https://www.phoenixcontact.com/us/products/2814715
01/09/2021Page1/7
Current transducers-MCR-S-1/5-UI-DCI-NC-2814715
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR current transducer, programmable and configurable, for measuring direct, alternating and distorted currents,
input current 0...0.2 to 0...11 A, unconfigured
Your advantages
True r.m.s. value measurement
Device can be set via DIP switches or MCR/PI-CONF-WIN configuration software
3-way isolation
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4017918169275
Weight per Piece (excluding packing) 192.100 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 22.5 mm
Height 99 mm
Depth 114.5 mm
https://www.phoenixcontact.com/us/products/2814715
01/09/2021Page2/7
Current transducers-MCR-S-1/5-UI-DCI-NC-2814715
Technical data
Ambient conditions
Ambient temperature (operation) -20 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude < 2000 m
Degree of protection IP20
Noise immunity EN 61000-6-2
Input data
Input Current measuring input
Number of inputs 3
Configurable/programmable Yes, unconfigured
Input current range 0 A ... 11 A (AC/DC)
Operate threshold 2 % (of measuring range nominal value 1/5/10 A)
Setting range for min. input current 0 A ... 200 mA
Setting range for max. input current 0 A ... 11 A
Impulse form AC, DC or distorted currents
Overload capacity 2 x IN (continuous)
Surge strength 20 x IN (1 s)
Frequency measuring range 15 Hz ... 400 Hz
Connection method Screw connection
Output data
Output name Voltage output / current output
Configurable/programmable Yes, unconfigured
Voltage output signal 0 V ... 10 V
2 V ... 10 V
-10 V ... 10 V
0 V ... 5 V
1 V ... 5 V
-5 V ... 5 V
10 V ... 0 V
10 V ... 2 V
10 V ... -10 V
5 V ... 0 V
5 V ... 1 V
5 V ... -5 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
https://www.phoenixcontact.com/us/products/2814715
01/09/2021Page3/7
Current transducers-MCR-S-1/5-UI-DCI-NC-2814715
Technical data
Output data
20 mA ... 4 mA
Load/output load voltage output > 10 kΩ
Load/output load current output < 500 Ω
Switching output
Output name No switching output
Power supply
Supply voltage range 20 VDC ... 30 VDC
Max. current consumption < 40 mA (without load)
Connection data
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
General
Maximum transmission error < 0.5 % (of nominal range value under nominal conditions)
Temperature coefficient, typical < 0.025 %/K
Step response (10-90%) 330 ms (with AC)
40 ms (with DC)
Status display Green LED
Overvoltage category III
Degree of pollution 2
Rated insulation voltage 300 VAC (to earth)
Test voltage input/output 4 kV (50 Hz, 1 min.)
Test voltage input/power supply 4 kV (50 Hz, 1 min.)
Test voltage output/power supply 500 V (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Color green
Housing material Polyamide PA non-reinforced
Mounting position any
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
https://www.phoenixcontact.com/us/products/2814715
01/09/2021Page4/7
Current transducers-MCR-S-1/5-UI-DCI-NC-2814715
Technical data
Standards and Regulations
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Connection in acc. with standard CUL
Low Voltage Directive Conformance with Low Voltage Directive
Conformance CE-compliant
UL, USA/Canada Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Conformance/approvals
Designation CE
Identification CE-compliant
Designation UL, USA/Canada
Identification Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Dimensional drawing
22,5
114,5
99
Dimensional drawing
99 22,5
114,5
https://www.phoenixcontact.com/us/products/2814715
01/09/2021Page5/7
Current transducers-MCR-S-1/5-UI-DCI-NC-2814715
Circuit diagram
OUT
µC
ADC DAC
DAC
OUT
U
SPAN
9
OUT U
GND 2
GND 2
10
11
12
OUT I
Po
wer
=
12
10A
11
5A
14
1A
1
5
2
6
3
7
4
8
NC
ZERO
TIME
24VDC
GND 1
SW
13
14
15
GND 1
16
IN
I
SET
POINT
Classifications
eCl@ss
eCl@ss 10.0.1 27210123
eCl@ss 11.0 27210123
eCl@ss 4.0 27271100
eCl@ss 4.1 27200300
eCl@ss 5.0 27200300
eCl@ss 5.1 27200300
eCl@ss 6.0 27210100
eCl@ss 7.0 27210123
eCl@ss 8.0 27210123
eCl@ss 9.0 27210123
ETIM
ETIM 3.0 EC002475
ETIM 4.0 EC002475
ETIM 5.0 EC002475
ETIM 6.0 EC002475
ETIM 7.0 EC002475
UNSPSC
UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121032
UNSPSC 18.0 39121032
UNSPSC 19.0 39121032
UNSPSC 20.0 39121032
UNSPSC 21.0 39121032
https://www.phoenixcontact.com/us/products/2814715
01/09/2021Page6/7
Current transducers-MCR-S-1/5-UI-DCI-NC-2814715
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
EAC EAC-Zulassung
cULus Recognized
Accessories
Accessories
Arrester test system
Cable-CM-KBL-RS232/USB-2881078
Connecting cable D-9-SUB to USB, with adapter D-9-SUB to D-25-SUB.
https://www.phoenixcontact.com/us/products/2814715
01/09/2021Page7/7
Current transducers-MCR-S-1/5-UI-DCI-NC-2814715
Accessories
Programming adapter
Adapter cable-MCR-TTL-RS232-E-2814388
Software adapter cable (Stereo jack connector/D-SUB 25-pos.), 1.2 m length, for programming MCR-T-..., MCR-S-... and
MCR-f-... modules
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com