PM4S PM4S Timers MULTI-RANGE ANALOG TIMER Features RoHS Directive compatibility information http://www.nais-e.com/ 1. Economic pricing that promptly reflects market demands Remarkable economic pricing is implemented in pursuit of cost performance. 2. Output contacts switchable between timed out 2C and timed out 1C/Instantaneous 1C The timed out 1C/Instantaneous 1C output contact enables the efficient addition of self-maintenance circuits. 3. 4 different time ranges selectable on a single unit Five types of timers cover the full range of time settings from 1 second to 30 hours. 4. Equipped with zero-setting instantaneous output Set the dial all the way to "0" for instantaneous operation, so circuit testing can be easily accomplished. 5. Compliant with UL, c-UL and CE. Product types Type /////// Contact arrangement Time range PM4S Multi-range Timer A type 1s/10s/1min/10min (4 time ranges selectable) PM4S Multi-range Timer B type 3s/30s/3min/30min (4 time ranges selectable) PM4S Multi-range Ttimer C type Power ON-delay T.D.: Timed-out 2C INST.: Timed-out 1C Instantaneous 1C (Selected by front switch) 6s/60s/6min/60min (4 time ranges selectable) PM4S Multi-range Timer D type 1min/10min/1h/10h (4 time ranges selectable) PM4S Multi-range Timer E type 3min/30min/3h/30h (4 time ranges selectable) Operating voltage 100 to 120V AC 200 to 240V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 12V DC 24V DC Parts name * The PM4S Multi-Range timer allows time units and output contacts to be selected via front switches. Output contact selector Time range selector Time unit selector All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. Part No. PM4S-A2C10M-AC120V PM4S-A2C10M-AC240V PM4S-A2C10M-DC12V PM4S-A2C10M-DC24V PM4S-A2C30M-AC120V PM4S-A2C30M-AC240V PM4S-A2C30M-DC12V PM4S-A2C30M-DC24V PM4S-A2C60M-AC120V PM4S-A2C60M-AC240V PM4S-A2C60M-DC12V PM4S-A2C60M-DC24V PM4S-A2C10H-AC120V PM4S-A2C10H-AC240V PM4S-A2C10H-DC12V PM4S-A2C10H-DC24V PM4S-A2C30H-AC120V PM4S-A2C30H-AC240V PM4S-A2C30H-DC12V PM4S-A2C30H-DC24V PM4S Specifications Type PM4S Multi-range Timer Item Rated operating voltage Rated frequency 100 to 120V AC Rated power consumption Output rating Operating mode Rating Time accuracy Note) A type B type Time range C type D type E type Operating time fluctuation Setting error Voltage error Temperature error Contact arrangement Contact Contact resistance (Initial value) Contact material Mechanical (contact) Electrical (contact) Allowable operating voltage range Life Insulation resistance (Initial value) Electrical function Breakdown voltage (Initial value) Min. power off time Max. temperature rise Functional Destructive Functional Destructive Vibration resistance Mechanical function Shock resistance Operating condition Others Ambient temperature Ambient humidity Atmospheric pressure Ripple factor (DC type) Weight 200 to 240V AC 12V DC 24V DC 50/60 Hz -- Approx. 3.0VA/3.6VA Approx. 5.6VA/6.8VA (at 100V AC) (at 200V AC) Approx. 1.3W Approx. 1.7W Approx. 4.5VA/5.25VA Approx. 7.5VA/9.8VA (at 120V AC) (at 240V AC) 5A 250V AC (resistive load) Power ON-delay 1s/10s/1min/10min (4 time ranges selectable) 3s/30s/3min/30min (4 time ranges selectable) 6s/60s/6min/60min (4 time ranges selectable) 1min/10min/1h/10h (4 time ranges selectable) 3min/30min/3h/30h (4 time ranges selectable) 1% (power off time change at the range of 0.1s to 1h) 5% (Full-scale value) 1% (at the operating voltage changes between 85 to 110%) 2% (at 20C ambient temp. at the range of -10 to +50C +14 to +122F) T.D.: Timed-out 2 Form C INST.: Timed-out 1 Form C, instantaneous 1 Form C (Selected by front switch) Max. 100m (at 1A 6V DC) Silver alloy Min. 107 Min. 105 (at raed control capacity) 85 to 110% of rated operating voltage Min. 100M Between live and dead metal parts (At 500V DC) Between input and output Between contacts of different poles Between contacts of same pole 2,000Vrms for 1 min Between live and dead metal parts 2,000Vrms for 1 min Between input and output 2,000Vrms for 1 min Between contacts of different poles 1,000Vrms for 1 min Between contacts of same pole 100 ms 55C 131F 10 to 55Hz: 1 cycle/min double amplitude of 0.25mm (10min on 3 axes) 10 to 55Hz: 1 cycle/min double amplitude of 0.375mm (1h on 3 axes) Min. 98m/s2 (4 times on 3 axes) Min. 980m/s2 (5 times on 3 axes) -10 to +50C +14 to +122F 30 to 85%RH (non-condensing) 860 to 1,060hPa 20% Approximately 110 g 3.880 oz Notes) 1. Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20C 68F ambient temperature, and 1s power off time. 2. For the 1s range, the tolerance for each specification becomes 10ms. Applicable standard Safety standard EN61812-1 (EMI)EN61000-6-4 Radiation interference electric field strength Noise terminal voltage (EMS)EN61000-6-2 Static discharge immunity EMC Pollution Degree 2/Overvoltage Category III EN55011 Group1 ClassA EN55011 Group1 ClassA EN61000-4-2 RF electromagnetic field immunity EN61000-4-3 EFT/B immunity EN61000-4-4 Surge immunity Conductivity noise immunity Power frequency magnetic field immunity Voltage dip/Instantaneous stop/Voltage fluctuation immunity EN61000-4-5 EN61000-4-6 EN61000-4-8 EN61000-4-11 4 kV contact 8 kV air 10 V/m AM modulation (80 MHz to 1 GHz) 10 V/m pulse modulation (895 MHz to 905 MHz) 2 kV (power supply line) 1 kV (power line) 10 V/m AM modulation (0.15 MHz to 80 MHz) 30 A/m (50 Hz) 10 ms, 30% (rated voltage) 100 ms, 60% (rated voltage) 1,000 ms, 60% (rated voltage) 5,000 ms, 95% (rated voltage) All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4S Dimension (Unit: mm inch) Tolerance: 