BCD.00365 Rev. AA, 21-May-14 Page 1 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
Rear Module Connection Area
Supply Front View
Fig.1 LPM409 Expanded Views
1. Description
The LPM/LMM409 Series is a modular 900-watt AC-DC power supply that provides a market-leading power
density of 14 watts per cubic inch and has an extra low 1U profile. LMM is medically approved version. Further will
be discussed only LPM version and differences of LMM will be noted. The LPM409 offers the flexibility of a
modular architecture and the combination of high efficiency and high power density.
Designed for use where a unique set of voltage and current requirements are needed, the supply's four slots can
be configured with PCB-based output modules to deliver up to four outputs. The LPM output modules operate in
any chassis position and can provide up to 900 watts total power from a 150 VAC input and 700 watts from a
85 VAC input. Forced-air cooling with airflow direction from front to back is provided by an internal fan.
For LPM409 supplies using less than the four-slot capability, blanking plates are installed for safety purposes and
to optimize airflow within the chassis. The supplies are pre-set with default output module settings or with the
customer’s desired output settings prior to delivery. The LPM409 chassis can be populated with the output
modules listed in Table 1.
Industrial equipment
Telecommunications
Test and measurement
Automation
Peripherals
Audio/broadcast
Linear and rotary motion
Standard output voltages of 1.5 to 54 VDC
Efficiencies up to 87% typical
Extra-Low 1U profile: 1.6 inch
High power density design of 14 Watts/cubic inch
1 to 4 isolated outputs with full user configurability
Power Factor Correction (PFC) IEC 61000-3-2
compliant
700W @ 85 VAC or 900W @ 150VAC of total output
power
Zero-load operation
Single-wire current sharing
Universal input AC range
Individual control signals on each module
Auxiliary power 5V (1A)
FE
ATURES
Imaging Equipment
Anesthesiology
Surgical Devices
Diagnostic Equipment
Patient Beds
Home Healthcare
Ultrasound
LMM409 (Medical) LPM409 (Industrial)
BCD.00365 Rev. AA, 21-May-14 Page 2 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
Table 1. Module Selection
MODULE P/N
NO. OF
SLOTS
REQUIRED
FACTORY-
SET SINGLE-
OUTPUT
(VDC)
MODULE
ADJUSTABLE
RANGE (VDC)
MAX.
OUTPUT
CURRENT
(AMPS)
MAX. OUTPUT
POWER
2
(WATTS)
E LPM126-OUTA1-05 1 5 2.0 to 5.3 53 265
F LPM126-OUTA1-12
1 12 5.2 to 15 22 265
G LPM126-OUTA1-24
1 24 14 to 30 11 265
H LPM126-OUTA1-36
1 36 29 to 44 7.4 265
J LPM126-OUTA1-48
1 48 43 to 54 5,5 265
K LPM109-OUTA1-10 1 15 1.5 to 15 6 90
L LPM109-OUTA1-20 1 30 3 to 32 3 90
M LPM118-OUTA2-10 1 15 2x 1.5 to 15 2x 6 2x 90
N LPM118-OUTA2-20 1 30 2x 3 to 32 2x 3 2x 90
0 LPM000-BLAN 1 Blank Panel (Slot Cover)
1
To determine your desired power supply's part number, please refer to Fig.3 for a detailed part number description.
Use the LPM Configurator located in the Modular Section on our website, or use our contacts page to locate a
distributor for further assistance. (http://lpm.power-one.com/cgi-bin/start.cgi/lpm/config_start.html)
2
For the power derating specification please see section 1.4 below.
1.1 Output Voltage Adjustment
Each LPM409 module’s output voltage is adjustable by means of a trimmer located on the module. For the
modules E<->J the trimmer is accessible through the adjustment hole located on the bottom of the power supply
(see Fig.11). For the modules K<->N the trimmer is accessible from rear side of the power supply (see Fig.6).
