Product data sheet
Characteristics
RE22R2KMR
Off-delay Timing Relay - 0.05s…10min - 24…
240V AC/DC - 2C/O
Main
Range of product Zelio Time
Product or component type Modular timing relay
Discrete output type Relay
Device short name RE22
Nominal output current 5 A
Complementary
Contacts type and composition 2 C/O timed contact, cadmium free
Time delay type K
Time delay range 3...30 s
30...300 s
0.3...3 s
1...10 s
10...100 s
1...10 min
0.05...1 s
Control type Rotary knob
External potentiometer
[Us] rated supply voltage 24...240 V AC/DC at 50/60 Hz
Release input voltage <= 2.4 V
Voltage range 0.85...1.1 Us
Supply frequency 50...60 Hz (+/- 5 %)
Connections - terminals Screw terminals : 1 x 0.5...1 x 3.3 mm², AWG 20...AWG 12 solid cable without cable end
Screw terminals : 2 x 0.5...2 x 2.5 mm², AWG 20...AWG 14 solid cable without cable end
Screw terminals : 1 x 0.2...1 x 2.5 mm², AWG 24...AWG 14 flexible cable with cable end
Screw terminals : 2 x 0.2...2 x 1.5 mm², AWG 24...AWG 16 flexible cable with cable end
Tightening torque 0.6...1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Jul 18, 2019
1
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1
Recovery time 100 ms (on de-energisation)
Immunity to microbreaks <= 10 ms
Power consumption in VA 3 VA at 240 V AC
Power consumption in W 2 W at 240 V DC
Switching capacity in VA 1250 VA
Minimum switching current 10 mA 5 V DC
Maximum switching current 5 A
Maximum switching voltage 250 V AC
Electrical durability 100000 cycles for 2 A at 24 V DC-1
100000 cycles for 5 A at 250 V AC-1
Mechanical durability 10000000 cycles
Rated impulse withstand voltage 5 kV for 1.2...50 µs conforming to IEC 60664-1
Power on delay < 200 ms
Creepage distance 4 kV/3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data B10d = 160000
MTTFd = 171.2 years
Mounting position Any position
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Status LED Green LED backlight (steady) for dial pointer indication
Yellow LED (steady) for output relay energised
Yellow LED (steady) for power ON
Width 22.5 mm
Product weight 0.1 kg
Environment
Dielectric strength 2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation
conforming to IEC 61812-1
Standards IEC 61812-1
UL 508
Directives 2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
Product certifications GL
EAC
RCM
China RoHS
CCC
CE
CSA
UL
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -40...70 °C
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Vibration resistance 20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn (not operating) (duration = 11 ms) conforming to IEC 60068-2-27
5 gn (in operation) (duration = 11 ms) conforming to IEC 60068-2-27
Relative humidity 95 % at 25...55 °C
Electromagnetic compatibility Fast transients immunity test (test level: 1 kV, level 3 - capacitive connecting clip) conforming to IEC
61000-4-4
Surge immunity test (test level: 1 kV, level 3 - differential mode) conforming to IEC 61000-4-5
Surge immunity test (test level: 2 kV, level 3 - common mode) conforming to IEC 61000-4-5
Electrostatic discharge (test level: 6 kV, level 3 - contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge (test level: 8 kV, level 3 - air discharge) conforming to IEC 61000-4-2
2
Radiated radio-frequency electromagnetic field immunity test (test level: 10 V/m, level 3 - 80 MHz...1
GHz) conforming to IEC 61000-4-3
Conducted RF disturbances (test level: 10 V, level 3 - 0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts (test level: 2 kV, level 3 - direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops (test level: 30 % - 500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops (test level: 100 % - 20 ms) conforming to IEC 61000-4-11
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1650 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product Environmental Profile
Product end of life instructions Available
End of Life Information
3
Product data sheet
Dimensions Drawings
RE22R2KMR
Dimensions
4
Product data sheet
Connections and Schema
RE22R2KMR
Wiring Diagram
5
Product data sheet
Technical Description
RE22R2KMR
Function K: Delay On De-energization without Auxillary Supply
Description
On energisation of power supply, the output(s) R close(s).On de-energisation of power supply, timing period T starts and at the end of this period,
the output(s) R revert(s) to its/their initial state.The energization of power supply > Tk is necessary to sustain the timing period T.
Function: 1 Output
Tk > 1s
Function: 2 Outputs
Tk > 80ms
Legend
Relay de-energised
Relay energised
Output open
Output closed
U - Supply
T - Timing period
R1/R2 -2 timed outputs