0.5 .020 * Surface mount dimensions 14.5 .571 48 1.890 5.5 .217 63.7 2.508 102.2 4.024 14.2 .559 DIN rail terminal block AT8-DF8K (Sold separately) 44.5 1.752 * Panel mount dimensions (with mounting frame) Device installation rail AT8-DLA1 (Sold separately) * Panel cut out dimensions Standard cut out dimensions are shown below. Use mounting frame (AT8-DA4) and rubber gasket (ATC18002). Mounting frame AT8-DA4 (Sold separately) 45+0.6 0 1.772+.024 0 Min. 80 3.150 45+0.6 0 1.772+.024 0 50 1.969 Min. 80 3.150 * Adjacent mounting 84.7 3.335 Rear terminal socket AT78041 (Sold separately) Panel (Thickness 1 to 3.5 mm .039 to .138 inch) 45+0.6 0 1.772+.024 0 A A = (48xn-2.5)+0.6 0 A = (1.890xn-.098)+.024 0 * Terminal layouts and wiring diagrams NC T. D. I N S T. 3 4 NO 4 3 4 MODE 1 1 NC NO 5 3 6 2 7 1 8 COM T.D.: Timed-out 2 Form C INST.: Timed-out 1 Form C, instantaneous 1 Form C * Selected by front switch Notes: 1. Operating voltage signs in parentheses ( ) indicate the polarity of the DC type. COM 2. is a time delay contact. Operating voltage is an instantaneous contact. Operation mode 1. T.D. mode 2. INST. mode Power supply Time out (N.O. contact) 1-3 or 6-8 OP.LED OFF ON ON OFF T Power supply T ON OFF Time out (N.O. contact) 6-8 ON ON OFF OFF Time out (N.O. contact) 1-3 OP.LED All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. Note: Keep 0.1s or more for power off time. PM4S Precautions during usage 4. In order to maintain the characteristics, do not remove the timer case. 5. When installing the panel, use the ATA4811 mounting frame (Sold separately). 6. If you change the operating voltage, be sure not to allow leak current into the timer. 7. Avoid leaving the unit powered continuously. Leaving the unit powered up with output set to ON continuously for a long period of time (about 1 month or more) will wear out the electronic components. If you will be keeping it powered continuously, combine with a relay to create the circuit shown below: 1. Avoid locations subject to flammable or corrosive gases, excessive dust, oil, vibrations, or excessive shocks. 2. Since the main-unit is made of polycarbonate resin, avoid contact with or use in environments containing methyl alcohol, benzene, thinners, and other organic solvents; and ammonia, caustic sodas, and other alkaline substances. 3. Power supply superimposed surge protector Although a surge protector will withstand standard-waveform voltage with the values in the next table, anything above this will destroy the internal circuit. You should therefore use a surge absorber. 12 V DC 24 V DC 500 V 100 to 120 V AC 200 to 240 V AC 4,000 V R T R * Surge waveform [(1.2x50) s uni-polar full wave voltage] R 8. The timer setting dial should only be turned within the range indicated on the dial face. Turning it too far may break the stopper and cause damage to internal components. T Acquisition of CE marking Please abide by the conditions below when using in applications that comply with EN61812-1. 1. Overvoltage category III, pollution level 2 2. The load connected to the output contact should have basic insulation. This timer is protected with basic insulation and can be doubleinsulated to meet EN/IEC requirements by using basic insulation on the load. 3. Please use a power supply that is protected by an overcurrent protection device which complies with the EN/ IEC standard (example: 250 V 1 A fuse, etc.). 4. You must use a terminal socket or socket for the installation. Do not touch the terminals or other parts of the timer when it is powered. When installing or un-installing, make sure that no voltage is being applied to any of the terminals. 5. Do not use this timer as a safety circuit. For example when using a timer in a heater circuit, etc., provide a protection circuit on the machine side. All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-A/S/M PM4H-A PM4H-S PM4H-M DIN48 SIZE MULTI-RANGE ANALOG TIMER UL File No.: E122222 CSA File No.: LR39291 Features 48 1.890 62.5 2.461 48 1.890 mm inch Pin type Screw terminal type 1. 100-240V AC free-voltage input, 48-125V DC type available 2. Short body -- 62.5mm 2.461 inch (screw terminal type) 3. Front panel of IP65 type is protected against water-splash and dust 4. Built-in Screw terminals Screw terminal type is used for easy wiring and reducing additional cost for accessories. 5. 0 setting instantaneous output operation 6. Multiple time ranges -- 1 s to 500 h (Max.) 7. 8 different operation modes: (PM4H-A) 8. Compliant with UL/CSA, CE and LLOYD RoHS Directive compatibility information http://www.nais-e.com/ Product types Type Contact arrangement Operation mode Time range Protective construction Rated operating voltage 100 to 240V AC 48 to 125V DC IP65 PM4H-A 8 operation modes * Pulse ON-delay * Pulse Flicker * Pulse ON-flicker * Differential ON/OFF-delay (1) (2) * Signal OFF-delay * Pulse One-shot * Pulse One-cycle 24V AC/DC 12V DC Relay Timed-out 2 Form C 100 to 240V AC 48 to 125V DC IP50 24V AC/DC 12V DC 100 to 240V AC 48 to 125V DC IP65 24V AC/DC PM4H-S Power ON-delay Relay Timed-out 2 Form C 12V DC 16 selectable ranges 1s to 500h 100 to 240V AC 48 to 125V DC IP50 24V AC/DC 12V DC 100 to 240V AC 48 to 125V DC IP65 PM4H-M 5 operation modes (With instantaneous contact) * Power ON-delay * Power Flicker * Power ON-flicker * Power One-shot * Power One-cycle 24V AC/DC Relay Timed-out 1 Form C Instantaneous 1 Form C 12V DC 100 to 240V AC 48 to 125V DC IP50 24V AC/DC 12V DC Terminal type Part number 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal PM4HA-H-AC240VW