www.carlingtech.com18
M-Series General Specifications
Agency Certifications
Table A: Lists UL Recognized and CSA Accepted configurations & performance capabilities as a Component Supplementary Protector.
Electrical
The low cost M-Series utilizes the hydraulic magnetic principle
which provides accurate and reliable circuit protection even when
exposed to extremely hot and/or cold application environments.
Available in a choice of rocker actuator styles and colors, push
button, push-pull, paddle, and baton style handle actuators, the
Visi-Rocker®two-color actuators as well as non-illuminated or illu-
minated rocker versions with LED or neon bulbs. The exclusive
Rockerguard®bezel helps prevent inadvertent actuation. "Wiping"
contact design insures long term reliability. Various styling options
allow design flexibility.
Typical applications include power supplies, medical equipment,
and telecommunications equipment. In addition, these breakers
meet CSA Standard 22.2 No. 100 for the Generator & Welder
markets.
NOTES FOR TABLE A
1 Polarity Sensitive
2 Available only with Special Catalog Number. Consult Factory.
3 Requires Branch Circuit Backup with a UL Listed type K-5 or RK-5 fuse rated 30 Amps maximum
4 Requires Branch Circuit Backup with a UL Listed type K-5 or RK-5 fuse rated 60 Amps maximum
UL Recognized
UL Standard 1077 Component Recognition Program as
Protectors, Supplementary (Guide
CCN/QVNU2, File E75596)
UL Listed
UL Standard 489A Communications Equipment (Guide
CCN/DITT, File E189195)
CSA Accepted Component Supplementary
Protector under Class 3215 30,
File 047848 0 000
CSA Standard C22.2 No. 235
VDE Certified EN60934, VDE 0642 under File
10537
TUV Certified EN60934, under License No.
R9671109
www.carlingtech.com 19
M-Series General Specifications
Electrical
NOTES FOR TABLE B
1 Polarity Sensitive
2 Available only with Special Catalog Number. Consult Factory.
3 Requires Branch Circuit Backup with a UL Listed type K-5 or RK-5 fuse rated 30 Amps maximum
4 TUV only, not VDE
5 Requires backup protection with a thermal magnetic circuit breaker rated 32 amps and having a Type C trip characteristic per EN60898/DIN VDE 0641 (C32A) for ratings greater than 15 amps,
and a thermal magnetic circuit breaker rated 16 amps and having a Type C trip characteristic per EN60898/DIN VDE 0641 (C16A) for ratings 15 amps and less.
Table B: Lists UL Recognized,CSA Accepted and TUV and VDE Certified configurations and performance capabilities as a
Component Supplementary Protector.
Table C: Lists UL489A Listed and TUV Certified configurations and performance capabilities for use in Communications
Equipment.
NOTES FOR TABLE C
1. Available only with Special Caralog Number
www.carlingtech.com20
M-Series General Specifications
Number of Poles 1 or 2
Internal Circuit Configurations Seri es with or without Auxiliary
Switch.
Switch Only with or without Auxiliary
Switch.
Weight Approximately 30 grams/pole
(Approximately 1.07 ounces/pole)
Standard Colors See Ordering Scheme.
MechanicalElectrical
Physical
Maximum Voltage 125/250 VAC 50/60 Hz, 80 VDC
(See Rating Tables.)
Current Ratings Standard current coils: 0.100, 0.250,
0.500, 0.750, 1.00 thru 15.0 in 1
amp increments, 18.0,
20.0, 25.0, 30.0. Other ratings avail-
able - see Ordering Scheme.
Auxiliary Switch Rating SPDT; 7A 250VAC, 7A (Res)
28VDC, 4A (Ind.) 28VDC, 0.25A
80VDC (Res) (silver contacts), 0.1A
125VAC (gold contacts).
Insulation Resistance Minimum of 100 Megohms at 500
VDC.