1.2 Parallel Connections
Depending on certain situations where current requirements exceed one module’s capability, the configurator will
process a solution using parallel connections. Paralleling busbars are available to make the connections requiring
higher current needs. To ensure the current sharing function works correctly it is required to interconnect the
signal pins of the modules that will operate in parallel. Only E-J modules can be connected in parallel. For more
details read section 10.3 and Fig.17.
1.3 Serial Connections
To increase the output voltage it is possible to connect modules in series. Serial busbars are available (see
section 10.4) to make the connections requiring higher voltage needs. The output of LPM409 is rated as SELV
circuit, so the output voltages are guaranteed to be less than 60V. The series combination of modules can exceed
this SELV voltage, so in this case the users must take adequate precautions. The maximal total voltage must not
exceed 200V. PowerOne recommends to only connect the same modules with the same current rating in series.
The voltage sense pins VS+, VS- available on LM126 modules must be connected according to Fig.18.
BCD.00365 Rev. AA, 21-May-14 Page 3 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
1.4 Power derating
When specifying an LPM409 power supply in an application it is necessary to ensure that LPM409-CHAS and
modules (LPM126, LPM118 and LPM109) are operating within their power output capabilities, taking into account
the temperature derating and input voltage derating. The maximum permissible output power that may be drawn
from LPM409-CHAS and modules assembled in this chassis is given in the Fig.2.
a.) b.)
c.) d.)
Fig.2 Power derating curves a.) for LPM409-CHAS, b.) for module LPM126-5V
c.) for modules LPM126-12/24/36/48V and d.) for modules LPM118 / LPM109
BCD.00365 Rev. AA, 21-May-14 Page 4 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
2. Part Numbering and Ordering Information
2.1 Chassis Identification Numbering
First left-to-right sequence of the part number (4 characters):
LPM409 .. Low Profile Modular 4-slot, 900W, with single-phase AC input. (see Fig.3)
Note: Chassis and modules are RoHS-6 compliant.
Fig.3 LPM 4-Slot model part number description
Example: After entering your requirements, the web Configurator could recommend the following optimized part
number: LPM409-0HEG-DXXX which represents: Low Profile Modular Series with single-phase AC input, 4-slot,
900W chassis with modules of: blank panel 0” and modules H, E, G in slots 1 to 4, respectively. Besides the
blanking panel in slots 1, the example's modules in this case would represent desired DC output voltages as
follows: Slot 2 = H for 36V, Slot 3 = E for 3.3V and Slot 4 = G for 24V.
Assembly facility code and customer build ID No. are established during actual power supply assembly.
The slots numbering 1-4 is from the left to right when looking from the rear.
3. Safety specifications
3.1 Safety approvals LMM medical
UL/CSA 60950-1, 2
nd
UL/CSA 60601-1, 3
rd
IEC 60950-1, 2
nd
IEC 60601-1, 3
rd
EN 60950-1, 2
nd
EN 60601-1, 3
rd
CE Mark for LVD
3.2 Insulation Safety Ratings
TEST POINTS MINIMUM TEST VOLTAGE INSULATION SAFETY RATING
Input-to-Chassis 2120 Vdc / min. 1s Basic Insulation
Input-to-Output 4240 Vdc / min. 1s Reinforced Insulation
Outputs-to-Chassis 200 Vdc / min. 1s Functional Insulation
Output-to-Output 200 Vdc / min. 1s Functional Insulation
BCD.00365 Rev. AA, 21-May-14 Page 5 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
4. Environmental and Reliability specifications
4.1 Environmental specification
PARAMETER CONDITIONS / DESCRIPTION MIN. NOM. MAX. UNITS
Cooling Internal DC fan, air intake is from the AC
connector side exiting at the DC module side
Audible Noise Single unit, 4 modules assembled and full loaded,
on a table at 1m distance.
