Industrial Control Transformers
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© January 2017
194
International Series Control Transformers: 50 - 750 VA
Electromagnetic control components demand inrush
currents up to 10 times the transformers nominal rating
without sacricing secondary voltage stability beyond
practical limits. The International series transformers fully
comply with IEC and NEMA standards and are available
with IEC touchproof covers (IP20).
Features
Epoxy encapsulated for cooler operation
Interleaved copper windings to reduce impedence
50/60 Hz
55°C Rise, 105°C insulation system for harsh,
heavy duty applications
Exceeds IEC, NEMA, ANSI, NMTBA, JIC and
automotive standards
Certifications and Compliances
Listed: E77014 - Type SBE
- UL 5085-1, UL 5085-2
- CSA C22.2 No. 66.1, No. 66.2
- IEC/EN 61558-1, IEC/EN 61558-2-2
RoHS Compliant
Related Products
DIN Rail Power Supplies
63 Series Power Conditioners
Surge Protective Devices
E77014
CATALOG NUMBER FIELD INSTALLED OPTIONS
DESCRIPTIONS
SBEDIN
DIN Circuit Breaker Mounting
Field installed IEC fuse holder adaptor
kit
IP20
Terminal Covers (Two Covers Per Kit)
Field installed primary and secondary
IEC Touch Proof Cover Kit.
Industrial Control Transformers
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© January 2017
195
Selection Tables: International Series
Group 1 – -/220/380 V Primary, 110/23 V Secondary, 50/60 Hz
208/240/415 V Primary, 120/24 V Secondary, 50/60 Hz
200/230/400 V Primary, 115/24 V Secondary, 50/60 Hz
Continuous
VA
Instantaneous
VA
Catalog
Number
Height
in (mm)
Width
in (mm)
Depth
in (mm)
Mtg Width
W1 / W2 - in (mm)
Mtg Depth
D1 / D2 - in (mm)
Slot Size
S1/S2 - in (mm)
Approx.
Ship Weight
lbs (kg)
50 105 E050TC 2.96
(75.2)
3.39
(86.1)
4.36
(110.7)
2.81 / 2.50
(71.4 / 63.5)
2.10 / N/A
(53.3 / N/A)
.20 x .50 / .20 x .50
(5.1 x 12.7 / 5.1 x 12.7) 4.0 (1.82)
100 230 E100TC 3.89
(98.8)
4.50
(114.3)
4.48
(113.8)
3.74 / 3.12
(95.0 / 79.3)
2.56 / 2.87
(65.0 / 72.9)
.20 x .65 / .20 x .33
(5.1 x 16.5 / 5.1 x 8.4) 8.0 (3.67)
150 420 E150TC 3.89
(98.8)
4.50
(114.3)
5.21
(132.3)
3.74 / 3.12
(95.0 / 79.3)
3.29 / 3.61
(83.6 / 91.7)
.20 x .65 / .20 x .33
(5.1 x 16.5 / 5.1 x 8.4) 11.0 (5.00)
250 675 E250TC 4.53
(115.1)
5.25
(133.4)
5.07
(128.8)
4.38 / 3.75
(111.3 / 95.3)
3.54 / N/A
(89.9 / N/A)
.31 x .85 / .31 x .85
(7.9 x 21.6 / 7.87 x 21.6 15.0 (6.82)
500 1550 E500TC 5.56
(141.2)
6.38
(162.1)
6.93
(176.0)
5.32 / 4.37
(135.1 / 111.0)
4.25 / 5.75
(108.0 / 146.1)
.31 x .03 / .31 x .85
(7.9 x .85 / 7.9 x 21.6) 30.0 (13.64)
Group 2 – 208/240/415 V Primary, 24 V Secondary, 50/60 Hz
277/480 V Primary, 24 V Secondary, 60 Hz
200/230/400 V Primary, 24 V Secondary, 50/60 Hz
220/380 V Primary, 23 V Secondary, 50/60 Hz
Continuous
VA
Instantaneous
VA
Catalog
Number
Height
in (mm)
Width
in (mm)
Depth
in (mm)
Mtg Width
W1 / W2
in (mm)
Mtg Depth
D1 / D2
in (mm)
Slot Size
S1/S2 - in (mm)
Approx.
