Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1
Recovery time 100 ms (on de-energisation)
Immunity to microbreaks <= 10 ms
Power consumption in VA 3 VA at 240 V AC
Power consumption in W 2 W at 240 V DC
Switching capacity in VA 1250 VA
Minimum switching current 10 mA 5 V DC
Maximum switching current 5 A
Maximum switching voltage 250 V AC
Electrical durability 100000 cycles for 2 A at 24 V DC-1
100000 cycles for 5 A at 250 V AC-1
Mechanical durability 10000000 cycles
Rated impulse withstand voltage 5 kV for 1.2...50 µs conforming to IEC 60664-1
Power on delay < 200 ms
Creepage distance 4 kV/3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data B10d = 160000
MTTFd = 171.2 years
Mounting position Any position
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Status LED Green LED backlight (steady) for dial pointer indication
Yellow LED (steady) for output relay energised
Yellow LED (steady) for power ON
Width 22.5 mm
Product weight 0.1 kg
Environment
Dielectric strength 2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation
conforming to IEC 61812-1
Standards IEC 61812-1
UL 508
Directives 2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
Product certifications GL
EAC
RCM
China RoHS
CCC
CE
CSA
UL
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -40...70 °C
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Vibration resistance 20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn (not operating) (duration = 11 ms) conforming to IEC 60068-2-27
5 gn (in operation) (duration = 11 ms) conforming to IEC 60068-2-27
Relative humidity 95 % at 25...55 °C
Electromagnetic compatibility Fast transients immunity test (test level: 1 kV, level 3 - capacitive connecting clip) conforming to IEC
61000-4-4
Surge immunity test (test level: 1 kV, level 3 - differential mode) conforming to IEC 61000-4-5
Surge immunity test (test level: 2 kV, level 3 - common mode) conforming to IEC 61000-4-5
Electrostatic discharge (test level: 6 kV, level 3 - contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge (test level: 8 kV, level 3 - air discharge) conforming to IEC 61000-4-2
2