65
dBA
Operating
Temperature
50°C at Full power and up to 70°C at 50% load
(linearly derated, for details see section 1.4) -20 25 50 ºC
Storage Temperature -40 75 ºC
Humidity 95% relative humidity @ 25 ºC, non-condensing
Vibration
Operating: Swept 5-500-5Hz profile, 3 axis, 5
sweep cycles per axis
Non-operating: Swept 5-500-5Hz profile, 3 axis, 5
sweep cycles per axis
1
4
Gpk
Gpk
Shock Operating: 11ms, half sine, 10 shocks per face
Non-operating: 11ms, half sine, 3 shocks per face
20
40
Gpk
Gpk
4.2 Reliability
PARAMETER CONDITIONS / DESCRIPTION MIN. NOM. MAX. UNIT
S
Calculated MTBF According to MIL-HDBK217,
Ground benign 30 ºC,
Note: Calculation was done for LPM409-EFGH.
250,000 hours
Demonstrated MTBF Tamb=25°C 250,000 hours
5.
Fault Protection
PARAMETER CONDITIONS / DESCRIPTION MIN. NOM. MAX. UNITS
Input Fuse One fuse, non-user serviceable, located
on line leg of AC input, Fast Acting type 12,5 A
Inrush Current Limitation Provided by NTC See Input specification section
Short Circuit Protection Provided by Current Limit circuit 105
1
125
1
% Io_nom
Output Overvoltage
Protection
Latching (unit needs to be turned-off and
on) 10 25 % Vo_nom
Over Temperature OT with auto restart 70 °C amb
1
100-150% for K, M modules
100-200% for L, N modules
BCD.00365 Rev. AA, 21-May-14 Page 6 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
6. EMC specifications
6.1 EMC Immunity
PARAMETER CONDITIONS / DESCRIPTION CRITERION
Electrostatic Discharge
(ESD)
IEC/EN61000-4-2; GR-1089 R2-1, R2-2, R2-3
Level 4: contact: ±8 kV, air: ± 15kV Perform, criterion B
RF Susceptibility
IEC/EN 61000-4-3;
Level 3: 10 V/m; 80 MHz to 1000 MHz;
AM 80%, 1 kHz radiated; RF electromagnetic field
Perform, criterion A
Fast transient / burst IEC/EN 61000-4-4; Level 3; ±2 kV, 5kHz
electrical fast transient / burst immunity test Perform, criterion B
Surge IEC61000-4-5, level 3; line to earth: ± 2kV, line to line: ± 1kV
surge immunity test Perform, criterion B
RF conducted
disturbance
IEC/EN 61000-4-6; Level 3; GR-108;
10V, 0.15 to 80MHz, AM 80%, 1kHz Perform, criterion A
Voltage dips / short
interruptions
IEC/EN 61000-4-11; Voltage dips, interruptions and variations.
(Interpretation: dip below Vi min with Po nom = hold-up time 10
ms)
1a: Dip 30%, 100ms Perform, criterion B
1a: Dip 30%, 200ms Perform, criterion B
1a: Dip 60%, 10ms Perform, criterion A
1a: Dip 60%, 100ms Perform, criterion B
1a: Dip >95%, 10ms (interruption) Perform, criterion A
1a: Dip >95%, 100ms (interruption) Perform, criterion B
6.2 EMC Emission
PARAMETER CONDITIONS / DESCRIPTION CRITERION
Conducted Emission
EN55022, FCC
EN 55022, FCC – EN 55022, and CISPR 22 Class B,
FCC 47CFR15 unintentional radiators; standalone at all nominal
input voltages and measured in Po1: 0, 50%, 100%;
signal connections open
Class B;
min. 3dB/µV margin
Radiated Emission
EN55022, FCC
EN 55022, FCC – EN 55022, and CISPR 22 Class B,
FCC 47CFR15 unintentional radiators; standalone at all nominal
input voltages and measured in Po1: 0, 50%, 100%;
signal connections open
Radiated Class A QSP / AVG
min. 3 dB margin
Input Current
Harmonics
EN 61000-3-2, sine wave input, Class D; measured standalone
at all Vin nominal at power levels between 0 and rated Pass
BCD.00365 Rev. AA, 21-May-14 Page 7 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
7. Electrical specifications
7.1 Input Specifications
PARAMETER CONDITIONS / DESCRIPTION MIN. NOM. MAX. UNITS
Input AC Voltage
Range
Continuous AC voltage Range
Po=700W from 85-150 VAC
