NA-4
NAP series
High-voltage pulses high-attenuation type
NAP -10 -472 -O
Ordering information
1 Model Name
2 Rated Current
3 Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code Leakage Current
(Input 125/250V 60Hz)
Line to ground
capacitor
(nominal value)
000 5 A/ 10 A max Not Provided
101 12.5 A/ 25 A max 100pF
221 25 A/ 50 A max 220pF
331 37.5 A/ 75 A max 330pF
471 50 A/ 100 A max 470pF
681 75.5 A/ 150 A max 680pF
102 0.13 mA/ 0.25mA max 1000pF
222 0.25
mA/
0.5 mA max 2200pF
332 0.38 mA/ 0.75mA max 3300pF
472 0.5 mA/
1.0 mA max 4700pF
* When the line to ground capacitor code is
different, the attenuation characteristic is
different.
4 Options
D
:DIN rail installation type
*
The dimensions change when the option is set.
Refer to External view.
R
1 2 3 4
Features of NAP series
Circuit Diagram Derating Curve
LINE
Case
: Mounting Plate
1
24
3
CY : Line to ground capacitor
LOAD
High-voltage pulses high-attenuation type
- Single Phase 250 VAC
- Push down type terminal block
9050 60 70 80
20
0
-4040-30-20
100
80
60
40
55
Ambient Temperature [C]
Load Factor [%]
Specifications
No. Items NAP-04-472 NAP-06-472 NAP-10-472 NAP-16-472 NAP-20-472 NAP-30-472
1Rated Voltage[V] AC 1f 250 / DC250
2 Rated Current[A] 4 6 10 16 20 30
3 Test Voltage (Terminal-Mounting Plate) 2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MW min at room temperature and humidity
5 Leakage current 125/250V 60Hz 0.5mA/1.0mA max
6 Voltage drop 1.0V max
7 Safety agency approval temperatures -25 to +85C (Refer to Derating Curve)
8 Operating temperature -40 to +85C (Refer to Derating Curve)
9 Operating humidity 20 to 95%RH (Non condensing)
10 Storage temperature/humidity -40 to +85C/20 to 95%RH (Non condensing)
11 Vibration 10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact 196.1m/s2 (20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (At only AC input)
14 Case size (without projection) /Weight
53X41X92 mm [2.09X1.61X3.62 inches] (WXHXD) /300g max (Option : -D refer to external view)
DIN rail installation type is optionThe terminal cover is retracted inside the unit