 3-way electrical isolation
RMS converter for current signals up to 1 A and up to 5 A of any wave form (DC, DC with superimposed
AC components, pure sinusoidal, triangular, phase-angle controlled, etc. in a measuring range of
0-600 Hz)
Adjustment and operating elements on the front
Short-circuit proof signal outputs
Plug-in connecting terminals for inputs, outputs and supply
RMS measurement and conversion of a current signal
Plug-in connecting
terminals
Gain adjustment
Offset adjustment
U: green LED -
supply voltage
Marker label
Type Rated supply voltage Order code Pack. unit
pieces
Price
1 piece
CC-U/I 24-48 V DC
110-240 V AC
1SVR 040 006 R0100
1SVR 040 007 R0200
1
1
• Accessories ........................................................................... 5/20
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
Wiring instruction DIP switch settings
2CDC 282 021 F0206
Burden
R 4.7 k
Burden
R 600
supply
2CDC 282 003 F0204
OFF
Legend
no influence
ON
12 4356
-10...-2 V
-5...-1 V
-8...0 V
-4...0 V
0...1 mA
0...20 mA
4...20 mA
0...10 mA
0...800 μA
0...8 mA
0...400 μA
125...625 μA
166...833 μA
2...10 mA
100...500 μA
0...666 μA
0...16 mA
0...5 V
0...10 V
1...5 V
2...10 V
-10...+10 V
-5...+5 V
-10...0 V
-5...0 V
0...8 V
0...4 V
2CDC 282 029 F0203
Switch
Output
1.25...6.25 V
0...6.66 V
-10...+3.33 V
-5...+1.66 V
-7.5...+2.5 V
-3.75...+1.25 V
1.66...8.33 V
-6.66...+6.66 V
-3.33...+3.33 V
0...0.5 mA
0...13.33 mA
2.5...12.5 mA
3.33...16.66 mA
0.2...1 mA
I(t) [A]
IN [%]
OUT [%]
0 50 100
t
5
4
3
2
1
0
-1
-2
-3
-4
-5
2CDC 282 028 F0203
Offset 20 %
Gain 15 %
resulting
RMS value
Input range selection
Example of application
 5/19
2CDC110004C0207
5
CC-U/V
2CDC 281 013 F0t03
Measuring converter for voltage RMS values
CC-U/V
Ordering details
CC-U/V universal measuring converter for RMS values of 0-600 V,
with 3-way electrical isolation
RMS converter for voltage signals up to 600 V of any wave form (DC, DC with superimposed AC
components, pure sinusoidal, triangular, phase-angle controlled, etc. in a measuring range of
0-600 Hz)
Adjustment and operating elements on the front
Short-circuit proof signal outputs
Plug-in connecting terminals for inputs, outputs and supply
Plug-in connecting
terminals
Input voltage range
selection
Gain adjustment
Offset adjustment
U: green LED -
supply voltage
Marker label
RMS measurement and conversion of a phase-angle controlled voltage signal L1 = 230 V
Type Rated supply voltage Order code Pack. unit
pieces
Price
1 piece
CC-U/V 24-48 V DC
110-240 V AC
1SVR 040 008 R1300
1SVR 040 009 R1400
1
1
• Accessories ........................................................................... 5/20
• Technical data ....................................................................... 5/21 • Dimensional drawings ............................................................ 5/27
Wiring instruction DIP switch settings
0...100 V
0...150 V
0...250 V
0...300 V
0...400 V
0...600 V
0...450 V
0...550 V
1
2
3
4
5
8
6
7