Dielectric Strength UL, CSA 1500V, 50/60 Hz for one
minute between all electrically isolat-
ed terminals. M-Series Circuit
Breakers comply with the 8mm
spacing and 3750 V 50/60Hz dielec-
tric requirements from hazardous
voltage to operator accessible sur-
faces, per Publications IEC 380,
435, 950, EN 60950 and VDE 0805.
Resistance, Impedance Values from Line to Load Terminal -
based on Series Trip Circuit Breaker.
Pulse Tolerance Curves
Endurance 10,000 ON-OFF operations @ 6 per
minute with rated Current and
Voltage.
Trip Free All M-Series Circuit Breakers will trip
on overload, even when actuator is
forcibly held in the ON position.
Trip Indication The actuator moves positively to the
OFF position when an overload
causes the circuit breaker to trip.
Designed and tested in accordance with requirements of specifi-
cation MIL-PRF-55629 & MIL-STD-202 as follows:
Shock Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Cond. I. Instantaneous
curves tested at 80% of rated current.
Vibration Withstands 0.060" excursion from 10-
55 Hz, and 10 Gs 55-500 Hz, at rated
current per Method 204C, Test
Condition A. Instantaneous curves
tested at 80% of rated current.
Moisture Resistance Method 106D, i.e., ten 24-hour
cycles @ + 25°C to +65°C, 80-98% RH.
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
to +25°C).
Operating Temperature -40° C to +85° C
Chemical Resistance Only the outside surfaces of the case
and the handles may be cleaned with
detergents or alcohol. Organic (hydro-
carbon based) solvents are not rec-
ommended because they attack plas-
tics. Caution should be taken when
solvents are used to clean and
remove flux from terminals. Lubricants
should not be introduced into the han-
dle/bushing openings.
Environmental
2 ACTUATOR 1
Handle
MPaddle NBaton
Push Button
TPush-Pull UPush To Reset
Push Button w/ Snap-In Mounting
VPush-Pull WPush To Reset
www.carlingtech.com 21
M-Series Handle/Pushbutton UL Recognized - Ordering Scheme
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
717 17.500
618 18.000
619 19.000
620 20.000
622 22.000
624 24.000
625 25.000
630930.000
6 CURRENT RATING (AMPERES)8
10
Legend
Plate
8
Actuator
Color
8 ACTUATOR COLOR5
Handle Push-Button Actuator Color
1AWhite
2BBlack
3CRed
4DGreen
5EBlue
6FYellow
8HOrange
12 AGENCY APPROVAL 8
CUL Recognized & CSA Accepted
DVDE Certified, UL Recognized & CSA Accepted
ETUV Certified, UL Recognized & CSA Accepted
10 LEGEND PLATE / BUTTON MARKING
Handle Actuator Legend Plate (Actuator Styles M & N)
ANo Legend Plate
BON - OFF Vertical
CON - OFF Horizontal
DI - O Vertical
EI - O Horizontal
Push-Pull Actuator Button Cap (Actuator Styles T & V)
1No Marking
2Rated Amps Horizontal
3Rated Amps Line Side Down
4Rated Amps Line Side Up
Push-to-Reset Actuator Button (Actuator Styles U& W)
1No Marking
7 TERMINAL8
1Push-On 0.250 Tab (Q.C.)
210 Screw 8-32 w/upturned lugs
310 Screw 8-32 (Bus Type)
A11 Push-In Stud
P12 Printed Circuit Board
3 POLES
1One 2Two
5 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
12 DC Short
14 DC Medium
20 50/60Hz Instantaneous
22 50/60Hz Short
24 50/60Hz Medium
30 DC, 50/60Hz Instantaneous
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
62 50/60Hz Short, Hi-Inrush
64 50/60Hz Medium, Hi-Inrush
72 DC, Short,Hi-Inrush
74 DC, Medium, Hi-Inrush
92 DC, 50/60Hz Short, Hi-Inrush
94 DC, 50/60Hz, Medium, Hi-Inrush
4 CIRCUIT 2
without Auxiliary Switch
ASwitch Only (No Coil), Maintained Contacts
BSeries Trip (Current)
with Auxiliary Switch, Silver Contacts Terminal Type:
P3 Switch Only, Maintained Contacts .060 Dia, Round Solder Turret
Q3, 4 Switch Only, Maintained Contacts .058 Dia, Round Q.C.