Po=900W from 150-264 VAC
85 115/230 264 VAC
Input Overvoltage
Range At max. power, no input OVP shutdown 300 VAC
Ground continuity 0.1
1
Ohm
Leakage Current @ 264 VAC, 60Hz, Commercial LPM / Medical
LMM 1.5 / 0.5 mA
Frequency AC line 47 50/60 63 Hz
Power Factor Active PFC meets requirements of
EN 61000-3-2 at full load ,120/230 VAC input 0.98
Input Current Steady state, 85 VAC at 700W 11 Arms
Inrush Current
180 VAC, Max Power, 25°C,
acc. prETS300-132-1
230 VAC, Max Power, 25°C,
acc. prETS300-132-1 (Repeat rate >1min)
40 A pk
Efficiency
2
Vi = 230 VAC 100% loading 86 87 %
Vi = 230 VAC 30-80% loading 80 82 %
Vi = 115 VAC 100% loading 83 84 %
Vi = 115 VAC 30-80% loading 78 80 %
1
For any combination of output modules, any valid load and voltage setting
2
Efficiency typical for standard configuration EFGH and nominal output voltage settings
7.2 Output Specifications
PARAMETER CONDITIONS/DESCRIPTION MIN. NOM. MAX. UNITS
Output Power One fan for internal cooling 900 W
Output DC
Voltages / Modules
All output modules work in any chassis position
and are max 1U high PCB-based -
Current Share
3
Active single-wire current share (modules E-J)
Max. difference in currents between two modules–
percentage of one module nominal current
±10 %
Line Regulation Input from 85 to 264 VAC , 80% load 1.0 % Vo_nom
Load Regulation From 0-100% load, Input >180VAC, Vo_nom 1.0 % Vo_nom
Thermal Drift After 15 minute warm-up period 0.02 %/ºC
BCD.00365 Rev. AA, 21-May-14 Page 8 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
Total Regulation Variation of line, load and temperature drift 2.0 % Vo_nom
Output Adjust. Range See Module Selection Table 1
Dynamic Response
Deviation for 10-90% or 90-10% load changes at
a rate of 1A/µs, (constant current mode, Vo reach
1% band around Voset)
4%
1,2
2000µs -
Deviation for 50-100% or 100-50% load steps with
1A/µs rate. (constant current mode, Vo reach 1%
band around Voset)
3%
1
400µs -
Output Ripple &
Noise
BW = 20MHz; Filter 10nF/10uF; over line and
load, 25°C 1% of
Vo_nom
1
mVpk-pk
CM Noise
Output to chassis, over line and load
(Measured across 50 Ohms, with 10µH / 10nF in
parallel)
220 500 mVpp
Overshoot Output voltage overshoot at turn-on 4 % Vo_nom
Turn-On
Characteristics Turn ON at minimum and nominal output current Monotonic characteristic -
Turn-Off
Characteristics Turn OFF at minimum and nominal output current Monotonic characteristic -
Turn-On Time
Time required for output within regulation after
initial application of AC input 1.5 s
Time required for output within regulation after
removing inhibit 100 ms
Hold-up Time
Vo is required to stay within 95% regulation after
AC is removed. Measured from the last AC peak,
VAC min and full load.
10
ms
Remote Sense
3
Total compensation for cable losses 250 500 mV
Over-current Protect. Automatic recovery / Hiccup by K-N modules 130 / 180 %
1
the E module dynamic deviation is less than 6%, the E, K, M module ripple is less than 2%
2
the K and M module dynamic deviation is less than 7% and response time is below 1000us
3
except K-N modules
BCD.00365 Rev. AA, 21-May-14 Page 9 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
7.3 Input - Signals, Features and Indicators description
Signal Name Pin Description
Auxiliary Output
- 5V -
1,2 vs
3,4
(RTN_D)
Output is available when the AC input is over 85VAC. The output nominal output voltage is
5.0V at maximum current rating of 1.0A. Over current protection occurs above 1.5A. The
output is referenced to logic return, RTN_D.
Input AC Low
Indication
- PFAIL -
5
Open Collector output with 20mA pull-down capability referenced to logic return RTN_D.
PFAIL open or High state indicates the warning that the input is out of limits (the input
voltage falls below 85Vac or rises over 264Vac ) 5 ms before the output goes below the
lower regulation limit. PFAIL will turn-off the green Input OK LED.
PFAIL LOW state indicates that the input voltage is within the operating range.
Fan Fail / OTP
Indication
- FAN_FAIL -
6
Open Collector output pin with 20mA pull-down capability referenced to logic return
RTN_D.
FAN_FAIL OPEN OR HIGH state indicates a fan failure/over temperature protection (OTP)
condition min. 100 ms before the unit shuts-down. A fan failure/OTP condition will turn-off
the green FAN OK LED.
FAN_FAIL LOW state indicates normal fan operation and no OTP condition.
7.4 Output - Signals, Features and Indicators description
Modules E, F, G, H, J
Signal Name Pin Description
Positive sense
wire
- VS+ -
1 Output voltage sense wire. Internally connected to Vout+ via 51 . It is recommended to
connect sense wire at positive load point.
Negative sense
wire
- VS- -
2 Output voltage sense wire. Internally connected to Vout- via 51 . It is recommended to connect
sense wire at negative load point.
Current share
- CSH - 3
Common wire for parallel connected modules to achieve proper current sharing between the
modules. Referenced to the Common pin. Interconnect CS pin on all parallel working modules.
Active current share pin enables control of output voltage. Pulling-up this pin to 5V is possible to
increase the output voltage. Pull-down of this pin has no effect. Voltage on this pin is 3.5V at
nominal module current.
Common 4 Reference pin to CSH
N/C 5
N/C 6
Output Good
indication
- PG_HI -
7
Open collector output with 20mA pull-down capability, max. 15V (recommended Rpull-up=1k,
Vcc=5V). Referenced to PG_LO.
PG_HI OPEN OR HIGH state indicates that the module output voltage is below lower regulation
limit. A PG_HI fail state turns the GREEN DC OK LED to RED.
PG_HI LOW state indicates the module output voltage is within normal operation limits.
- PG_LO - 8 Reference pin to PG_HI
Output Inhibit
function
- INH_HI -
9
An opto-isolated input with 2-10mA current capability. Apply +(3-15)V on INH_HI and RTN on
INH_LO (e.g. from the Auxiliary Output 5V) to activate the inhibit function.
INH_HI OPEN OR LOW state ENABLES the module output.
INH_HI HIGH state INHIBITES the module output.
- INH_LO - 10 Reference pin to INH_HI
BCD.00365 Rev. AA, 21-May-14 Page 10 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
Output - Signals, Features and Indicators description
Modules K, L, M, N
Signal Name Pin Description
- INH_LO_B - 1 Reference pin to INH_HI_B
Output Inhibit
function
- INH_HI_B -
2
An opto-isolated input with 2-10mA current capability. Apply +(3-15)V on INH_HI_B and
RTN on INH_LO_B (e.g. from the Auxiliary Output 5V) to activate the inhibit function.
INH_HI OPEN OR LOW state ENABLES the module output.
INH_HI HIGH state INHIBIT the module output.
- PG_LO_B - 3 Reference pin to PG_HI_B
Output Good
indication
- PG_HI_B -
4
Open collector output with 20mA pull-down capability, max. 15V (recommended Rpull-
up=1k, Vcc=5V). Referenced to PG_LO_B.
PG_HI OPEN OR HIGH state indicates that the module output voltage is below lower
regulation limit. A PG_HI fail state turns the GREEN DC OK LED to RED.
