Power+INNOVATION SOLUTIONS SUPPORT RELIABILITY
ALPHA SERIES
Alpha Datasheet - Document Number 69698 - Rev 3.3 October 08
1
INPUT
Input Voltage
Alpha 400 90 - 264Vac
Alpha 600 90 - 264Vac, 160 - 358Vdc
Alpha 1000 85 - 264Vac, 120 - 360Vdc
Alpha 1500 85 - 264Vac (1000W below 150Vac input)
Input Frequency 47 - 63Hz (440Hz with reduced PFC - consult factory)
Inrush Current <50A at 25°C and 264Vac (cold start)
Input Fuse
250Vac HBC Fast Acting (not user accessible)
10A for 400W
12A for 600W
20A for 1000W and 1500W
Leakage Current 1.1mA max at 264Vac & 63Hz
Lower Leakage Option see configuring guide
Power Factor 0.99 typical
OUTPUT
Voltage / Current See module output table
Turn on Delay 1.5s max at 90Vac (150Vac for Alpha 1500W) & 100% rated output power
Rise Time <50ms to 90% of voltage, monotonic rise above 10%
Turn on Overshoot <5% or 250mV Load type dependant, no overshoot with resistive load
Efficiency 75% typical at 230Vac & 100% rated power, config dependent
Hold up 15ms min at 90Vac & 100% rated output power
13ms for 1000W, 8ms for 1500W and at 207Vac for 1500W
Ripple & Noise <2% (or 100mV if greater) Pk- Pk, using EIAJ test method & 20MHz bandwidth
Voltage Accuracy <1% of set Voltage
Remote Sense Yes Standard on single output modules
Minimum Load No on any output
Temperature Coefficient <0.02% of rated voltage per °C
Load Regulation <0.5% or 25mV for 0-100% load change (with sense connected, <2% without)
Line Regulation <0.5% for 90 - 264Vac input change (210-264Vac for 1500W)
Cross Regulation <0.2% for 100% load change on any other output
Transient Response Recovery <10% of set voltage for 50% load change (above 25% load)
500µs for recovery to 1% or 100mV of set voltage (1000µs for S module)
Over Voltage Protection Standard for all outputs
Over Current Protection Standard for all outputs
Short Circuit Protection <150% of rated current, when output voltage <1%
Over Temperature Protection Yes Shuts down all outputs. Cycle ac off / on to reset
Note shutdown temp varies according to ambient, output power and input V
Up to 1500W output
Up to 16 outputs
Voltages up to 48V, Current up to 300 Amps
Fast-on output connection
Worldwide approvals & CB report
Medical Approval Option
3 Year Warranty
Key Market Segments & Applications
Instrumentation Broadcast
Medical ATE
Automation Industrial Computing
Security Lifesciences/Laboratory
Network Servers and Routers
Alpha
400, 600, 1000 & 1500 Watts Modular
ALPHA SERIES
Alpha Datasheet - Document Number 69698 - Rev 3.3 October 08
2
ENVIRONMENT
Temperature 0°C to 70°C operational, -40° to 85°C storage (max 12 months)
Derating 50°C to 70°C derate each output by 2.5% per °C
Low Temperature Start-up -20°C
Humidity 5-95% RH non condensing
Shock 3000 shocks, each of 10g(16ms) half sine
Vibration 10 - 200Hz @ 1.5g
Altitude 3,000 metres operational (15,000 metres non operational)
Pollution Degree 2, Material group 3
IP Rating IP 10
IMMUNITY
Criteria
Electrostatic Discharge EN61000-4-2 Level 4 Air discharge 15kV
Contact discharge 8kV A
Electromagnetic Field EN61000-4-3 Level 3 10V/m (tested to 12V/m) A
Fast / Burst Transient EN61000-4-4 Level 4
Input 4kV
Outputs 2kV,
Tested at 5kHz and 100kHz
A
Surge Immunity EN61000-4-5 Level 3 Line to Line (Differential) 1.1kV
Line to Earth (Common Mode) 2.2kV A
Conducted RF Immunity EN61000-4-6 Level 3 10V (tested to 12V) A
Power Frequency Magnetic Field EN61000-4-8 Level 4 30A Continuous A
Voltage Dips, Variation,
Interruptions EN61000-4-11 Class 3 A
B for 5s interruptions
Voltage Fluctuations EN61000-4-14 Class 3 For 100 to 240V nominal A
SAFETY APPROVALS
Date Amendments Date Amendments
EN 60950-1 2001 IEC 60601-1a1988 A1, A2
UL 60950-1 2003 UL 60601-1a2003
CSA22.2 No 60950-1 2003 CSA 60601-1a2003
IEC60950-1* 2001 CE Mark LV Directive 2006/95/EC (EN60950-1)
* CB Certificate and report available on request a - Only for LL, RL and TL leakage variants. CA400 + CA1000 only
EMISSIONS
Radiated Electric Field EN55022 Class B (as per CISPR.22)
Class A for Alpha 1000/1500
See application note for details.