R3, 13 Switch Only, Maintained Contacts .080 Dia x .020 Flat Q.C.
S3Series Trip (Current) .060 Dia, Round Solder Turret
T3, 4 Series Trip (Current) .058 Dia, Round Q.C.
U3, 13 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C.
with Auxiliary Switch, Gold Contacts
23, 4 Switch Only, Maintained Contacts .058 Dia, Round Q.C.
33, 13 Switch Only, Maintained Contacts .080 Dia x .020 Flat Q.C.
43,4 Series Trip (Current) .058 Dia, Round Q.C.
53, 13 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C.
1 SERIES
M
6
Current Rating
4
Circuit
3
Poles
2
Actuator 9
Front Panel
Hardware
M
7
Terminal
5
Frequency
& Delay
1
Series
M 1 B 34 260 1 1 B B
Notes:
1 One actuator is located in the center of each multi-pole breaker. Actuator codes V & W
limited to single pole breakers only.
2 Switch Only circuits are not available with Push-To-Reset actuators.
For Switch Only circuits, select Current Coil Rating from the following chart:
12
Agency
Approval
11
Bushing
Color
B C
9 FRONT PANEL HARDWARE 6
Handle Push-Button
No outer Panel Hardware A1
Knurled Nut
Bright nickel B2
Bright nickel w/ locking ring C
Black D
Black w/ locking ring E
Panel Dress Nut
Bright nickel F
Bright nickel w/ locking ring G
Black H
Black w/ locking ring J
11 BUSHING COLOR 7
BBlack
3 One Auxiliary Switch is supplied per breaker. On two-pole breakers, standard Auxiliary
Switch mounting is in pole one. Auxiliary Switch option limited to Series Trip and Switch
Only circuits. Not available with back connect screw or push-in stud terminals.
4 Mates with AMP .058" diameter pin receptacles including 60983-1 (gold plated) and 60983-
2 (tin plated).
5 Actuator color is only visible in the OFF position on Push-Pull actuators.
6 All units except snap-in mounting have one hex nut installed on bushing for use behind the
panel.
7 Other colors available. Consult factory.
8 TUV and VDE Certification above 15 amps is for 2-pole only and is limited to a max. of 25
amps. Screw Terminal or Push-In Stud recommended above 20 amps.
9 30 amp rating not available with delay’s 30, 32, 34, 92 or 94.
10 Screw Terminals are VDE certified only with use of ring terminal attached to wire.
11 Terminal code A available with circuit codes A & B only.
12 Printed circuit board available with UL recognized approval only.
13 Auxiliary switch (flat Q.C.) available with UL recognized approvals only.
www.carlingtech.com22
M-Series Handle/Pushbutton UL489A/UL Recognized – Ordering Scheme
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
717 17.500
618 18.000
619 19.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
6 CURRENT RATING (AMPERES)
Notes:
1 One actuator is located in the center of each multi-pole breaker. Actuator codes V & W
limited to single pole breakers only.
2 One Auxiliary Switch is supplied per breaker. On two-pole breakers, standard Auxiliary
Switch mounting is in pole one. Auxiliary Switch option limited to Series Trip and Switch
Only circuits. Not available with Back Connected Screw or Push-in Stud terminals.
3 Mates with AMP .058" diameter pin receptacles including 60983-1 (gold plated) and
60983-3 (tin plated).
