https://www.phoenixcontact.com/us/products/2811116
06/27/2020Page3/6
Voltage measuring transducers-MCR-VDC-UI-B-DC-2811116
Technical data
Output data
Ripple < 50 mVPP
Power supply
Supply voltage range 18.5 VDC ... 30.2 VDC
Max. current consumption < 50 mA
General
Maximum transmission error < 1 % (of final value)
Maximum temperature coefficient < 0.015 %/K
Limit frequency (3 dB) 40 Hz
Frequency measuring range 40 Hz ... 70 Hz
Alignment zero ± 20 %
Alignment span ± 20 %
Step response (10-90%) 12 ms
Overvoltage category II
Degree of pollution 2
Test voltage input/output 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Color green
Housing material Polyamide PA non-reinforced
Configuration INTERBUS
Conformance CE-compliant
UL, USA/Canada cULus
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Connection in acc. with standard CUL
Conformance CE-compliant
UL, USA/Canada cULus
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings