Part Number: 123092A
ControlNet™, (1) 18 AWG Solid BCCS, FPE/PVC/PVC, Foil+TC Braid Shld,
Alum Armor, CM
Product Description
One 18 AWG solid bare copper-covered steel conductor, foam polyethylene insulation, Duobond IV® quad shield (100% coverage), PVC inner jacket,
aluminum interlocked armor, PVC outer jacket.
Technical Specifications
Product Overview
Suitable Applications: ControlNet™, Modbus II, Industrial Coax
Physical Characteristics (Overall)
Conductor
AWG Stranding Material Nominal Diameter No. of Coax
18 Solid BCCS - Bare Copper Covered Steel 0.0403 in 1
Conductor Count: 1
AWG Size: 18
Insulation
Material Nominal Diameter
FPE - Foamed Polyethylene 0.178 in
Inner Jacket Material
Material Nominal Diameter
PVC - Polyvinyl Chloride 0.298 in
Outer Shield Material
Type Layer Material Material Trade Name Coverage [%]
Tape 1Bonded Aluminum Foil-Polyester Tape-Aluminum Foil Bonded Duofoil® 100 %
Braid 2AL - Aluminum 60 %
Tape 3Aluminum Foil-Polyester Tape-Aluminum Foil Duofoil® 100 %
Braid 4AL - Aluminum 40 %
Outer Jacket Material
Material Nominal Diameter Nominal Wall Thickness
PVC - Polyvinyl Chloride 0.591 in 0.045 in
Construction and Dimensions
Armor
Type of Armor Material
Interlocked Armor Aluminum
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR Nominal Outer Shield DCR Outer Conductor DCR
28 Ohm/1000ft 3.6 Ohm/1000ft 3.6 Ohm/1000ft
Capacitance
Nom. Capacitance Conductor to Shield
16.2 pF/ft
Inductance
Nominal Inductance
0.097 µH/ft
Impedance
Nominal Characteristic Impedance
100 Ohm
High Frequency (Nominal/Typical)
Frequency [MHz] Nom. Insertion Loss
1 MHz 0.35 dB/100ft
2 MHz 0.38 dB/100ft
5 MHz 0.45 dB/100ft
10 MHz 0.59 dB/100ft
20 MHz 0.86 dB/100ft
50 MHz 1.37 dB/100ft
100 MHz 1.97 dB/100ft
200 MHz 2.82 dB/100ft
300 MHz 3.48 dB/100ft
400 MHz 4.04 dB/100ft
Delay
Nominal Delay Nominal Velocity of Propagation (VP) [%]
1.28 ns/ft 82 %
High Freq
Frequency [MHz] Min. SRL (Structural Return Loss)
1 MHz 23 dB
2 MHz
5 MHz
10 MHz
20 MHz
50 MHz
100 MHz
200 MHz
300 MHz
400 MHz
Voltage
UL Voltage Rating
300V RMS
Electrical Characteristics Notes: SRL Minimum 23dB (5MHz - 50MHz)
Temperature Range
UL Temp Rating: 75°C
Operating Temp Range: -40°C To +75°C
Mechanical Characteristics
Bulk Cable Weight: 142 lbs/1000ft
Max Recommended Pulling Tension: 200 lbs
Min Bend Radius/Minor Axis: 7.1 in
Standards
NEC Articles: 800
NEC/(UL) Specification: CL2, CM
CEC/C(UL) Specification: CMG, HL
RG Type: RG-6/U Type
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2011/65/EU (ROHS II): Yes
EU Directive 2012/19/EU (WEEE): Yes
EU Directive 2015/863/EU: Yes
EU Directive Compliance: EU Directive 2003/11/EC (BFR)
EU RoHS Compliance Date (yyyy-mm-dd): 2005-10-01
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Suitability
Suitability - Hazardous Locations: Yes
Suitability - Indoor: Yes
Suitability - Outdoor: Yes
Suitability - Sunlight Resistance: Yes
Flammability, LS0H, Toxicity Testing
UL Flammability: UL1685 UL Loading
CSA Flammability: FT4
Part Number
Plenum (Y/N): No
Variants
Item # Color
123092A 0101000 BLACK
123092A 0102000 BLACK
123092A J221000 BLUE, STRONG
123092A J225000 BLUE, STRONG
Product Notes
Notes: ControlNet is a ControlNet International trademark.
© 2018 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without
notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages
(including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS(Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be instock at Belden facilities and in our Distributor's
inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden's knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the safe handling, storage, and any other operation of the product
itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.