4 Screw terminals or Push-in Stud recommended above 20 amps.
5 Actuator color is only visible in the OFF position on Push-Pull actuators.
6 All units have one hex nut installed on bushing for use behind the panel.
7 Other colors available. Consult factory.
8 Not available with UL489A Listed breakers.
9 TUV certified to 25 amps. UL Recognized, CSA Accepted and UL Listed to 30 amps.
10 Terminal code A available with circuit codes A & B only.
11 Printed circuit board available with UL recognized approval only.
12 Auxiliary switch (flat Q.C.) available with UL recognized approvals only.
10
Legend
Plate
8
Actuator
Color
8 ACTUATOR COLOR & LEGEND 5
Gloss Handle Push-Button Actuator Color
1AWhite
2BBlack
3CRed
4DGreen
5EBlue
6FYellow
8HOrange
10 LEGEND PLATE / BUTTON MARKING
Handle Actuator Legend Plate (Actuator Styles M & N)
ANo Legend Plate
BON - OFF Vertical
CON - OFF Horizontal
DI - O Vertical
EI - O Horizontal
Push-Pull Actuator Button Cap (Actuator Styles T & V)
18No Marking
2Rated Amps Horizontal
3Rated Amps Line Side Down
4Rated Amps Line Side Up
Push-To-Reset Actuator Button Cap (Actuator Styles U & W)
18No Marking
3 POLES
1One
5 FREQUENCY & DELAY
12 DC Short
14 DC Medium 72 DC, Short, Hi-Inrush
74 DC, Medium, Hi-Inrush
4 CIRCUIT
without Auxiliary Switch
BSeries Trip (Current)
with Auxiliary Switch, Silver Contacts Terminal Type:
S 2 Series Trip (Current) .060 Dia, Round Solder Turret
T 2,3 Series Trip (Current) .058 Dia, Round Q.C.
U3, 12 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C.
with Auxiliary Switch, Gold Contacts
42,3 Series Trip (Current) .058 Dia, Round Q.C.
53, 12 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C.
1 SERIES
M
6
Current Rating
4
Circuit
3
Poles
2
Actuator 9
Front Panel
Hardware
M
7
Terminal
5
Frequency
& Delay
1
Series
M 1 B 14 620 1 1 B B
12
Agency
Approval
11
Bushing
Color
B J
9 FRONT PANEL HARDWARE 6
Handle Push-Button
No outer Panel Hardware A1
Knurled Nut
bright nickel B2
bright nickel w/ locking ring C
black D
black w/ locking ring E
Panel Dress Nut
bright nickel F
bright nickel w/ locking ring G
black H
black w/ locking ring J
11 BUSHING COLOR7
BBlack
12 AGENCY APPROVAL9
JUL489A Listed, TUV Certified
MUL Recognized, CSA Accepted
NUL Recognized, TUV Certified
TUL489A Listed
7 TERMINAL4
1Push-On 0.250 Tab (Q.C.)
