CORCOM Product Guide
Lower Current Three Phase RFI Filters
Specifications
Maximum leakage current, each line-to-ground:
3, 6, 10A 20A
@ 120 VAC 60 Hz: 2.0 mA 3.5mA
@ 250 VAC 50 Hz: 3.0 mA 5.5mA
Hipot rating (one minute):
line-to-ground 1500 VAC
line-to-line 1450 VDC
Operating frequency: 50/60 Hz
Rated voltage (max.):
phase-to-phase 440 VAC
phase-to-neutral/ground 250 VAC
Rated current:
03AYO1 3A
06AYO1 6A
10AYO1 10A
20AYO1 20A
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current Frequency-MHz
Rating .15 .5 1 5 10 30
03A 12 23 29 33 38 35
06A 72330405030
10A ––5162815
20A 711322312
Line-to-line in 50 ohm circuit
Current Frequency-MHz
Rating .15 .5 1 5 10 30
03A 12 20 50 35 30
06A 10 18 24 31 28 28
10A 10 18 24 42 28 22
20A 10 18 24 42 38 23
18 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.cor.com
Revised 03-04 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject 1-508-992-4495
are metric equivalents. to change. Germany: 49-89-6089-0
AYO Series
AYO Series
UL Recognized
CSA Certified
VDE Approved
The AYO series filters are designed for 3-phase, four wire,
WYE applications providing filtering in each of the three
lines plus neutral.
These lower current RFI filters provide filtering to industrial
3-phase applications.
Electrical Schematic
NN
LINE LOAD
AYO1
CORCOM Product Guide
Lower Current Three Phase RFI Filters (Continued)
Case Dimensions
Part No. ABCDE
(max) (max) (max) ±.015 (max)
±.38
AYO 3.37 2.07 1.53 2.938 3.35
85.6 52.5 38.7 74.63 85.1
Part Numbers
03AYO1
06AYO1
10AYO1
20AYO1
19
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.cor.com
Revised 03-04 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject 1-508-992-4495
are metric equivalents. to change. Germany: 49-89-6089-0
RFI Power Line Filters
AYO Series
Case Style
A
B
C
D
E
Typical dimensions:
Terminals: .250 [6.35] (9)
Holes: .07 [1.8] Dia.(8)
Slot: .07 x .16 [1.8 x 4.1]
Mounting holes: .188 [4.78] Dia.(2)