Ship Weight
lbs (kg)
50 105 E050TE 2.96
(75.2)
3.39
(86.1)
4.36
(110.7)
2.81 / 2.50
(71.4 / 63.5)
2.10 / N/A
(53.3 / N/A)
.20 x .50 / .20 x .50
(5.1 x 12.7 / 5.1 x 12.7) 4.0 (1.82)
100 230 E100TE 3.89
(98.8)
4.50
(114.3)
4.48
(113.8)
3.74 / 3.12
(95.0 / 79.3)
2.56 / 2.87
(65.0 / 72.9)
.20 x .03 / .20 x .01
(5.1 x .65 / 5.1 x .33) 8.0 (3.67)
150 420 E150TE 3.89
(98.8)
4.50
(114.3)
5.21
(132.3)
3.74 / 3.12
(95.0 / 79.3)
3.29 / 3.61
(83.6 / 91.7)
.20 x .03 / .20 x .01
(5.1 x .65 / 5.1 x .33) 11.0 (5.00)
250 700 E250TE 4.53
(115.1)
5.25
(133.4)
5.07
(128.8)
4.38 / 3.75
(111.3 / 95.3)
3.54 / N/A
(89.9 / N/A)
.30 x .71 / .30 x .71
(7.9 x 18.0 / 7.9 x 18.0) 15.0 (6.82)
500 1550 E500TE 5.56
(141.2)
6.38
(162.1)
6.93
(176.0)
5.32 / 4.37
(135.1 / 111.0)
4.25 / 5.75
(108.0 / 146.1)
.30 x .85 / .30 x .85
(7.9 x 21.6 / 7.9 x 21.6) 30.0 (13.64)
Note: Instantaneous VA calculated at At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
Design Style
Mounting Dimensions Profile Top View
Industrial Control Transformers
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© January 2017
196
Selection Tables: International Series - continued
Group 3 – 208/240/415/480/600 V Primary, 120 V Secondary, 50/60 Hz
200/230/400/460/575 V Primary, 115 V Secondary, 50/60 Hz
220/277 /380 V Primary, 110 V Secondary, 50/60 Hz
Note: 277V, 575V, 600V taps are 60Hz only.
Continuous
VA
Instantaneous
VA
Catalog
Number
Height
in (mm)
Width
in (mm)
Depth
in (mm)
Mtg Width
W1 / W2 - in (mm)
Mtg Depth
D1 / D2 - in (mm)
Slot Size
S1/S2 - in (mm)
Approx.
Ship Weight
lbs (kg)
H4
H3
X2
H1
0
50/60 Hz
X3
X4
120 (415/208)
115 (400/200)
110 (380)
H2
X1
120 (480/240)
115 (460/230)
110 (220)
120 (600)
115 (575)
110 (277)
200-277
H3
H1 H2 H4
380-600
H3
H1 H2 H4
60 Hz
Only
0
50 93 E050TF 2.96
(75.2)
3.39
(86.1)
4.36
(110.7)
2.81 / 2.50
(71.4 / 63.5)
2.10 / N/A
(53.3 / N/A)
.20 x .50 / .20 x .50
(5.1 x 12.7 / 5.1 x 12.7) 4.0 (1.82)
100 205 E100TF 3.89
(98.8)
4.50
(114.3)
4.48
(113.8)
3.74 / 3.12
(95.0 / 79.3)
2.56 / 2.87
(65.0 / 73.0)
.20 x .65 / .20 x .33
(5.1 x 16.5 / 5.1 x 8.4) 8.0 (3.67)
150 390 E150TF 3.89
(98.8)
4.50
(114.3)
5.21
(132.3)
3.74 / 3.12
(95.0 / 79.3)
3.29 / 3.61
(83.6 / 91.7)
.20 x .65 / .20 x .33
(5.1 x 16.5 / 5.1 x 8.4) 11.0 (5.00)
250 630 E250TF 4.53
(115.1)
5.25
(133.4)
5.07
(128.8)
4.38 / 3.75
(111.3 / 95.3)
3.54 / N/A
(89.9 / N/A)
.31 x .71 / .31 x .71
(7.9 x 18.0 / 7.9 x 18.0) 15.0 (6.82)
500 1200 E500TF 5.56
(141.2)
6.38
(162.1)
6.93
(176.0)
5.32 / 4.37
(135.1 / 111.0)
4.25 / 5.75
(108.0 / 146.1)
.31 x .85 / .31 x .85
(7.9 x 21.6 / 7.9 x 21.6) 30.0 (13.64)
750 2290 E750TF 5.56
(141.2)
6.38
(162.1)
7.36
(187.0)
5.32 / 4.37
(135.1 / 111.0)
4.68 / 6.18
(118.9 / 157.0)
.31 x .85 / .31 x .85
(7.9 x 21.6 / 7.9 x 21.6) 34.0 (15.45)
Group 4 – 240/415/480 V Primary, 120/240 V Secondary, 50/60 Hz
230/400/460 V Primary, 115/230 V Secondary, 50/60 Hz
220/380/440 V Primary, 110/220 V Secondary, 50/60 Hz
Continuous
VA
Instantaneous
VA
Catalog
Number
Height
in (mm)
Width
in (mm)
Depth
in (mm)
Mtg Width
W1 / W2
in (mm)
Mtg Depth
D1 / D2
in (mm)
Slot Size
S1/S2 - in (mm)
Approx.