2Screw 8-32 w/upturned lugs
3Screw 8-32 (Bus Type)
A10 Push-In Stud
P11 Printed Circuit Board
2 ACTUATOR 1
Handle
MPaddle NBaton
Push Button
TPush-Pull UPush To Reset
Push Button w/ Snap-In Mounting
VPush-Pull WPush To Reset
www.carlingtech.com 23
M-Series Rocker UL Recognized – Ordering Scheme
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
717 17.500
618 18.000
619 19.000
620 20.000
622 22.000
624 24.000
625 25.000
63012 30.000
6 CURRENT RATING (AMPERES)10
10
Legend
8
Illumination
10 LEGEND11
1No Legend
2ON - OFF Vertical
3ON - OFF Horizontal
4I - O Vertical
5I - O Horizontal
6Dual Vertical
7Dual Horizontal
3 POLES
1One 2Two
1 SERIES
M
6
Current Rating
4
Circuit
3
Poles
2
Actuator 9
Actuator
Color
M
7
Terminal
5
Frequency
& Delay
1
Series
G 2 B 34 620 1 H C 6
12
Agency
Approval
11
Bezel
Color
7 C
8 ROCKER ILLUMINATION
Non-illuminated
A
Neon
5
Neon Green Glow8
without resistor, 120VAC/250VAC BC
LED
7, 8
Red Green Amber
without resistor DG K
with resistor, 4-8 VDC EH L
with resistor, 9-16 VDC FJ M
9 ACTUATOR & LEGEND COLOR
Solid Color
Actuator Legend
1White Black
2Black White
3Red White
4Green White
5Blue White
6Yellow Black
7Gray Black
8Orange Black
Visi-Rocker
6
Visi & Legend (remainder of rocker same color as bezel)
1White
2Black
3Red
4Green
5Blue
6Yellow
7Gray
8Orange
Illuminated
8
Actuator Legend
AClear White
BRed Transparent White
CGreen Transparent White
DAmber Transparent White
ESmoke Gray Transparent White
FWhite Translucent Black
11 BEZEL COLOR / STYLE9
Color without Rockerguard with Rockerguard
White A1
Black B2
Gray G7
12 AGENCY APPROVAL10
CUL Recognized & CSA Accepted
DVDE Certified, UL Recognized & CSA Accepted
ETUV Certified, UL Recognized & CSA Accepted
5 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
12 DC Short
14 DC Medium
20 50/60Hz Instantaneous
22 50/60Hz Short
24 50/60Hz Medium
30 DC, 50/60Hz Instantaneous
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
62 50/60Hz Short, Hi-Inrush
64 50/60Hz Medium, Hi-Inrush
72 DC, Short, Hi-Inrush
74 DC,Medium, Hi-Inrush
92 DC, 50/60Hz Short, Hi-Inrush
94 DC, 50/60Hz, Medium, Hi-Inrush
7 TERMINAL10
1Push-On 0.250 Tab (Q.C.)
2 13 Screw 8-32 w/upturned lugs
3 13 Screw 8-32 (Bus Type)
A14 Push-In Stud
P15 Printed Circuit Board
Notes:
1 One actuator is located in the center of each multi-pole breaker.
2 For Switch Only circuits, select Current Coil Rating from the following chart:
3 One Auxiliary Switch is supplied per breaker. On two-pole breakers, standard Auxiliary Switch
mounting is in pole one. Auxiliary Switch option limited to Series Trip & Switch Only circuits, & is not
available in single pole illuminated breakers, or Back Connected Screw or Push-in Stud terminals.
4 Mates with AMP .058" diameter pin receptacles: 60983-1 (gold plated) & 60983-2 (tin plated).
5 For neon bulb applications at 120VAC @ 47K, 1/4 WATT and for 250VAC applications @ 150K,
1/4 WATT, external resistors must be supplied by customer.
6 On Visi-Rocker breakers, Visi portion of rocker cannot be the same color as the bezel.
7 For LED (DC or rectified AC) applications, LED is mounted in the center of the rocker actuator with
electrical characteristics: 100 millicandela at 20mA; Maximum power dissipation = 75mW at 25°C;
Maximum forward current = 25mA; Typical forward voltage = 2.1V at 20mA; Typical reverse current
= 100uA at 3V. Customer supplies the proper external resistor limiting current to these values.
8 Rocker color for LED’s and green neon lamp must be clear, smoke gray, white translucent or
match color of LED or neon lamp.
9 Other colors available. Consult factory.
10 TUV and VDE Certified to 25 amps. UL Recognized and CSA Accepted to 30 amps. Screw
Terminals or Push-in Stud recommended above 20 amps.
11 TUV or VDE Certified must have I-O or Dual Legends. Legend required on Visi-Rocker breakers.
12 30 amp rating not available with delay’s 30, 32, 34, 92 or 94.