PM4HA-H-AC240VSW PM4HA-H-DC125VW PM4HA-H-DC125VSW PM4HA-H-24VW PM4HA-H-24VSW PM4HA-H-DC12VW PM4HA-H-DC12VSW PM4HA-H-AC240V PM4HA-H-AC240VS PM4HA-H-DC125V PM4HA-H-DC125VS PM4HA-H-24V PM4HA-H-24VS PM4HA-H-DC12V PM4HA-H-DC12VS PM4HS-H-AC240VW PM4HS-H-AC240VSW PM4HS-H-DC125VW PM4HS-H-DC125VSW PM4HS-H-24VW PM4HS-H-24VSW PM4HS-H-DC12VW PM4HS-H-DC12VSW PM4HS-H-AC240V PM4HS-H-AC240VS PM4HS-H-DC125V PM4HS-H-DC125VS PM4HS-H-24V PM4HS-H-24VS PM4HS-H-DC12V PM4HS-H-DC12VS PM4HM-H-AC240VW PM4HM-H-AC240VSW PM4HM-H-DC125VW PM4HM-H-DC125VSW PM4HM-H-24VW PM4HM-H-24VSW PM4HM-H-DC12VW PM4HM-H-DC12VSW PM4HM-H-AC240V PM4HM-H-AC240VS PM4HM-H-DC125V PM4HM-H-DC125VS PM4HM-H-24V PM4HM-H-24VS PM4HM-H-DC12V PM4HM-H-DC12VS If you use this timer under harsh environment, please order above sealed type (IP65 type). IP65 type -- Protection dust and water jet splay on the front face. All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-A/S/M Time range Time unit sec Scale 1 5 10 Control time range min hrs 10h 1.0h to 10h 0.1s to 1s 0.1 min to 1 min 0.1h to 1h 0.5s to 5s 0.5 min to 5 min 0.5h to 5h 5h to 50h 1.0s to 10s 1.0 min to 10 min 1.0h to 10h 10h to 100h 5s to 50s 5 min to 50 min 5h to 50h 50h to 500h 50 PM4H-A/PM4H-S/PM4H-M All types of PM4H timer have multi-time range. 16 time ranges are selectable. 1s to 500h (Max. range) is controlled. Note: 0 setting is for instantaneous output operation. Specifications Type Item Rated operating voltage Rated frequency Rated power consumption Rated control capacity Rating Operating mode Time range Operating time fluctuation Time Setting error accuracy Note:) Voltage error Temperature error Contact arrangement Contact Life Contact resistance (Initial value) Contact material Mechanical (contact) Electrical (contact) Allowable operating voltage range Insulation resistance (Initial value) Electrical function Breakdown voltage (Initial value) Min. power off time Max. temperature rise Vibration resistance Mechanical function Operating condition Others Shock resistance Functional Destructive Functional Destructive Ambient temperature Ambient humidity Atmospheric pressure Ripple factor (DC type) Protective construction Weight PM4H-A PM4H-S 100 to 240V AC, 48 to 125V DC, 12V DC, 24V AC/DC 50/60Hz common (AC operating type) Approx. 10VA (100 to 240V AC) Approx. 2.5VA (24V AC) Approx. 1.5W (12V DC, 24V DC, 48 to 125V DC) 5A 250V AC (resistive load) PM4H-M Pulse ON-delay Power ON-delay Pulse Flicker Power Flicker Pulse ON-Flicker Power ON-flicker Power ON-delay Differential ON/OFF-delay (1) (2) Power One-shot Signal OFF-delay Power One-cycle Pulse One-shot (with instantaneous contact) Pulse One-cycle 1s to 500h (Max.) 16 time ranges switchable 0.3% (power off time change at the range of 0.1s to 1h) 5% (Full-scale value) 0.5% (at the operating voltage changes between 85 to 110%) 2% (at 20C ambient temp. at the range of -10 to +50C +14 to +122F) Timed-out 1 Form C Timed-out 2 Form C Instantaneous 1 Form C Max. 100m (at 1A 6V DC) Silver alloy Au flash on Silver alloy 2x107 105 (at rated control capacity) 85 to 110% of rated operating voltage (at 20C coil temp.) Between live and dead metal parts Between input and output Min. 100M (At 500V DC) Between contacts of different poles Between contacts of same pole 2,000Vrms for 1 min Between live and dead metal parts 2,000Vrms for 1 min Between input and output 2,000Vrms for 1 min Between contacts of different poles 1,000Vrms for 1 min Between contacts of same pole 100ms 55C 131F 65C 149F 10 to 55Hz: 1 cycle/min double amplitude of 0.25mm (10min on 3 axes) 10 to 55Hz: 1 cycle/min double amplitude of 0.375mm (1h on 3 axes) Min. 98m/s2 (4 times on 3 axes) Min. 980m/s2 (5 times on 3 axes) -10 to +50C +14 to +122F 30 to 85%RH (at 20C 68F, non-condensing) 860 to 1,060hPa 20% IP65 on front panel (using rubber gasket ATC18002) 100g 3.527 oz (Pin type) 110g 3.880 oz (Screw terminal type) Note: 1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20C 68F ambient temperature, and 1s power off time. 2) For the 1s range, the tolerance for each specification becomes 10ms. All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-A/S/M Terminal layouts and Wiring diagrams PM4H-A Pin type * Timed-out 2 Form C PM4H-S Pin type * Timed-out 2 Form C Screw terminal type * Timed-out 2 Form C Screw terminal type * Timed-out 2 Form C Reset input Start input Stop input N.C. N.O. 4 3 2 (-) N.C. N.O. 6 N.C. 5 6 7 1 11 7 8 9 1 8 9 10 Operating voltage N.O. 11 N.O. 2 3 4 4 5 3 2 5 Stop input (+) (+) Reset input Start input Operating voltage (-) N.C. N.C. N.C. N.O. 10 (-) N.C. N.O. 6 N.O. 7 8 9 10 N.C. N.O. 11 6 7 1 1 8 Operating voltage (+) (+) 2 3 4 5 Operating voltage (-) 1) DC Type PM4H-M Pin type * Timed-out 1 Form C * Instantaneous 1 Form C 4 5 3 2 (-) Pin Screw terminal Connect the terminal to negative PM4H-A (-), and the terminal to positive (+). Connect the terminal x to negative (-), and the terminal PM4H-S Connect the terminal to negative z to positive (+). PM4H-M (-), and the terminal to positive (+). N.C. N.C. N.O. Type Screw terminal type * Timed-out 1 Form C * Instantaneous 1 Form C N.O. N.C. N.O. 6 1 8 9 10 N.C. N.O. 2) Contact 2 3 4 5 Timed-out contact 1 8 Operating voltage 7 11 6 7 (+) (+) Operating voltage Instantaneous contact 3) Voltage should not be applied to the various inputs (reset, start, and stop) of (-) the PM4H-A multi-range timer. These inputs should be input without voltage. Parts name PM4H-S PM4H-A Power indicator LED PM4H-M Output indicator LED Hand Time indicator window Time unit indicator Time range