System Power and Expansion
B-116 Programmable Controller CJ1
CPU Rack Configuration Checklist
JCPU Rack Configuration
Item Products Requirements
CJ1 Series
CPU Rack
CJ1 Series CPU
(Provided with 1 End Cover as a
standard accessory.)
One of each Module required for every CPU Rack.
CJ1 Series Power Supply Unit
CJ1 Series Basic I/O Module Total number of Modules: 10 Modules max.
CJ1 Series Special I/O Module (Mounting 11 or more Modules will result in a fatal error.)
CJ1 Series CPU Bus Module
End Cover (CJ1W-TER01) Required on the right-hand side of CJ1 Series CPU Racks. (One End Cover is
provided with each CPU as a standard accessory. Not mounting an End Cover on
the right-hand side of the CPU Rack will result in a fatal error.)
Memory Card Install as required.
I/O Control Module
(CJ1W-IC101)
Required for connection to CJ1 Series Expansion Racks. Connect to the right-hand
side of the CPU Rack.
I/O Connecting Cable Required for connecting CPU Racks to Expansion Racks.
JProducts Used in CPU Racks
Item Model Specifications
CJ1 Series
CPUs
CJ1H-CPU66H I/O bits: 2,560 (3 Expansion Racks), program capacity: 120K steps, LD execution time: 0.02 µs, Data
Memory: 256K words (DM: 32K words, EM: 32K words x 7 banks)
CJ1H-CPU65H I/O bits: 2,560 (3 Expansion Racks), program capacity: 60K steps, LD execution time: 0.02 µs, Data
Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks)
CJ1G-CPU45H I/O bits: 1,280 (3 Expansion Racks), program capacity: 60K steps, LD execution time: 0.04 µs, Data
Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks)
CJ1G-CPU44H I/O bits: 1,280 (3 Expansion Racks), program capacity: 30K steps, LD execution time: 0.04 µs, Data
Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)
CJ1G-CPU43H I/O bits: 960 (2 Expansion Racks), program capacity: 20K steps, LD execution time: 0.04 µs,
Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)
CJ1G-CPU42H I/O bits: 960 (2 Expansion Racks), program capacity: 10K steps, LD execution time: 0.04 µs,
Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)
CJ1M-CPU23 I/O bits: 640 (1 Expansion Rack), program capacity: 20K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs
CJ1M-CPU22 I/O bits: 320 (No Expansion Racks), program capacity: 10K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs
CJ1M-CPU21 I/O bits: 160 (No Expansion Racks), program capacity: 5K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs
CJ1M-CPU13 I/O bits: 640 (1 Expansion Rack), program capacity: 20K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM)
CJ1M-CPU12 I/O bits: 320 (No Expansion Racks), program capacity: 10K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM)
CJ1M-CPU11 I/O bits: 160 (No Expansion Racks), program capacity: 5K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM)
Battery Set CPM2A-BAT01 Can also be used with CPM2A and CQM1H PLCs.
This battery cannot be used for CS1 Series PLCs.
CJ1W-BAT01 Can be used with CJ1M only.
This battery cannot be used for CJ1G/H or CS1 Series PLCs.
CJ1 Series
CJ1W-PA205R 100 to 240 VAC (with RUN output); output capacity: 5 A, 5 VDC
Power
CJ1W-PA202 100 to 240 VAC; output capacity: 2.8 A, 5 VDC
CJ1W-PD025 24 VDC; Output capacity: 5 A, 5 VDC
I/O Control
Module
CJ1W-IC101 Used to connect a CJ1 Series Expansion Rack to a CJ1 Series CPU Rack. Connect to the right-hand
side of the CPU. Connect to an I/O Interface Module mounted on a CJ1 Series Expansion Rack using
a CS1/CJ1 Series Connecting Cable.
End Cover CJ1W-TER01 Required on the right-hand side of CJ1 Series CPU Racks. (Not mounting an End Cover on the
right-hand side of the CPU Rack will result in a fatal error.)
Note: One is provided with CPUs and I/O Interface Modules as a standard accessory.
Din Track
PFP-50N Length: 50 cm; height: 7.3 mm
and
PFP-100N Length: 1 m; height: 7.3 mm
PFP-100N2 Length: 1 m; height: 16 mm
PFP-M There are two locking clips provided with each CPU and I/O Interface Module as standard accessories
to secure the Modules on the DIN Track.