PG_HI LOW state indicates that the module output voltage is within normal operation
limits.
N/C 5
N/C 6
- INH_LO_A - 7 Reference pin to INH_HI_A
Output Inhibit
function
- INH_HI_A -
8
An opto-isolated input with 2-10mA current capability. Apply +(3-15)V on INH_HI_A and
RTN on INH_LO_A (e.g. from the Auxiliary Output 5V) to activate the inhibit function.
INH_HI OPEN OR LOW state ENABLES the module output.
INH_HI HIGH state INHIBIT the module output.
- PG_LO_A - 9 Reference pin to PG_HI_A
Output Good
indication
- PG_HI_A -
10
Open collector output with 20mA pull-down capability, max. 15V (recommended Rpull-
up=1k, Vcc=5V). Referenced to PG_LO_A.
PG_HI OPEN OR HIGH state indicates that the module output voltage is below lower
regulation limit. A PG_HI fail state turns the GREEN DC OK LED to RED.
PG_HI LOW state indicates that the module output voltage is within normal operation
limits.
7.5 Visual Alarms description
Alarm Name LED position Description
Input AC Good Front panel – LED2
(see Fig.7)
ON state LED indicates operation within specified input voltage range.
GREEN LED indicator goes to an OFF condition on PFAIL signal failure state.
Fan Good Front panel – LED1
(see Fig.7)
ON state LED indicates normal fan operation and no OTP status.
GREEN LED indicator goes to an OFF condition on FAN_FAIL / OTP signal
failure state.
Output Good
Module connector /
rear side
(see Fig.5 and Fig.6)
GREEN LED indicates that module output voltage is over minimum regulation
limit.
GREEN LED indicator goes to RED on PG_HI signal failure state.
BCD.00365 Rev. AA, 21-May-14 Page 11 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
8. Connector Details
8.1 Input Connector Information
LPM409 front panel connectors pinout refers to Fig.4 and chapter 8.2 and 8.3. The signal connector is Cvilux part
number: CI3306P1H10, the mating part is Cvilux
CI3306S0010, Molex 50-57-9406 or
Taiwan King Pin P553L-
06(LF).
Note: See chapter 10.1 Mating Connections and cables for Input cable information.
Fig.4 LPM409 Front Panel Connectors Pinout View
8.2 Input Power Connector - Pinout
Name Pin # Type Recommended wires
V max
I max
Earth Earth / Chassis Min. 0,75 mm
2
e.g. Interpower 86230120
Max. torque on screws
(M4x6): 1,5 Nm
AC Neutral N Input Power AC 264 Vrms
10 Arms
AC Line L Input Power AC Fused
Caution: The plastic cover must be in place when AC input voltage is applied to the unit! The cover may be
removed (with the help of a screwdriver) only when the input cable is disconnected from the mains.
8.3 Input Signal Connector – Pinout (Mating connector: Molex 50-57-9406, pins: Molex 16-02-0082)
Sign
al
Name
Pin
# Wire Color Type
reference
Low level
High level
V max
I max
+5V 1 Red Aux Output RTN_D - 5.0Vdc
1.0Adc
+5V 2 Red Aux Output RTN_D -
RTN_D 3 Black Logic Reference Potential - - -
RTN_D 4 Black Logic Reference Potential - - -
PFAIL 5 Yellow Open Collector Output + ZD 5.6V RTN_D
<400mV@
20mA
Pull up
-
20mA
FAN_FAIL 6 Green Open Collector Output + ZD 5.6V RTN_D
<400mV@
20mA
Pull up
-
20mA
BCD.00365 Rev. AA, 21-May-14 Page 12 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
8.4 Module Outputs Pinout
Modules E, F, G, H, J - A, B Bus-Bar
Signal Name Pin # Type Signal reference
Low level
High level
V max
I max
Vout+ Vout+ Output Power DC Vout- - See Module
Selection Table 1
Vout- Vout- Output Power DC - - See Module
Selection Table 1
Connector type: Bus-bar see Fig.5
Mating part: Ring terminal for M4 screw, with appropriate cross section for wire.