2CDC 282 012 F0204
Switch
position
Selecting input range by
front-face rotary switch
U(t) [V]
INUeff [V]
OUT [%]
0 50 100
300
0
-300
2CDC 282 030 F0203
Offset 20 %
Gain 15 %
resulting
RMS value
operating angle
2CDC 282 022 F0206
Burden
R 4.7 k
Burden
R 600
supply
2CDC 282 003 F0204
OFF
Legend
no influence
ON
12 4356
-10...-2 V
-5...-1 V
-8...0 V
-4...0 V
0...1 mA
0...20 mA
4...20 mA
0...10 mA
0...800 μA
0...8 mA
0...400 μA
125...625 μA
166...833 μA
2...10 mA
100...500 μA
0...666 μA
0...16 mA
0...5 V
0...10 V
1...5 V
2...10 V
-10...+10 V
-5...+5 V
-10...0 V
-5...0 V
0...8 V
0...4 V
2CDC 282 029 F0203
Switch
Output
1.25...6.25 V
0...6.66 V
-10...+3.33 V
-5...+1.66 V
-7.5...+2.5 V
-3.75...+1.25 V
1.66...8.33 V
-6.66...+6.66 V
-3.33...+3.33 V
0...0.5 mA
0...13.33 mA
2.5...12.5 mA
3.33...16.66 mA
0.2...1 mA
Example of application
Input range selection
5/20 
2CDC110004C0207
5
2CDC 252 187 F0005
4,5
62,5
60
10 11,5
22,5
.177”
2.46”
2.36”
.394”
.886”
.453”
2CDC 252 185 F0005
22,5
68,5
7
3,5
.886”
2.70 ”
.138”
.275”
front-to-back
size 107
ADP.01
20
3A11
8
.315”
.787”
2CDC 252 186 F0005
MAR.01
Sealable cover
COV.01
Analog signal converters
Accessories for CC-U range
Ordering details
Accessories
Adapter for screw mounting
Sealable transparent cover
Type for type Width
in mm
Order code Pack.
unit
pieces
Price
1 piece
Weight
1 piece
g / oz
ADP.01 CC-U 22.5 1SVR 430 029 R0100 1 18.4/0.65
Type for type Width
in mm
Order code Pack.
unit
pieces
Price
1 piece
Weight
1 piece
g / oz
COV.01 CC-U 22.5 1SVR 430 005 R0100 1 5.2/0.18
Marker label
Type for type Order code Pack.
unit
pieces
Price
1 piece
Weight
1 piece
g / oz
MAR.01 CC-U 1SVR 366 017 R0100 10 0.19/0.007
 5/21
2CDC110004C0207
5
Analog signal converters
CC-E/STD, CC-E x/x, CC-E/RTD, CC-E/TC
Technical data
Type CC-E/STD CC-E/RTD 3) CC-E/TC
Input circuits - Analog inputs J-G-H Current Voltage Temperature sensors Thermocouples
(IEC 584-1 and 2)
Input signal Standard signals PT100 TC.K, TC.J
Rated input range 0...20 mA /
4...20 mA
0...5 V /
0...10 V /
-10...+10 V
-50...+500 °C
TC.K: 0...1000 °C,
TC.J: 0...600 °C
Limitation of input signals +55 mA ± 11 V
Infl uence of line resistance - < 0.01 %/< 0.5 % / 100
Gain adjustment range ± 5 % (universal devices)
Offset adjustment range ± 5 % (universal devices)
Input impedance 50 1 M--
Suppression at 50 Hz - - > 35 dB
Common-mode rejection - 100 dB
Output circuits - Analog outputs D-F, A-C Current Voltage
Output signal 0-20 mA, 4-20 mA 0-5 V, 0-10 V
Output burden 500 1.0 K
Accuracy 1) ± 0.5 % of full-scale
Residual ripple < 0.5 %
Response time 200 μs 10 ms
Transmission frequency 2 kHz 80 Hz 2 Hz (up to -3 dB)
Reaction to input circuit interruption High fail safe: Output voltage > 115 % of measuring range 2)
Low fail safe: Output voltage < -0.6 V, output current = 0 mA
Supply circuits K-M DC versions AC versions
Supply voltage 24 V DC 110-240 V AC - 50/60 Hz
Supply voltage tolerance -15...+15 % -15...+10 %
Power consumption 1.5 W typ. 1.5 VA typ.