Only for ‘S’ type leakage versions
Conducted Emissions EN55022 Class B (as per CISPR.22)
Class A for Alpha 1000/1500
Only for ‘S’ type leakage versions.
‘M’ & ‘L’ types meet Class A
Conducted Harmonics EN61000-3-2: 2001 Compliant to Class A
Flicker EN61000-3-3: 1995 + A1:2001 Compliant - dmax only.
ISOLATION
Input to Output Reinforced 4.3 kV (dc) Output to Earth Operational 500 V (dc)
Input to Earth Basic 2.3 kV (dc) Output to Output Operational 500 V (dc)
PRODUCT, GENERIC & COLLATERAL STANDARDS
Low Voltage Power Supply, EMC EN61204-3: 2001 Compliant to High
Severity Immunity Class A emissions for CA1000 / CA1500
Medical Electrical Equipment, EMC EN61601-1-2: 2001 Compliant Class A emissions for CA1000 / CA1500
Immunity for residential, commercial and
light industrial environments EN61000-6-1: 2001 Compliant
Immunity for industrial environments EN61000-6-2: 2001 Compliant
Emissions for residential, commercial and
light industrial environments EN61000-6-3: 2001 Compliant CA1000 and CA1500 not compliant
Emissions for industrial environments EN61000-6-4: 2001 Compliant
ALPHA SERIES
Alpha Datasheet - Document Number 69698 - Rev 3.3 October 08
3
OUTPUT VOLTAGES (single output modules) (twin output modules)
Module Adjustment Amps Slots Module V1 Adjustment Amps V2 Adjustment Amps Slots
A4.5 -5.5 60 2E5 - 16 8 5 - 16 8 1
AA 4.5 -6.5 60 2EB 4.5 -5.5 94.5 -5.5 9 1
B4.5 -5.5 25 1EQ 4.5 -5.5 92.7 -3.9 9 1
BB 4.5 -6.5 25 1H18 -32 518 -32 5 1
C5 - 16 16a1P18 -29 5 5 - 16 8 1
D18 -29 8 1
F9 - 16 33 2
G17.5 -29 25b2
a) 12A max above 12V
b) 21A max above 24.5V
c) Derate output current by 0.25A / V above 40V
d) 1A max above 29V
J30 -48 10c2
K18 -29 15 2
L1.8 -3.2 25 1
M5 - 16 8 1
N18 -32 5d1
Q2.7 -3.9 25 1
R2.7 -3.9 60 2
S2.5 -5.7 85 2
T1.8 -3.2 60 2
U10 -21 16 1
W4.5 -5.5 15 1
Z4.5 -5.5 25 1
The extensive range of output modules and options make it possible to achieve many combinations of Volts and Amps. To achieve
the optimum configuration, please contact our sales office. However you can also create your own configuration from this datasheet
by using the guide below.
Configuring from Datasheet
1Calculate total output power to determine Alpha 400W, 600W, 1000W or 1500W and select converter, then select required
Cooling and Leakage Current from the following table:-
2Select Output Modules and Options from the Output Voltages tables.
Example - if you require 5.2V / 18A with output inhibit : -
a) select B as closest match for voltage and current and prefix with voltage (e.g. 5.2B)
b) add suffix for option (if required)
‘_PA’ for parallel/current share (for N+1 redundant applications)
‘_PP’ for parallel (increase current from one PSU)
‘_IN’ for inhibit
‘_RP’ for remote programming
‘_MF’ (only applicable on 1st module) for global inhibit, ac fail and 5V/50mA standby supply
c) repeat for other outputs
Ensure that the total width of all selected modules is within the slots for the chosen converter. For example:-
CA600LL 5A 12/12E 24D which represents a four output 600W Alpha with Forward air, 240µA Earth Leakage, with:-
Output 1 = 5V / 60A with remote sense
Output 2 = 12V / 8A
Output 3 = 12V / 8A
Output 4 = 24V / 8A with remote sense
3Contact TDK-Lambda to validate configuration and issue a part number.