selector 16 time settings selectable (1 s to 500 h) 1s 5s 10s 50s 1min 5min 10min 50min 1h 5h 10h 50h 10h 50h 100h 500h Set dial Operation mode indicator Operation mode selector Instantaneous output area When the hand is in this area, instantaneous operation starts. Selectable from 8 operation modes ON : Pulse ON-delay FL : Pulse Flicker FO : Pulse ON-flicker OF1 : Differential ON/OFF-delay (1) SF : Signal OFF-delay OS : Pulse One-shot OF2 : Differential ON/OFF-delay (2) OC : Pulse One-cycle All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. Operation mode selector Selectable from 5 operation modes ON : Power ON-delay FL : Power flicker FO : Power ON-flicker OS : Power One-shot OC : Power One-cycle PM4H-A/S/M mm inch Tolerance: 0.5 .020 Dimensions * PM4H- Screw terminal type (Flush mount) Pin type (Flush mount/Surface mount) 41 dia. 1.614 dia. 48 1.890 44.5 1.752 * Panel mount dimensions (with mounting frame) Screw terminal type Rubber gasket ATC 18002 (attached) 6.0 12.0 .236 .472 48 1.890 62.5 2.461 66.5 2.618 48 1.890 44.5 1.752 Pin type Rubber gasket ATC18002 Panel Panel Mounting frame AT8-DA4 (Sold separately) 48 1.890 44.5 1.752 66 2.598 1 .039 50 1.969 50 1.969 Mounting frame AT8-DA4 (attached) 48 1.890 14.5 41 dia. 1.614 dia. 6.0 12.0 .236 .472 48 1.890 48 1.890 61.5 2.421 66 2.598 72.5 2.854 (8-pin) 78 3.071 (11-pin) 48 1.890 Rear terminal socket AT78041 (8-pin: sold separately) AT78051 (11-pin: sold separately) * Surface mount dimensions Pin type * Panel cut out dimensions Din rail socket AT8-DF8K (8-pin: sold separately) AT8-DF11K (11-pin: sold separately) Mounting rail AT8-DLA1 97.3 (8-pin) 3.831 104.0 (11-pin) 4.094 Standard cut out dimensions are shown below. Use mounting frame (AT8-DA4) and rubber gasket (ATC18002). 45+0.6 0 1.772+.024 0 * Adjacent mounting 45+0.6 0 1.772+.024 0 Min. 80 3.150 A A = (48xn-2.5)+0.6 0 A = (1.890xn-.098)+.024 0 45+0.6 0 1.772+.024 0 Min. 80 3.150 Note) 1. The proper thickness of mounting panel is between 1 to 5mm. 2. Adjacent mount is less water-resistant. All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-A/S/M Operation mode LED lighting LED flickering T: Setting time t1, t2, ta, tb 100g 3.527 oz (Pin type), 110g 3.880 oz (Screw terminal type) Notes: 1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage, 20C 68F ambient temperature, and 1s power off time. 2) For the 2s range, the tolerance for each specification becomes 10ms. 3) Between contacts of different poles for PM4H-SDM type only. All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-SD/SDM Time range Time range unit Operating (s) Time range 2 10 20 100 - switching time (s) 0.04 0.1 0.3 0.5 0.7 0.2 to 2 1 to 10 2 to 20 10 to 100 Product types Operation mode Type PM4H-SD Star ( )-Delta () switching PM4H-SDM Star ( )-Delta () switching (Instantaneous contact) PM4H-SD Star ( )-Delta () switching Contact arrangement Time range Protective Rated operating construction voltage 100 to 240V AC Relay Timed-out side: 1 Form A side: 1 Form A 24V AC IP65 Star ( )Delta () switching Relay Timed-out side: 1 Form A side: 1 Form A Instantaneous: 1 Form A Relay Timed-out side: 1 Form A side: 1 Form A 100 to 240V AC 4 selectable ranges over 2s to 100s ( - switching time: 0.04, 0.1, 0.3, 0.5, 0.7s) 24V AC 100 to 240V AC 24V AC IP50 PM4H-SDM Star ( )-Delta () switching (Instantaneous contact) Relay Timed-out side: 1 Form A side: 1 Form A Instantaneous: 1 Form A 100 to 240V AC 24V AC Terminal type 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal Part number PM4HSD-S-AC240VW PM4HSD-S-AC240VSW PM4HSD-S-AC24VW PM4HSD-S-AC24VSW PM4HSDM-S-AC240VW PM4HSDM-S-AC240VSW PM4HSDM-S-AC24VW PM4HSDM-S-AC24VSW PM4HSD-S-AC240V PM4HSD-S-AC240VS PM4HSD-S-AC24V PM4HSD-S-AC24VS PM4HSDM-S-AC240V PM4HSDM-S-AC240VS PM4HSDM-S-AC24V PM4HSDM-S-AC24VS Terminal layouts and Wiring diagrams Pin type Screw terminal type * No instantaneous contact 4 5 3 2 * With instantaneous contact 4 5 6 7 3 2 1 8 Operating voltage * No instantaneous contact 6 6 7 7 8 9 * With instantaneous contact 10 1 2 3 4 5 Operating voltage side time-delay contact side time-delay contact Instantaneous contact (PM4H-SDM type) mm inch Dimensions 6.0 .236 12.0 .472 48 1.890 66.5 2.618 14.5 .571 44.5 1.752 41 dia. 1.614 dia. Operation Power supply Instantaneous contact side Contact t1: ( side Contact t2: t3: t1 t2 t3 7 8 9 1 2 3 4 10 11 5 1 8 Operating voltage 48 1.890 6 11 ( operation time indicator LED lights) - switching time operation time indicator LED lights) All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. Operating voltage side time-delay contact side time-delay contact Instantaneous contact (PM4H-SDM type) PM4H SERIES MODES AND TIME SETTING 1. Operation method 1) Operation mode setting [PM4H-A type] 8 operation modes are selectable with operation mode selector. Turn the operation mode selector with screw driver. Operation mode is shown up through the window above the mode selector. The marks are ON , FL , FO , OF1 , SF , OS , OF2 , OC . Turn the mode selector to the mark until you can check by clicking sound. Confirm the mode selector position if it is correct. If the position is not stable, the timer might mis-operate. 2) Time range setting [PM4H series common] 16 time ranges are selectable between 1s to 500h. Turn the time range selector with the screw driver. Clockwise turning increases the time range, and Counter-clockwise turning decrease the time range. Confirm the range selector position if it is correct. If the position is not stable, the timer might mis-operate. 