CONTROLS CONTROLS SR SERIES UNDER VOLTAGE RELAY UL listed * * * * CSA recognized Multiple AC/DC Voltages 5 to 20% Hysteresis Adjustment Automatic Operation Adjustable Threshold Threshold hysteresis R 0 t The voltage threshold SR Relay controls a voltage supply which is its own supply. The output relay is energized when the supply (effective for AC) exceeds the selected threshold. It de-energizes when the controlled supply falls below (5 to 20% Hysteresis) of the supply voltage or when the input power breaks. Hysteresis is controlled by a potentiometer and its selection does not change the chosen threshold. Pulses or drops of 100ms or less are ignored. SPECIFICATIONS: Input . . . . . . . . . . . . . . . . . . . . . . . .12 VDC, 24 VAC, 24 VDC, 48 VAC 48 VDC, 110 VAC, 220 VAC, 50/60 Hz -20% to +30% DC, -30% to +15% AC Maximum power consumption . . .24 VAC: 1.5 VA 24 VDC: .6 W . . . . . . . . . . . . . . . . . . . . . . . . . . . .48 VAC: 2 VA 24 VDC: .8 W . . . . . . . . . . . . . . . . . . . . . . . . . . . .110 VAC: 5 VA 48 VDC: 1.8 W 220 VAC: 11 VA Residual ripple . . . . . . . . . . . . . . .