Alpha Configuring Guide
Output
Power
400 (5 slots)
600 (5 slots)
1000 (7 slots)
1500 (8 slots)
Cooling
empty Forward air - Standard
QFaForward air - Quiet fan
RAbReverse air
Earth Leakage
Current
(at 264Vac, 63Hz)
empty Standard 1.1 mA
ML 500µA
LL 240µA
RL 110µA
TL 50µA
CA 400 QF LL
Notes:
a) CA400/600 only. CA400 derates to 300W, CA600 derates to 475W
b) Contact sales office for details
ALPHA SERIES
Alpha Datasheet - Document Number 69698 - Rev 3.3 October 08
4
4
5
6
1
2
3
Pin IN option PA option PP option RP option MF option
1n/c +Sense + Sense + Sense Inhibit (low)
2Module Good Module Good n/c - Sense 5V supply
3Inhibit Star point n/c Control 2 Power Fail
4n/c - Sense - Sense n/c 0V
5- Power - Power n/c Control 1 Inhibit (high)
6- Power Star point n/c n/c n/c
Alpha 400
Alpha 600
+
-
+
-
+
-
+
-
+
-
+
-
6
5
4
3
2
1
Remote sense
1 slot, 2 output 1 slot, 1 output 2 slot, 1 output
MF option
IN, PA,
PP, RP
Option
Option Connections
ALPHA SERIES
Alpha Datasheet - Document Number 69698 - Rev 3.3 October 08
5
Alpha 1000
Alpha 1500
ALPHA SERIES
Alpha Datasheet - Document Number 69698 - Rev 3.3 October 08
6
TDK-LAMBDA EMEA
FRANCE
TDK-LAMBDA FRANCE SAS Telephone: +33 (0) 1 60 12 71 65
ZAC des Delaches, BP1077 - Gometz le Chatel Facsimile: +33 (0) 1 60 12 71 66
91940 Les Ulis Web: www.lambda-f.com
GERMANY
TDK-LAMBDA GERMANY GmbH Telephone: +49 (0) 78 41 666 0
Karl-Bold-Straße 40 Facsimile: +49 (0) 78 41 5000
D-77855 Achern Web: www.lambda-germany.com
ISRAEL
NEMIC LAMBDA LTD Telephone: +972 (0) 3 902 4333
Kibbutz Givat Facsimile: +972 (0) 3 902 4777
Hashlosha 48800 Web: www.nemic.co.il
ITALY
TDK-LAMBDA ITALYs.r.l. Telephone: +39 (0) 02 61 29 38 63
Via dei Lavoratori 128/130, Facsimile: +39 (0) 02 61 29 09 00
20092, Cinisello Balsamo (Mi) Web: www.lambda-italy.com
SWEDEN
TDK-LAMBDA SCANDINAVIA Telephone: +46 (0) 8 598 94 090
PO Box 546, Rallervägen 41 Facsimile: +46 (0) 8 540 66 096
SE-184 25. Åkersberga Web: www.lambda-scandinavia.com
UK
TDK-LAMBDA UK Telephone: +44 (0) 1271 856666
Kingsley Avenue Facsimile: +44 (0) 1271 864894
Ilfracombe Devon EX34 8ES Web: www.lambda-gb.com
AUSTRIA
TDK-LAMBDA GERMANY GmbH Telephone: +43 (0) 2256 655 84
Aredstraße 22 Facsimile: +43 (0) 2256 645 12
A-2544 Leobersdorf Web: www.lambda-austria.com
TDK-LAMBDA NORTH AMERICA
TDK-LAMBDA ASIA
LOCAL DISTRIBUTION
visit http://us.tdk-lambda.com/ for a list of TDK-Lambda offices and distributors
visit http://www.tdk-lambda.com/ for a list of TDK-Lambda offices and distributors
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
TDK-Lambda:
CA400 H47271