1716
Specifications
General Specifications
Pro/Lite (LCD Model/No LCD Model) 12-I/O Type 24-I/O Type 40-I/O Type 48-I/O Type
Part Number H12RC / H12RA
B12RC / B12RA
H24RC / H24RA
B24RC / B24RA
H40RC / H40RKA / H40RSA
B40RC / B40RKA / B40RSA
H48KC / H48SC / H48KA / H48SA
B48KC / B48SC / B48KA / B48SA
Rated Power Voltage AC power: 100 to 240V AC, DC power: 24V DC
Allowable Voltage Range AC power: 85 to 264V AC, DC power: 20.4 to 28.8V DC (including ripple)
Rated Power Frequency AC power: 50 to 60Hz (47 to 63Hz)
Power
Consumption
AC Power 12-I/O: 18VA maximum, 24-I/O: 41VA maximum, 40-I/O: 48VA maximum, 48-I/O: 43VA maximum
DC Power 12-I/O: 4.3W maximum, 24-I/O: 4.8W maximum, 40-I/O: 7.9W maximum, 48-I/O: 6.0W maximum
Allowable Momentary Power Interruption AC power: 20ms maximum; DC power: 10ms maximum
Dielectric Strength
AC power type: Between power/input and PE terminals: 1,500V AC, 5mA, 1 minute
Between transistor output and PE terminals: 1,500V AC, 5mA, 1 minute
Between relay output and PE terminals: 2,300V AC, 5mA, 1 minute
Between power and input terminals: 1,500V AC, 5mA, 1 minute
Between power/input and transistor output terminals: 1,500V AC, 5mA, 1 minute
Between power/input and relay output terminals: 2,300V AC, 5mA, 1 minute
DC power type: Between power/input and FE terminals: 500V AC, 5mA, 1 minute
Between transistor output and FE terminals: 500V AC, 5mA, 1 minute
Between relay output and FE terminals: 2,300V AC, 5mA, 1 minute
Between power/input and transistor output terminals: 500V AC, 5mA, 1 minute
Between power/input and relay output terminals: 2,300V AC, 5mA, 1 minute
EMC Immunity IEC/EN 61131-2:2007 compliant
Inrush Current AC power: 35A maximum (Cold start with Ta=25°C, 200V AC), DC power: 30A maximum (5ms maximum)
Operating Temperature 0 to +55°C Note 1
Storage Temperature –25 to +70°C (no freezing)
Relative Humidity 10 to 95% RH (no condensation)
Pollution Degree 2 (IEC 60664-1)
Corrosion Immunity Atmosphere free from corrosive gases
Degree of Protection IP20 (IEC 60529)
Ground D-type ground (Class 3 ground)
Protective Grounding Conductor UL1007 AWG16
Vibration Resistance 5 to 8.4Hz half amplitude 3.5mm, 8.4Hz to 150Hz acceleration 9.8m/s2(1G), 2 hours per axis on each of three mutually perpendicular axis(IEC 61131-2)
Shock Resistance 147m/s2, 11ms, X, Y, Z directions 3 times (IEC 61131-2)
Mounting Structure DIN rail or direct mount
Weight (approx.) AC Power 12-I/O: 230g, 24-I/O: 400g, 40-I/O: 580g, 48-I/O: 540g
DC Power 12-I/O: 190g, 24-I/O: 310g, 40-I/O: 420g, 48-I/O: 380g
FT1A Version V110 are UL, c-UL Listed at 0 to +50°C.
Touch (PLC + HMI)
Part Number FT1A-*12RA-* FT1A-*14KA-* / FT1A-*14SA-*
Output Relay output Transistor output
Rated Power Voltage 24V DC
Allowable Voltage Range 20.4 to 28.8V DC (including ripple)
Power Consumption 9.2W maximum 10.1W maximum
Allowable Momentary Power Interruption 10ms maximum
Dielectric Strength Between power terminal and FG: 500V AC, 5mA, 1 minute,
Between power terminal and output terminal: 2,300V AC, 5mA, 1 minute
Between power terminal and FG: 500V AC, 5mA, 1 minute,
Between power terminal and output terminal: 500V AC, 5mA, 1 minute
EMC Immunity IEC/EN 61131-2:2007 compliant
Inrush Current 50A maximum (5ms maximum)
Operating Temperature Color display: –20 to +55°C, Monochrome display: 0 to +55°C Note 2
Storage Temperature –20 to +60°C (no freezing)
Relative Humidity 10 to 95% RH (no condensation)
Pollution Degree 2 (IEC 60664-1)
Corrosion Immunity Atmosphere free from corrosive gases
Degree of Protection IP66F, Type 4X & 13 (Panel front) Note 1, IP20 (Rear)
Ground Functional grounding
Protective Grounding Conductor UL1007 AWG16
Vibration Resistance 5 to 8.4Hz half amplitude 3.5mm, 8.4Hz to 150Hz acceleration 9.8m/s2 (1G), 2 hours per axis on each of three mutually perpendicular axis (IEC 61131-2)
Shock Resistance 147m/s2, 11ms, X, Y, Z directions 3 times (IEC 61131-2)
Mounting Structure Panel mount
Weight (approx.) 300g 250g
1. Operation not guaranteed when used with certain types of oils. 2. FT1A-*12RA-* hardware version V130 and earlier is UL, c-UL listed at 0 to +50°C.