Modules K, L, M, N
Signal Name Pin # Type Signal reference
Low level
High level
V max
I max
Vout1+ Vout1+ Output 1 Power DC Vout1- - See Module
Selection Table 1
Vout1- Vout1- Output 1 Power DC - - See Module
Selection Table 1
Vou2+
1
Vout2+ Output 2 Power DC Vout2- - See Module
Selection Table 1
Vout2-
1
Vout2- Output 2 Power DC - - See Module
Selection Table 1
1
valid only for two outputs modules M and N.
Connector type: Phoenix Contact 1803277
Mating part: Phoenix Contact 1850660
Fig.5 Modules E,F,G,H,J Power Output Connectors Fig.6 Modules K,L,M,N Power Output Connectors
BCD.00365 Rev. AA, 21-May-14 Page 13 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
8.5 Module Output C Signal Connector Pinout
The output signal connector provides signal information across its 10-pin output, for position of the output signal
connector please see Fig.5 and Fig.6.
Connector type: JST S10B-PHDSS-B
Mating part: JST housing PHDR-10VS, pins SPHD-002T-P0.5 (AWG 28-24)
or SPHD-001T-P0.5 (AWG 26-22)
Modules E, F, G, H, J – signal output connector pinout
Signal Name Pin # Type Signal reference
Low level
High level
V max
I max
VS+ 1
Output voltage sense wire.
Internally connected to Vout+ via
51
Vout+ - 0.5V
10mA
VS- 2
Output voltage sense wire.
Internally connected to Vout- via
51
Vout- - 0.5V
10mA
CSH 3 Active Current Share pin Common - 5V
-
Common 4 Reference pin to CSH - - -
N/C 5 - - - -
N/C 6 - - - -
PG_HI 7 Open collector output PG_LO <400mV@5mA
Pull up
15V
20mA
PG_LO 8 Reference for PG_HI - - -
20mA
INH_HI 9 Input, protected by 18V Zener
diode INH_LO LED with a serial
resistor 2 kOhms
15V
10mA
INH_LO 10 Reference for INH_HI - - -
10mA
BCD.00365 Rev. AA, 21-May-14 Page 14 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
Modules K, L, M, N– signal output connector pinout
Signal Name Pin # Type Signal reference
Low level
High level
V max
I max
INH_LO_B 1 Reference for INH_HI_B - - -
10mA
INH_HI_B 2 Input, protected by 18V Zener
diode INH_LO_B LED with a serial
resistor 2 kOhms
15V
10mA
PG_LO_B 3 Reference for PG_HI_B - - -
20mA
PG_HI_B 4 Open collector output PG_LO_B <400mV@5mA
Pull up
15V
20mA
N/C 5 - - - -
N/C 6 - - - -
INH_LO_A 7 Reference for INH_HI_A - - -
10mA
INH_HI_A 8 Input, protected by 18V Zener
diode INH_LO_A LED with a serial
resistor 2 kOhms
15V
10mA
PG_LO_A 9 Reference for PG_HI_A - - -
20mA
PG_HI_A 10 Open collector output PG_LO_A <400mV@5mA
Pull up
15V
20mA
BCD.00365 Rev. AA, 21-May-14 Page 15 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
9. Mechanical Drawings
Overall Dimensions: 11.9" x 3.6" x 1.6" (303.7 x 92 x 40.64mm)
Weight: 1.38 kg (including 4 modules)
All drawing dimensions are shown in millimeters, unless otherwise notated.
Fig.7 Front View
Fig.8 Rear View
BCD.00365 Rev. AA, 21-May-14 Page 16 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
Fig.9 Side View
Fig.10 Top View
Fig.11 Bottom View
BCD.00365 Rev. AA, 21-May-14 Page 17 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
10. Accessories
10.1 Mating Connections and Cables
All the power and signal cables and mating connectors are not included in the LPM409 standard package. These
all need to be ordered extra.