Ship Weight
lbs (kg)
440/460/480
H4
H3
H2
380/400/415
220/230/240
H1
00
50/60 Hz
X3
X4
230 (460/400/230)
240 (480/415/240)
220 (440/380/220)
120 (480/415/240)
115 (460/400/230)
110 (440/380/220)
X3
X1 X2 X4
X3
X1 X2 X4
X2
X1
50 110 E050TH 2.96
(75.2)
3.39
(86.1)
4.36
(110.7)
2.81 / 2.50
(71.4 / 63.5)
2.10 / N/A
(53.3 / N/A)
.20 x .50 / .20 x .50
(5.1 x 12.7 / 5.1 x 12.7) 4.0 (1.82)
100 235 E100TH 3.89
(98.8)
4.50
(114.3)
4.48
(113.8)
3.74 / 3.12
(95.0 / 79.3)
2.56 / 2.87
(65.0 / 73.0)
.20 x .65 / .20 x .33
(5.1 x 16.5 / 5.1 x 8.4) 8.0 (3.67)
150 470 E150TH 3.89
(98.8)
4.50
(114.3)
5.21
(132.3)
3.74 / 3.12
(95.0 / 79.3)
3.29 / 3.61
(83.6 / 91.7)
.20 x .65 / .20 x .33
(5.1 x 16.5 / 5.1 x 8.4) 11.0 (5.00)
250 730 E250TH 4.53
(115.1)
5.25
(133.4)
5.07
(128.8)
4.38 / 3.75
(111.3 / 95.3)
3.54 / N/A
(89.9 / N/A)
.31 x .81 / .31 x .85
(7.9 x 20.6 / 7.9 x 18.0) 15.0 (6.82)
500 1550 E500TH 5.56
(141.2)
6.38
(162.1)
6.93
(176.0)
5.32 / 4.37
(135.1 / 111.0)
4.25 / 5.75
(108.0 / 146.1)
.31 x .85 / .31 x .85
(7.9 x 21.6 / 7.9 x 21.6) 30.0 (13.64)
750 2250 E750TH 5.56
(141.2)
6.38
(162.1)
7.36
(187.0)
5.32 / 4.37
(135.1 / 111.0)
4.68 / 6.18
(118.9 / 157.0)
.31 x .85 / .31 x .85
(7.9 x 21.6 / 7.9 x 21.6) 34.0 (15.45)
Note: Instantaneous VA calculated at At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
International Series - Fuse Recommendations
Primary Fusing: Consult local electrical code. Secondary Fusing: per IEC/EN61558-2-2.
VA Maximum Current Rating of Fuse
24 Vac 115 Vac 230 Vac
50 2 0.5 0.25
100 4 1 0.5
150 6 1.6 0.8
250 10 2.5 1.25
500 20 5 2.5
750 20 6.3 3.15
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Sola/Hevi-Duty:
E050TE E050TF E050TH E100TF E100TH E150TE E150TF E250TF E250TH E500TF E500TH E750TF
E250TE E500TE E100TE E250TC E050TC E100TC E500TC E150TH CE1500MC E150TC