Touch (PLC + HMI) Pro/Lite FT1A (LCD Model/No LCD Model)
Part Number
FT1A-*
12RA-*
(Relay)
FT1A-*14KA-* (Sink)
FT1A-*14SA-*(Source)
H12RA
B12RA
H12RC
B12RC
H24RA
B24RA
H24RC
B24RC
H40RKA
H40RSA
B40RKA
B40RSA
H40RC
B40RC
H48KA
H48SA
B48KA
B48SA
H48KC
H48SC
B48KC
B48SC
Control System Stored program system
Instruction
Words
Basic Instructions 42 types
Advanced Instructions 98 types 99 types 98 types 103 types 102 types 110 types 104 types 110 types 109 types
Program Capacity Program size: 47.4KB
Configuration memory capacity: 5MB 12KB 47.4KB
User Program Storage Flash ROM (100,000 times) Built-in Flash ROM (10,000 times rewritable)
Processing
Time
Basic Instruction 1850μs/1,000 steps 950μs/1,000 steps
END Processing 5msec minimum 2ms (Pro) / 640μs (Lite)
Function Block Note 1 37 types 38 types 37 types 38 types 37 types 45 types 39 types 45 types 44 types
Function Block Program Capacity Program size: 38KB
Configuration memory capacity: 5MB 10KB 38KB
No of Function
Blocks
Function Blocks 1,000 200 1,000
Timer (T) / Counter (C) 200 / 200 100 / 100 200 / 200
Processing
Time
Basic Instruction 4ms/100 1.3ms/100
END Processing 5ms minimum 2.5ms (Pro) /1ms (Lite)
I/O Points Inputs / Outputs 8 / 4 8 / 6 8 / 4 16 / 8 24 /16 30 / 18
Analog Input / Output 2 / – 2 / 2 2 / – 4 / – —6 / – —8 / – —
Internal Relays / Shift Registers 1024 / 128 256 / 128 1024 / 128
Data Registers / Special Data Registers 2000 / 200 400 / 200 2000 / 200
Adding/Reversible Counters 200 100 200
Timer (1ms, 10ms, 100ms, 1s) 200 100 200
Clock Precision: ±30 seconds/month (25°C, typical)
RAM
Backup
Backup Data / Backup Duration Internal relays, shift registers, counters, data registers, clock data / Approximately 30 days (typical) at 25°C after backup battery is fully charged
Battery / Charging Time Lithium secondary battery / Approximately 15 hours required to charge from 0 to 90%
Replaceability Not possible
Self-Diagnostic Functions Keep data check, power failure check, clock error check, watchdog timer check, timer/counter preset value change error check, user program syntax check, user
program execution check, system error check, memory cartridge transfer error check (Pro/Lite only)
Input Filter No filter, 3 to 15ms (selectable in increments of 1ms)
Catch Input / Interrupt Input 4 / 4 4 / 4 6 / 6
High-speed
Counter
Maximum
Counting
Frequency
& Points
Single/two-phase
Selectable
1 (5kHz, multiple 2/4, single phase not
available) 2 Note 2 — 2 Note 2 — 2 Note 2 — 2 Note 2 —
Single-phase 4 (x 10kHz) 2 (x
100kHz) — 4 (x
100kHz) — 4 (x 100kHz) — 4 (x
100kHz) —
Counting Range 0 to 4,294,967,295 (32 bits)
Operation Mode Rotary encoder mode and adding counter mode
Analog Voltage
Inputs
Points 2 2 None 4None 6None 8None
Input Range 0 to 10V DC 0 to 10V DC (voltage input)
/4 to 20mA (current input) 0 to 10V DC
Input Impedance 78kΩ 78kΩ (voltage input)
/ 250Ω (current input) 78kΩ
Digital Resolution 0 to 1,000 (10 bits)
Output Type 10A Relay Transistor 10A Relay 10A Relay/Transistor 10A Relay Transistor
Analog Output
Built-in Points —2
—
Output Range —0 to 10V DC (voltage output)
/4 to 20mA (current output)
Digital Resoltuion —0 to 1,000 (10 bits)
Pulse Outputs
100 kHz
No. of
Outputs — — — — — 2 — 2
Function — — — — — PULS, PWM, RAMP,
ARAMP, ZRN —PULS, PWM,
RAMP, ARAMP, ZRN
5 kHz
No. of
Outputs — — — — — 2 — 2
Function — — — — — PULS, PWM — PULS, PWM
External Output
Power Supply for
Sensor
Output Voltage — — — — 24V DC
(+10%,-15%) —24V DC
(+10%, -15%) —24V DC
(+10%, -15%)
Output Current — — — — 250mA — 300mA — 300mA
Overload Detection — — — — Not Available — Not Available — Not Available
Insulation — — — — Internal Circuit —Internal Circuit —Internal Circuit
USB-mini B Note 3 X X X X X
USB-A Note 3 X — — — —
RS232C Note 3 X — X Note 4 X Note 4 X Note 4
RS485/422 Note 3 X — X Note 4 X Note 4 X Note 4
Ethernet X — X X X
Expansion Communication
Ports
Port 2 — — X X X
Port 3 — — — X X
Memory Cartridge — X X X X
SD Memory Card — — — X Note 5 X Note 5
Analog Cartridge
Interface
Number of Ports —4—
Connectable Cards —2—
1. Except for timer, counter, input Function Block, and output Function Block. 2. 100kHZ when single-phase, 50kHz when two-phase multiple 2.4. 3. Not isolcated from internal circuits.
4. When communication cartridge is installed. 5. The maximum capacity is 32 GB. DLOG and TRACE instructions are used to write data.