Indication of operational states
Rated control supply voltage USU: green LED
General data
Ambient temperature range operation / storage 0...+60 °C / -20...+80 °C
Temperature coeffi cient ± 500 ppm/°C
Degree of protection (DIN 40050) IP20
Mounting position ventilation slots on top and bottom
Mounting DIN rail (IEC/EN 60715), snap-on mounting
Electrical connection
Wire size rigid 0.2-4 mm2 (24-12 AWG)
ne-strand with(out) wire end ferrule
0.2-
2.5 mm2 (24-14 AWG)
Stripping length 7 mm (0.28 inch)
Tightening torque 0.5 Nm (4.4 lb.in)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic eld
(HF radiation resistance)
IEC/EN 61000-4-3 10 V/m
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 ±2 kV / ±1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission EN 61000-6-4 Class B
Isolation data
Test voltage between all isolated circuits 2.5 kV AC
Rated insulation voltage - - -
1) includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
2) Only -/RTD and -/TC: Single-function devices respond with Low fail safe to input signal interruptions
3) When connecting a 2-wire sensor, the terminals J and H have to be jumpered.
Approvals ...................................... 5/3
5/22 
2CDC110004C0207
5
Analog signal converter
CC-E I/I-1, CC-E I/I-2
Technical data
Type CC-E I/I
Input circuits - Analog inputs Current
Input current IIN 0-20 mA, 4-20 mA
Min. input current < 100 μA
Max. input current 50 mA1) (VIN < 18 V)
Input voltage UIN < 2.5 V + (IIN x RL)
Input voltage drop Ui< 2.5 V (20 mA, RL = 0 )
Max. input voltage 18 V1) (IIN < 50 mA)
Output circuits
Output current IOUT 0-20 mA, 4-20 mA
Output load RL0-500
Output voltage UOUT IOUT x RL
Residual ripple < 20 mVpp (500 , 20 mA)
Response time (0-100 %) < 15 ms (0-500 , 20 mA),
< 5 ms (500 , 20 mA, 25 °C)
Accuracy 0.1 % of full-scale (20 mA)
Load infl uence (0-500 ) 0.05 % / 100 ,
-0.1 % / 100 (25 °C)
General data
Width of the enclosure 18 mm
Weight 1 channel approx. 0.037 kg (0.082 lb)
2 channel approx. 0.044 kg (0.097 lb)
Mounting position any
Degree of protection
enclosure / terminals
IP20 / IP20
Ambient temperature range operation / storage -25...+60 °C / -40...+85 °C
Temperature coeffi cient < 50 ppm / °C
Mounting DIN rail (IEC/EN 60715)
Electrical connection
Wire size rigid 0.2-4 mm2 (24-12 AWG)
ne-strand with(out) wire end ferrule
0.2-
2.5 mm2 (24-14 AWG)
Stripping length 7 mm (0,28 inch)
Tightening torque 0.5 Nm (4.4 lb.in)
Standards
Product standard EN 50178
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic eld
(HF radiation resistance)
EN 61000-4-3 10 V/m
fast transients (Burst) EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) EN 61000-4-5 ±2 kV / ±1 kV
HF line emission EN 61000-4-6 10 V
magnetisches Feld EN 61000-4-8 30 A/m
Interference emission EN 61000-6-4
Radiated noise EN 55011 Class B
Operational reliability (EN 68-2-6) 4 g
Mechanical resistance (EN 68-2-6) 10 g
Environmental testing (IEC 68-2-30 Db) 24 h cycle, 55 °C, 93 % rel., 96 h
Isolation data
Insulation voltage input / output 500 Veff / 50 Hz
Insulation voltage between channels 5 kVeff / 50 Hz
(device with 2 channels)
Pollution category 2
Overvoltage category II
1) The input parameters have to be limited to the indicated maximum values.
Approvals ...................................... 5/3
 5/23
2CDC110004C0207
5
Analog signal converters
CC-U/STD, CC-U/RTD, CC-U/TC
Technical data
Type CC-U/STD CC-U/RTD 3) CC-U/TC
Input circuits - Analog inputs J-G-H Current Voltage Potentio-
meter Temperature sensors Thermocouples
(IEC 584-1 and 2)
Input signal 0-20 mA 0-100 mV 470 - PT10, PT100, PT1000 TC.K TC.J
4-20 mA 0-1 V 1 M2) (IEL 751 and JICC 1604) TC.T TC.S
10-50 mA 0-5 V TC.E TC.N
0-1 mA 1-5 V TC.R TC.B
0-10 V
2-10 V
± 10 V
Limitation of input signals ± 55 mA ± 11 V - -
Rated input range
---
Max. temperature adjustable:
6-60 °C for PT1000
50-500 °C for PT100
500-850 °C for PT10
refer to temperature specs.