Front panel signal cable: Power-One accessory LPM000-LEAD-03, see Fig.12
Output signal cable: Power-One accessory LPM000-LEAD-04, see Fig.13a
mating connector: JST, housing PHDR-10VS, pins SPHD-002T-P0.5 (AWG 28-24)
Output power cable (for LPM126): 14AWG – 10AWG depend on the output current, min. thermal
class 105°C, lug terminal 4mm 6mm
2
Output power cable (for LPM109/118): Power-One accessory LPM000-LEAD-05, see Fig.13b
Fig.12 LPM000-LEAD-03 – Front Fig.13a LPM000-LEAD-04 - Output Fig.13b LPM000-LEAD-05 - Output
panel signal cable signal cable power cable for modules K-N
(length of the cable 1.8m) (length of the cable 0.75m) (length of the cable 0.75m)
10.2 Signal Output wire colors
Pin # Signal Name by
Modules E, F, G, H, J
Signal Name by
Modules K, L, M, N Wire Color
1 VS+ PG_HI_A Red
2 VS- PG_LO_A Blue
3 CSH INH_HI_A Yellow
4 Common INH_LO_A White
5 N/C N/C -
6 N/C N/C -
7 PG_HI PG_HI_B Violet
8 PG_LO PG_LO_B Brown
9 INH_HI INH_HI_B Black
10 INH_LO INH_LO_B Green
BCD.00365 Rev. AA, 21-May-14 Page 18 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
10.3 Paralleling Busbars (only for modules E-J)
Item Description
Model
LPM000-BBAR-07
Busbar for parallel connection of two modules, central screw M5,
max. 100A
1
.
Two pieces are in one package LPM000-BBAR-07.
LPM000-BBAR-08 Busbar washer with 1 opening for odd module paralleling.
Two pieces are in one package LPM000-BBAR-08.
Notes:
1
For load current over 100A use two or more cables connected to separate busbars.
2
By using busbars (paralleling modules) you will need also the signal output leads LPM000-LEAD-04, one for each
connected module. The interconnection is shown in Fig.17 (especially all pins 3 - CSH and all pins 4 - Common must be
reconnected).
3
Modules K-N cannot be connected in parallel.
The example of LPM409-00EE-DXXX assembly configuration (two modules in parallel) is on Fig.14. One set of
busbars LPM000-BBAR-07 + 2x LPM-LEAD-04 is necessary for connection.
Fig.14 LPM409-00EE-DXXX Parallel Configuration Fig.15 LPM409-0EEE-DXXX Parallel Configuration
An example of an LPM409-0EEE-DXXX assembly configuration (three modules in parallel) is on Fig.15. Two sets
of busbars LPM000-BBAR-07 + one set of LPM000-BBAR-08 + 3x LPM-LEAD-04 are necessary to make the
interconnections.
Note, that for odd number of modules in parallel it is necessary to also use one set of busbar washers LPM000-
BBAR-08.
To connect the load in case of higher output currents, more output cables must be used for each pole. For
example for 200A output current (LPM409-EEEE-DXXX) connect minimal two power cables for each pole (2x
42mm
2
for one pole). Use min. 105°C thermal class isolation.
BCD.00365 Rev. AA, 21-May-14 Page 19 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
Fig.16 LPM409 – Paralleling Connection Diagram for LPM126 Modules
10.4 Serial Busbars (only for modules E-J)
Item Description
Model
LPM000-BBAR-09 Busbar for serial connection of two modules.
Fig.17 LPM409-0EEE-DXXX Serial Configuration
BCD.00365 Rev. AA, 21-May-14 Page 20 of 20
www.power-one.com
LPM/LMM409 AC-DC Modular Power Supply Data Sheet
5V, 10V, 12V, 20V, 24V, 36V & 48V Single-Output Modules
10V, 20V Dual-Output Modules
Fig.18 LPM409 – Serial Connection Diagram for LPM126 Modules
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.