2. How to use "Set ring" [PM4H series common] 2) Time range setting 1) Fixed time setting Example: Time range 20s to 30s. Set the desired time and put 2 set rings together. Shorter time value setting Insert the rings into stopper to fix the Set the dial to 20s. time. Place the stop ring at the right side of stopper. Stopper boss Stopper 3) Time setting [common] To set the time, turn the set dial to a desired time within the range. Instantaneous output will be on when the dial is set to "0". When the instantaneous output is used, the dial should be set under "0" range. (Instantaneous output area) When power supply is on, the time range, setting time and operation mode cannot be changed. Turn off the power supply or a reset signal is applied to set the new operation mode. If the position is not stable, the timer might mis-operate. Longer time value setting Set the dial to 30s. Place the stop ring at the left side of stopper. Set range Shorter time value Longer time value Stopper boss Set ring (2 pcs) ATC18001 (sold separately) Stop ring 20 Set dial 0 30 0 SEC SEC Note) The stoppers for the lower limit setting set ring and the upper limit setting set ring face the opposite directions. Applicable standard (PM4H series common) Safety standard EN61812-1 (EMI)EN61000-6-4 Radiation interference electric field strength Noise terminal voltage (EMS)EN61000-6-2 Static discharge immunity RF electromagnetic field immunity EMC EFT/B immunity Surge immunity Conductivity noise immunity Power frequency magnetic field immunity Voltage dip/Instantaneous stop/Voltage fluctuation immunity Pollution Degree 2/Overvoltage Category III EN55011 Group1 ClassA EN55011 Group1 ClassA EN61000-4-2 4 kV contact 8 kV air EN61000-4-3 10 V/m AM modulation (80 MHz to 1 GHz) 10 V/m pulse modulation (895 MHz to 905 MHz) EN61000-4-4 2 kV (power supply line) 1 kV (signal line) EN61000-4-5 1 kV (power line) EN61000-4-6 10 V/m AM modulation (0.15 MHz to 80 MHz) EN61000-4-8 30 A/m (50 Hz) EN61000-4-11 10 ms, 30% (rated voltage) 100 ms, 60% (rated voltage) 1,000 ms, 60% (rated voltage) 5,000 ms, 95% (rated voltage) All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-F DIN48 SIZE ANALOG MULTIRANGE POWER OFF-DELAY TIMERS PM4H-F UL File No.: E122222 CSA File No.: LR39291 Features 1. Switch operation times between three types of time ranges of 1 s to 10 s and 1 min to 10 min. 2. Instantaneous reset available. 3. The shorter body makes it easier to use. 4. Compliant with UL, CSA, CE and LLOYD. 48 1.890 48 1.890 62.5 2.461 mm inch RoHS Directive compatibility information http://www.nais-e.com/ Specifications Type Item Rated operating voltage Rated frequency Rating Time accuracy *1 Contact Life Rated power consumption Rated control capacity Operation mode Time range Operation time fluctuation Setting error Voltage error Temperature error Contact arrangement Contact resistance (Initial value) Contact material Mechanical (contact) Electrical (contact) Allowable operating voltage range Insulation resistance (Initial value) Electrical function Breakdown voltage (Initial value) Min. power supply width Min. reset time Max. temperature rise Vibration resistance Mechanical function Operating condition Others Shock resistance Functional Destructive Functional Destructive Ambient temperature Ambient humidity Atmospheric pressure Ripple factor (DC type) Protective construction Weight PM4H-F8R PM4H-F11R 100 to 120V AC, 200 to 240V AC, 24V AC, 12V DC, 24V DC 50/60Hz common (AC operating type) Approx. 1.6VA (100 to 120V AC, 200 to 240V AC), Approx. 2.3VA (24V AC) Approx. 1.1W (12V DC, 24V DC) 3A 250V AC (resistive load) Power OFF-delay Power OFF-delay (with reset) 1s to 10s: 3 range switchable 1 min to 10 min: 3 range selectable 0.3% 5% (Full-scale value) 0.5% (at the operating voltage changes between 85 to 110%) 2% (at 20C ambient temp. at the range of -10 to +50C +14 to +122F) Timed-out 2 Form C Timed-out 1 Form C Timed-out 2 Form C Max. 100m (at 1A 6V DC) Au flash on Silver alloy 107 5 10 (at rated control capacity) 85 to 110% of rated operating voltage (at 20C coil temp.), 90 to 110% (DC Type) Between live and dead metal parts Between input and output Min. 100M (At 500V DC) Between contacts of different poles (*3) Between contacts of same pole 1,500Vrms for 1 min Between live and dead metal parts 1,500Vrms for 1 min Between input and output 1,000Vrms for 1 min Between contacts of different poles (*3) 750Vrms for 1 min Between contacts of same pole s range type: 100ms min range type: 2s 50ms 55C 131F 10 to 55Hz: 1 cycle/min double amplitude of 0.25mm (10min on 3 axes) 10 to 55Hz: 1 cycle/min double amplitude of 0.375mm (1hr on 3 axes) Min. 98m/s2 (4 times on 3 axes) Min. 980m/s2 (5 times on 3 axes) -10 to +50C +14 to +122F 30 to 85%RH (non-condensing) 860 to 1,060hPa 20% IP65 on front panel (using rubber gasket ATC18002) 100g 3.527 oz (Pin type), 110g 3.880 oz (Screw terminal type) PM4H-F8 *Notes: 1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20C 68F ambient temperature. 