of individual thermocouples
Infl uence of line resistance - - - 0.015 °C/< 0.01 % / 100
Gain adjustment range
(universal devices)
0.9-
110 mA
45 mV -
22 V - see DIP switch settings
Offset adjustment range (universal devices) -137.5...+62.5 % ± 5 % ± 10 %
Input impedance for different ranges - -
without detection of input signal interruption
51 6 M3 G--
with detection of input signal interruption
51 3.5 M9.5 G--
Suppression at 50 Hz - - - - > 40 dB
Common-mode rejection - - - 120 dB 105 dB
Output circuits - Analog outputs D-F, A-C Current Voltage
Output signal 0-20 mA, 4-20 mA 0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V
Output burden 600   4.7 K
Accuracy 1) ±0.1 % of full-scale ±0.2 % of full-scale ±0.1 % of full-scale
Residual ripple - < 0.15 % -
Response time 200 μs 10 ms 200 ms
Transmission frequency 1 kHz 80 Hz 2 Hz (to -3 dB)
Supply circuits K-M
Rated supply voltage 24-48 V DC 110-240 V AC
Supply voltage range 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC
Supply voltage tolerance DC: -15...+15 % AC: -15...+10 %
Rated frequency 0 Hz or 50/60 Hz
Power consumption 2 W at 24 V DC 4.5 VA at 230 V AC
Indication of operational states
Supply voltage U: green LED
General data
Ambient temperature range operation / storage -20...+60 °C / -40...+80 °C
Temperature coeffi cient ±150 ppm/°C ±250 ppm/°C ±200 ppm/°C at min. offset
±400 ppm/°C at max. offset
Mounting position any
Mounting DIN rail (IEC/EN 60715), snap-on mounting / screw mounting with adapter
Electrical connection
Wire size rigid plug-connector with screw terminals 0.2-2.5 mm2 (24-12 AWG)
ne-strand with(out) wire end ferrule plug-connector with screw terminals 0.2-2.5 mm2 (24-12 AWG)
Stripping length 7 mm (0.28 inch)
Tightening torque 0.4 Nm (3.5 ib.in)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD)
IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic eld
(HF radiation resistance)
IEC/EN 61000-4-3 10 V/m
fast transients (Burst)
IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge)
IEC/EN 61000-4-5 2 kV / 1 kV
HF line emission
IEC/EN 61000-4-6 10 V
Interference emission
EN 61000-6-4 Class B
Isolation data
Isolation test (between all isolated circuits) 1.5 kV
Test voltage (between all isolated circuits) 1.5 kV / 50 Hz
1) includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
2) Detection of an input signal break (fail safe) and resistance > 10 k results in a linearity of 0,2 %.
3) When connecting a 2-wire sensor, the terminals J and H have to be jumpered.
Approvals ...................................... 5/3
5/24 
2CDC110004C0207
5
Analog signal converters with relay output
CC-U/STDR, CC-U/RTDR, CC-U/TCR
Technical data
Type CC-U/STDR CC-U/RTDR 1) CC-U/TCR
Input circuits - Analog inputs J-H Current Voltage Temperature sensors Thermocouples
(IEC 584-1 and 2)
Measuring signal / input range 0-20 mA 0-1 V / 1-5 V PT100 TC.K, TC.J
4-20 mA 0-10 / ±10 V TC.T, TC.S
Input resistance
approx. 50
approx. 1,5 M
Adjustable threshold 2-100 % of selected input range
Adjustable hysteresis 5-50 % of threshold
Repeat accuracy (constant parameters) ±0.5 % of full-scale
Output circuits - Relay outputs E-D-F, B-C-A Relay, 2 c/o contacts
Rated switching voltage 250 V AC
Rated switching
current
AC12 (resistive) 230 V
4 A
AC15 (inductive) 230 V
3 A
DC12 (resistive) 24 V
4 A
DC13 (inductive) 24 V
2 A
AC rating
(UL 508)
Utilization category
(Control Circuit Rating Code) B 300
max. rated operational voltage 300 V AC
max. continuous thermal current at B 300 5 A
max. making/breaking
apparent power at B 300 3600/360 VA
Minimum switching voltage 12 V
Minimum switching current / power 10 mA / 0.6 VA (W)
Response time 10 ms
Mechanical lifetime 30 x 106 switching cycles
Electrical lifetime at AC12, 230 V, 4 A 0.1 Mio. switching cycles
Supply circuits K-M
Rated supply voltage 24-48 V DC 110-240 V AC
Supply voltage range 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC
Supply voltage tolerance DC: -15...+15 % AC: -15...+10 %
Rated frequency 0 Hz or 50/60 Hz
Power consumption 2 W at 24 V DC 4.5 VA at 230 V AC
Indication of operational states
Supply voltage U: green LED
1st / 2nd output relay energized R1: yellow LED / R2: yellow LED
General data
Ambient temperature range operation / storage -20...+60 °C / -40...+80 °C
Temperature coeffi cient ±300 ppm/°C
Mounting position any
Mounting DIN rail (IEC/EN 60715), snap-on mounting / screw mounting with adapter
Electrical connection
Wire size rigid plug-connector with screw terminals 0.2-2.5 mm2 (24-12 AWG)
ne-strand with(out) wire end ferrule plug-connector with screw terminals 0.2-2.5 mm2 (24-12 AWG)
Stripping length 7 mm (0.28 inch)
Tightening torque 0.4 Nm (3.5 ib.in)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD)
IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic eld
(HF radiation resistance)
IEC/EN 61000-4-3 10 V/m
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 2 kV / 1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission
EN 61000-6-4 Class B
Isolation data
Insulation voltage (between all isolated circuits) 2.5 kV
Test voltage (between all isolated circuits) 2.5 kV
1) When connecting a 2-wire sensor, the terminals J and H have to be jumpered.
Approvals ...................................... 5/3
 5/25
2CDC110004C0207
5
Analog signal converters
CC-E/I, CC-E IAC/ILPO
Technical data
Type CC-E/I CC-E IAC/ILPO
Input circuits - Analog inputs
J-G-H C-D
AC current DC current 2 meas. ranges selectable
Rated input range 0-5 A / 0-20 A 0-5 A / 0-20 A
0-1 A / 0-5 A / sinusoidal
Measuring frequency 50/60 Hz
Overload capacity of
inputs
input range 1 10 x INom (50 A) for max. 1 s 10 x INom (50 A) for max. 2 s
input range 2 10 x INom (200 A) for max. 1 s 10 x INom (200 A) for max. 2 s
Gain adjustment range ±5 % (universal devices) -
Offset adjustment range ±5 % (universal devices) -
Input impedance / resistance 5A : 65 m20 A : 2.5 m5 m
Output circuits - Analog outputs D-F
Current
A-C
Voltage
F-E
passive current output in proportion
to input current
Output signal 0-20 mA / 4-20 mA 0-10 V 4-20 mA
Output burden / load
500  1.0
12 V DC: 150 ,
24 V DC: 750
30 V DC: 1050
Accuracy 1) ± 2 % of full-scale
Offset adjustment range ±5 % (universal device) ± 5 %
Gain adjustment range ±5 % (universal device) ± 20 %
Residual ripple < 0.5 %
Response time 0.5 s 0.6 s
Transmission frequency DC or 50/60 Hz AC: 50/60 Hz
Reaction to input circuit interruption Low fail safe: output voltage < 200 mA,
output current < 400 μA -
Supply circuits K-M DC versions AC versions
Supply voltage 24 V DC 110-240 V AC 50/60 Hz 12-30 V DC
Supply voltage tolerance -15...+15 % -15...+10 % -
Power consumption typ 1.5 W typ 1.5 VA -
Indication of operational states
Supply voltage U: green LED -
General data
Ambient temperature range operation / storage 0...+60 °C / -20...+80 °C -20...+60 °C / -40...+80 °C
Temperature coeffi cient ± 500 ppm/°C 300 ppm/°C
Degree of protection (DIN 40050) IP20
Mounting position ventilation slots on top and bottom
Mounting DIN rail (IEC/EN 60715), snap-on mounting
Electrical connection
Wire size rigid 0.2-4 mm² (24-12 AWG)
ne-strand with(out) wire end ferrule 0.2-2.5 mm² (24-14 AWG)