2) For the 1s range, the tolerance for each specification becomes 10ms. When the power goes on, in rush current (0.3A) flows. Cautions should be taken. The minimum power supplying time after forced reset input is 2s or more. 3) Between contacts of different pools for PM4H-F8, PM4H-F11R types only. All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-F Time range Time range unit Time range 1 5 10 s range type min range type 0.04s to 1s 0.2s to 5s 0.4s to 10s 0.04 min to 1 min 0.2 min to 5 min 0.4 min to 10 min Product types Type Operation mode Contact arrangement Time range 3 selectable time ranges over 1s to 10s 3 selectable time ranges over 1 min to 10 min PM4H-F8 Power OFF-delay (without reset) Relay Timed-out 2 Form C 3 selectable time ranges over 1s to 10s 3 selectable time ranges over 1 min to 10 min 3 selectable time ranges over 1s to 10s PM4H-F8R Power OFF-delay (with instantaneous reset) 3 selectable time ranges over 1 min to 10 min Relay Timed-out 1 Form C 3 selectable time ranges over 1s to 10s 3 selectable time ranges over 1 min to 10 min Protective Rated operating construction voltage 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC IP65 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC IP50 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC IP65 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC IP50 100 to 120V AC 200 to 240V AC 24V AC 12V DC 24V DC Terminal type 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins 8 pins All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. Part number PM4HF8-S-AC120VW PM4HF8-S-AC240VW PM4HF8-S-AC24VW PM4HF8-S-DC12VW PM4HF8-S-DC24VW PM4HF8-M-AC120VW PM4HF8-M-AC240VW PM4HF8-M-AC24VW PM4HF8-M-DC12VW PM4HF8-M-DC24VW PM4HF8-S-AC120V PM4HF8-S-AC240V PM4HF8-S-AC24V PM4HF8-S-DC12V PM4HF8-S-DC24V PM4HF8-M-AC120V PM4HF8-M-AC240V PM4HF8-M-AC24V PM4HF8-M-DC12V PM4HF8-M-DC24V PM4HF8R-S-AC120VW PM4HF8R-S-AC240VW PM4HF8R-S-AC24VW PM4HF8R-S-DC12VW PM4HF8R-S-DC24VW PM4HF8R-M-AC120VW PM4HF8R-M-AC240VW PM4HF8R-M-AC24VW PM4HF8R-M-DC12VW PM4HF8R-M-DC24VW PM4HF8R-S-AC120V PM4HF8R-S-AC240V PM4HF8R-S-AC24V PM4HF8R-S-DC12V PM4HF8R-S-DC24V PM4HF8R-M-AC120V PM4HF8R-M-AC240V PM4HF8R-M-AC24V PM4HF8R-M-DC12V PM4HF8R-M-DC24V PM4H-F Type Operation mode Contact arrangement Protective Rated operating construction voltage Time range 100 to 120V AC 200 to 240V AC 24V AC IP65 12V DC 24V DC 3 selectable time ranges over 1s to 10s 100 to 120V AC 200 to 240V AC 24V AC IP50 12V DC PM4H-F11R Power OFF-delay (with instantaneous reset) 24V DC Relay Timed-out 2 Form C 100 to 120V AC 200 to 240V AC 24V AC IP65 12V DC 24V DC 3 selectable time ranges over 1 min to 10 min 100 to 120V AC 200 to 240V AC 24V AC IP50 12V DC 24V DC Terminal type 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 11 pins Screw terminal 6.0 .236 * Pin type (Flush mount/surface mount) 62.5 2.461 48 1.890 44.5 1.752 48 1.890 12.0 .472 6.0 .236 66.5 2.618 41 dia. 1.614 dia. 48 1.890 12.0 .472 41 dia. 1.614 dia. 48 1.890 All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4HF11R-S-AC120VW PM4HF11R-S-AC120VSW PM4HF11R-S-AC240VW PM4HF11R-S-AC240VSW PM4HF11R-S-AC24VW PM4HF11R-S-AC24VSW PM4HF11R-S-DC12VW PM4HF11R-S-DC12VSW PM4HF11R-S-DC24VW PM4HF11R-S-DC24VSW PM4HF11R-S-AC120V PM4HF11R-S-AC120VS PM4HF11R-S-AC240V PM4HF11R-S-AC240VS PM4HF11R-S-AC24V PM4HF11R-S-AC24VS PM4HF11R-S-DC12V PM4HF11R-S-DC12VS PM4HF11R-S-DC24V PM4HF11R-S-DC24VS PM4HF11R-M-AC120VW PM4HF11R-M-AC120VSW PM4HF11R-M-AC240VW PM4HF11R-M-AC240VSW PM4HF11R-M-AC24VW PM4HF11R-M-AC24VSW PM4HF11R-M-DC12VW PM4HF11R-M-DC12VSW PM4HF11R-M-DC24VW PM4HF11R-M-DC24VSW PM4HF11R-M-AC120V PM4HF11R-M-AC120VS PM4HF11R-M-AC240V PM4HF11R-M-AC240VS PM4HF11R-M-AC24V PM4HF11R-M-AC24VS PM4HF11R-M-DC12V PM4HF11R-M-DC12VS PM4HF11R-M-DC24V PM4HF11R-M-DC24VS mm inch Toletance: 0.5 .020 Dimensions * Screw terminal type (Flush mount) Part number 14.5 .571 44.5 1.752 PM4H-F Terminal layouts and Wiring diagrams * PM4H-F8 (without reset input) Pin type Time-out 2 Form C N.C. N.C. N.O. 4 5 3 2 (-) * PM4H-F8R (with reset input) Pin type Time-out 1 Form C, with reset input N.C. N.O. 4 5 6 7 3 2 Reset input 1 8 Operating voltage * PM4H-F11R (with reset input) Pin type Time-out 2 Form C, with reset input (+) (-) Screw-tightening pin type The PM4H-F11R should be used for the timelimit 2C. Reset input N.O. N.C. N.C. 6 7 5 6 7 N.O. 4 3 2 1 8 Operating voltage 1 11 N.O. 8 9 10 Operating voltage (+) (-) Screw-tightening pin type The PM4H-F11R should be used for the timelimit 1C and to connect reset input. (+) Screw terminal type Time-out 2 Form C, with reset input N.C. N.O. 6 7 8 9 10 N.C. N.O. 11 1 (+) 2 3 Operating voltage 4 5 Reset input (-) PM4H-F (with reset) input conditions 1. Contact input (pin type example) PM4H-F8R 2. Non-contact input (pin type example) PM4H-F11R PM4H-F11R Reset input Reset input PM4H-F8R Use a contact with good contact reliability for the input. Contact bounce can lead to erroneous operation of the timer, so use a contact with short bounce time. Make the resistance between terminals for a short circuit less than 1k-ohms. Make the resistance between terminals for an open circuit greater than 100k-ohms. Photo-coupler Reset input Reset input Check that Vce = 0.6V Max. when ON. Photo-coupler Operation * PM4H-F8 (without reset input) * PM4H-F8R/F11R (with reset input) Note: Tr Tr Note: Ts Tr Ts Power supply Power supply T Time-delay contact N.O. Reset input Time-delay contact N.C. Time-delay contact N.O. T Be sure to use a photocoupler for non-contact input. t Time-delay contact N.C. t 120g 4.233 oz (Pin type), 130g 4.586 oz (Screw terminal type) Notes: 1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20C 68F ambient temperature, and 1s power off time. 2) For the 1s range, the tolerance for each specification becomes 10ms. 3) As internal components may become worn when using continuous conduction, the product should be replaced periodically. All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PM4H-W Time range All types of PM4H-W timer have multi-time range. 16 time ranges are selectable. 