Stripping length 7 mm (0.28 inch)
Tightening torque 0.5 Nm (4.4 lb.in)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic eld
(HF radiation resistance)
IEC/EN 61000-4-3 10 V/m
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 ±2 kV / ±1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission EN 61000-6-4 Class B
Isolation data
Test voltage (between all isolated circuits) 2.5 kV AC
Rated insulation voltage - 250 V AC
1) includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
Approvals ...................................... 5/3
5/26 
2CDC110004C0207
5
Analog signal converters
CC-U/I, CC-U/V
Technical data
Type CC-U/I CC-U/V
Input circuits - Analog inputs J-G-H any current signals,
RMS measurement
any voltage signals
,
RMS measurement
Rated input range 0-1 A
0-5 A
0-100 V, 0-200 V
0-300 V, 0-400 V
0-500 V, 0-600 V
Measuring frequency 0-600 Hz
Overload capacity of
inputs
input range 1 10 x INom (10 A) for max. 2 s -
input range 2 10 x INom (50 A) for max. 2 s -
Gain adjustment range ±15 %
Offset adjustment range ±20 %
Input impedance / resistance 1A: 60 m,
5 A: 12 m> 800 k
Output circuits - Analog outputs D-F, A-C Current Voltage
Output signal 0-20 mA, 4-20 mA
0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V
Output load 600  4.7 K
Accuracy1) ±0.5 % of full-scale
Temperature coeffi cient ±250 ppm/°C max. ±300 ppm/°C max.
Residual ripple < 0.15 %
Response time 150 ms
Supply circuits K-M
Rated supply voltage 24-48 V DC 110-240 V AC
Supply voltage range 24-48 V DC, 24 V AC 110-240 V AC, 100-300 V DC
Supply voltage tolerance DC: -15...+15 % AC: -15...+10 %
Rated frequency 0 Hz or 50/60 Hz
Power consumption 2 W at 24 V DC 4.5 VA at 230 V AC
Indication of operational states
Supply voltage U: green LED
General data
Ambient temperature range operation / storage -20...+60 °C / -40...+80 °C
Mounting position any
Mounting DIN rail (IEC/EN 60715), snap-on mounting / screw mounting with adapter
Electrical connection
Wire size rigid plug-connector with screw terminals 0.2-2.5 mm2 (24-12 AWG)
ne-strand with(out) wire end ferrule plug-connector with screw terminals 0.2-2.5 mm2 (24-12 AWG)
Stripping length 7 mm (0.28 inch)
Tightening torque 0.4 Nm (3.5 lb.in)
Standards
Product standard -
Low Voltage directive 2006/95/EG
EMC directive 2004/108/EG
RoHS directive 2002/95/EG
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD)
IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic eld
(HF radiation resistance)
IEC/EN 61000-4-3 10 V/m
fast transients (Burst)
IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge)
IEC/EN 61000-4-5 2 kV / 1 kV
HF line emission
IEC/EN 61000-4-6 10 V
Interference emission
EN 61000-6-4 Class B
Isolation data
Insulation voltage (between all isolated circuits) 1.5 kV
Test voltage (between all isolated circuits) 1.5 kV / 50 Hz
1) includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
Approvals ...................................... 5/3
 5/27
2CDC110004C0207
5
.039
2CDC 282 024 F0b06
J
DF
G
M
H
LK
AC
E
B
2CDC 282 023 F0b06
CC-E/x CC-E IAC/ILPO, CC-E I/I
CC-U/x , CC-U/xR
22.5
0,88 "
2CDC 282 011 F0b06
18
0.71"
2CDC 282 012 F0b06
2CDC 282 025 F0b06
1.0
0.9
0.8
0.7
0.6
0.5
F
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos
2CDC 282 014 F0b06
2CDC 282 026 F0b06
Analog signal converters
CC-E, CC-U
Technical diagr., Connection diagr., Dimensional drawings
Dimensional drawings Dimensions in mm
Connection diagram CC-U/x
Width 22.5 mm (0.89 in)
Technical diagrams
Load limit curves CC-U/xxR
Resistive AC load Resistive DC load
Derating curve
5/28 
2CDC110004C0207
5
Notes