1s to 500h (Max. range) is controlled. Time unit sec Scale 1 5 Control time range 10 50 min hrs 10h 1.0h to 10h 0.1s to 1s 0.1 min to 1 min 0.1h to 1h 0.5s to 5s 0.5 min to 5 min 0.5h to 5h 5h to 50h 1.0s to 10s 1.0 min to 10 min 1.0h to 10h 10h to 100h 5s to 50s 5 min to 50 min 5h to 50h 50h to 500h Product types Operating mode Type Contact arrangement Time range Protective structure Rated Operating voltage 100 to 240V AC 48 to 125V DC IP65 24V AC/DC Relay Timed-out 2 Form C Cyclic (OFF-start, Twin) PM4H-W Twin timer 12V DC 16 selectable ranges (1s to 500h) 100 to 240V AC 48 to 125V DC IP50 24V AC/DC 12V DC Terminal type 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal 8 pins Screw terminal Part number PM4HW-H-AC240VW PM4HW-H-AC240VSW PM4HW-H-DC125VW PM4HW-H-DC125VSW PM4HW-H-24VW PM4HW-H-24VSW PM4HW-H-DC12VW PM4HW-H-DC12VSW PM4HW-H-AC240V PM4HW-H-AC240VS PM4HW-H-DC125V PM4HW-H-DC125VS PM4HW-H-24V PM4HW-H-24VS PM4HW-H-DC12V PM4HW-H-DC12VS Terminal layouts and Wiring diagrams Pin Type Screw terminal type Cyclic timed-out relay contact: 2C Cyclic timed-out relay contact: 2C N.C. N.C. N.O. 4 5 3 2 (-) N.C. N.O. 6 N.O. 7 8 9 10 N.C. N.O. 11 6 7 1 2 3 4 5 1 8 Operating voltage (+) (+) Operating voltage (-) mm inch Toletance: 0.5 .020 Dimensions * Screw terminal type: M3.5 * Pin type 48 1.890 6.0 17.0 .236 .670 48 1.890 62.5 2.461 41 1.614 48 1.890 44.5 1.752 48 1.890 41 1.614 6.0 17.0 .236 .670 Operation Power supply T1 T2 T1 Time-delay contact (N.O. contact) Time-delay contact (N.C. contact) Output ON-OFF indicator : : T1: T2: Output OFF indicator (green) Output ON indicator (orange) OFF set time ON set time All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. 66.5 2.618 14.5 .571 44.5 1.752 PM4H SERIES MODES AND TIME SETTING 1. Operation method 1) Operation mode setting [PM4H-A type] 8 operation modes are selectable with operation mode selector. Turn the operation mode selector with screw driver. Operation mode is shown up through the window above the mode selector. The marks are ON , FL , FO , OF1 , SF , OS , OF2 , OC . Turn the mode selector to the mark until you can check by clicking sound. Confirm the mode selector position if it is correct. If the position is not stable, the timer might mis-operate. 2) Time range setting [PM4H series common] 16 time ranges are selectable between 1s to 500h. Turn the time range selector with the screw driver. Clockwise turning increases the time range, and Counter-clockwise turning decrease the time range. Confirm the range selector position if it is correct. If the position is not stable, the timer might mis-operate. 2. How to use "Set ring" [PM4H series common] 2) Time range setting 1) Fixed time setting Example: Time range 20s to 30s. Set the desired time and put 2 set rings together. Shorter time value setting Insert the rings into stopper to fix the Set the dial to 20s. time. Place the stop ring at the right side of stopper. Stopper boss Stopper 3) Time setting [common] To set the time, turn the set dial to a desired time within the range. Instantaneous output will be on when the dial is set to "0". When the instantaneous output is used, the dial should be set under "0" range. (Instantaneous output area) When power supply is on, the time range, setting time and operation mode cannot be changed. Turn off the power supply or a reset signal is applied to set the new operation mode. If the position is not stable, the timer might mis-operate. Longer time value setting Set the dial to 30s. Place the stop ring at the left side of stopper. Set range Shorter time value Longer time value Stopper boss Set ring (2 pcs) ATC18001 (sold separately) Stop ring 20 Set dial 0 30 0 SEC SEC Note) The stoppers for the lower limit setting set ring and the upper limit setting set ring face the opposite directions. Applicable standard (PM4H series common) Safety standard EN61812-1 (EMI)EN61000-6-4 Radiation interference electric field strength Noise terminal voltage (EMS)EN61000-6-2 Static discharge immunity RF electromagnetic field immunity EMC EFT/B immunity Surge immunity Conductivity noise immunity Power frequency magnetic field immunity Voltage dip/Instantaneous stop/Voltage fluctuation immunity Pollution Degree 2/Overvoltage Category III EN55011 Group1 ClassA EN55011 Group1 ClassA EN61000-4-2 4 kV contact 8 kV air EN61000-4-3 10 V/m AM modulation (80 MHz to 1 GHz) 10 V/m pulse modulation (895 MHz to 905 MHz) EN61000-4-4 2 kV (power supply line) 1 kV (signal line) EN61000-4-5 1 kV (power line) EN61000-4-6 10 V/m AM modulation (0.15 MHz to 80 MHz) EN61000-4-8 30 A/m (50 Hz) EN61000-4-11 10 ms, 30% (rated voltage) 100 ms, 60% (rated voltage) 1,000 ms, 60% (rated voltage) 5,000 ms, 95% (rated voltage) All Rights Reserved (c) COPYRIGHT Matsushita Electric Works, Ltd. PRECAUTIONS IN USING THE PM4H SERIES 1. Input connections (PM4H-A type) 1) Be sure not to use terminal as the common terminal of the input signal as shown in Fig. A. Otherwise, the internal circuit of the timer may be damaged. Use terminal as the common terminal as shown in Fig. B. Contact input (or non-contact input) Fig. A 6 5 10 2 Operating voltage Fig. B 6 5 10 2 Operating voltage If the circuits is connected as in Fig. C, the internal circuits must be broken. Be sure to connect the circuit as in Fig. D. Fig. C 10 6 T No good 2. Input signal conditions (PM4H-A type) 1) Connection of contact input (Pin type example Reset input 2 Fig. D Stop input Good Contact input (or non-contact input) 7 Start input No good 7 3) Terminal - (screw terminal x-c) should be connected as the start input. Connect terminals - (screw terminal x-v) for reset signal input. Connect terminals - (screw terminal x-b) for stop signal input. Be sure not to connect with other terminals and apply excessive voltage. The internal circuit will be damaged. 4) The input wiring other than the power supply circuit should avoid these conditions, high-voltage wiring and parallel wiring with power wire. Wire in short with using the shielding wire or metal wiring tube. 5) For start, reset and stop input, use gold-plated contact with high reliability. Since contact bouncing causes errors in the start, use an input contact less bounce time. 6) Keep the minimum signal input time over 0.05 s. 5 6 7 2 10 6 T Good 2 2) When one input signal is simultaneously applied to more than one timer, be sure to avoid the wiring shown in Fig. E. Otherwise, the short-circuit current will flow and cause damage. Be sure to align the polarity of the power supply as shown in Fig. F. Fig. E Use gold-plated contacts with high-reliability. The bounce time at the contacts causes errors in the timer operation time. Accordingly, use start input contact whose bounce time is short. The resistance when shorted should be less than 1k, and when open resistance should be more than 100k. For the screw terminal type, connect the terminal x to the each input signal. 2) Connection of non-contact input (Pin type example) (open-collector) Input terminal 2 10 Fig. F Contact or non-contact input Input terminal 2 10 Good Input terminal 2 32 10 Power supply Stop input Power supply Start input No good 10 Reset input Input terminal 2 5 6 7 2 Apply the open-collector connection. The characteristics of the transistor used must be VCEO=10V or more, IC=10mA or more, and ICBO=6A or less. Additionally, the input impedance must be 1k or less, and the residual voltage must be 0.6V or less. For the screw terminal type, connect the terminal x to the each input signal. 3) Connection of non-contact input (Pin type example) (voltage input) Internal circuit with photoelectric sensor, etc. (The start input is turned on.) 1mA 5 6 7 Q 2 [Example of start input] Even if the open collector is not used, input is also possible from the non-contact circuit of 6 to 30V DC. In this case, the start input is turned on when the signal is turned from H to L. The residual voltage must be 0.6V or less when Q is on. On the AC type, an insulated transformer is required as the power supply for the photoelectric sensor, etc. (power supply for the input devices). Note: Keep the minimum input signal time of each signal to 0.05s or more. 3. Checking the contacts before use (PM4H-F only) When the power ON time is less than the minimum power application time, the contacts may remain in an ON state, so the state of the contacts should be checked before use. When the contacts are in an ON state, activating them once will return them to their normal state (the OFF state after time-out). (Be aware that relay characteristics may result in the contacts being in that same ON state if exposed to excessive vibration and impact during transport.) 4. Time setting To set the time, turn the set dial to a desired time within the range. Instantaneous output will be on when the dial is set to "0". When the instantaneous output is used, the dial should be set under "0" range. (Instantaneous output area) Note) When power supply is on, the time range, setting time and operation mode cannot be changed. Turn off the power supply or a reset signal is applied to set the new operation mode. If the position is not stable, the timer might mis-operate. PRECAUTIONS IN USING THE PM4H SERIES 5. Superimposed surge of power supply (PM4H series common) For the superimposed surge of power supply, the standard waveform is taken as the standard value for surge-proof voltage. If external surge occurs exceeding the specified value, the internal circuit may break down. In this case, use a surge absorption element. Operation voltage 100 to 240V AC 100 to 120V AC 200 to 240V AC 48 to 125V DC 12V DC, 24V DC 24V AC/DC Surge voltage 4,000V 500V The positive and negative voltages are applied each five times between the power pins. The typical surge absorption elements include a varistor, a capacitor, and a diode. If a surge absorption element is used, use an oscilloscope to see whether or not the foreign surge exceeding the specified value appears. 6. Acquisition of CE marking Please abide by the conditions below when using in applications that comply with EN61812-1. 1) Overvoltage category III, pollution level 2 2) This timer employs a power supply without a transformer, so the power and input signal terminals are not insulated. (PM4H-A only) (1) When a sensor is connected to the input circuit, install double insulation on the sensor side. (2) In the case of contact input, use dualinsulated relays, etc. 3) The load connected to the output contact should have basic insulation. This timer is protected with basic insulation and can be double-insulated to meet EN/IEC requirements by using basic insulation on the load. 4) Please use a power supply that is protected by an overcurrent protection device which complies with the EN/IEC standard (example: 250 V 1 A fuse, etc.). 5) You must use a terminal socket or socket for the installation. Do not touch the terminals or other parts of the timer when it is powered. When installing or un-installing, make sure that no voltage is being applied to any of the terminals. 6) Do not use this timer as a safety circuit. For example when using a timer in a heater circuit, etc., provide a protection circuit on the machine side. 33