13 Screw Terminals are VDE certified only with use of ring terminal attached to wire.
14 Terminal code A available with circuit codes A & B only.
15 Printed circuit board available with UL recognized approval only.
16 Auxiliary switch (flat Q.C.) available with UL recognized approvals only.
2 ACTUATOR 1
Non-Illuminated
single color
AAngled
BFlat
Two Color
Visi-Rocker
DIndicate ON
EIndicate OFF
llluminated
single color
FAngled
GFlat
4 CIRCUIT 2
without Auxiliary Switch
ASwitch Only (No Coil), Maintained Contacts
BSeries Trip (Current)
with Auxiliary Switch, Silver Contacts Terminal Type:
P3 Switch Only, Maintained Contacts .060 Dia, Round Solder Turret
Q3, 4 Switch Only, Maintained Contacts .058 Dia, Round Q.C.
R3, 16 Switch Only, Maintained Contacts .080 Dia x .020 Flat Q.C.
S3Series Trip (Current) .060 Dia, Round Solder Turret
T3, 4 Series Trip (Current) .058 Dia, Round Q.C.
U3, 16 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C.
with Auxiliary Switch, Gold Contacts
23, 4 Switch Only, Maintained Contacts .058 Dia, Round Q.C.
33, 16 Switch Only, Maintained Contacts .080 Dia x .020 Flat Q.C.
43,4 Series Trip (Current) .058 Dia, Round Q.C.
53, 16 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C.
www.carlingtech.com24
M-Series Rocker UL489A/UL Recognized – Ordering Scheme
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
717 17.500
618 18.000
619 19.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
6 CURRENT RATING (AMPERES)
2 ACTUATOR 1
Non-Illuminated single color
AAngled BFlat
Two Color Visi-Rocker
DIndicate ON EIndicate OFF
llluminated single color
FAngled GFlat
10
Legend
8
Illumination
12 AGENCY APPROVAL9
JUL489A Listed & TUV Certified
MUL Recognized & CSA Accepted
NTUV Certified, UL Recognized & CSA Accepted
TUL489A Listed
10 LEGEND10
1No Legend (Single Color or Illuminated Rocker Options Only)
2ON - OFF Vertical
3ON - OFF Horizontal
4I - O Vertical
5I - O Horizontal
6Dual Vertical
7Dual Horizontal
3 POLES
1One
5 FREQUENCY & DELAY
10 DC Instantaneous
12 DC Short
14 DC Medium
72 DC, Short,Hi-Inrush
74 DC, Medium, Hi-Inrush
4 CIRCUIT2
without Auxiliary Switch
BSeries Trip (Current)
with Auxiliary Switch, Silver Contacts Terminal Type
SSeries Trip (Current) .060 Dia, Round Solder Turret
T3Series Trip (Current) .058 Dia, Round Q.C.
U3, 13 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C.
with Auxiliary Switch, Gold Contacts
43 Series Trip (Current) .058 Dia, Round Q.C.
53, 13 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C.
1 SERIES
M
6
Current Rating
4
Circuit
3
Poles
2
Actuator 9
Actuator
Color
M
7
Terminal
5
Frequency
& Delay
1
Series
A 1 B 14 620 1 A 1 6
12
Agency
Approval
11
Bezel
Color
2 J
8 ILLUMINATION
Non-illuminated
A
Neon
4
Neon Green Glow 7
without resistor, 120VAC/250VAC BC
LED
Red Green Amber
without resistor 5, 7 DG K
with resistor, 4-8 VDC EH L
with resistor, 9-16 VDC FJ M
9 ACTUATOR & LEGEND COLOR
Solid Color
Actuator Legend
1White Black
2Black White
3Red White
4Green White
5Blue White
6Yellow Black
7Gray Black
8Orange Black
Visi-Rocker
6
Visi & Legend (remainder of rocker same color as bezel)
1White
2Black
3Red
4Green
5Blue
6Yellow
7Gray
8Orange
Illuminated
7
Actuator Legend
AClear White
BRed Transparent White
CGreen Transparent White
DAmber Transparent White
ESmoke Gray Transparent White
FWhite Translucent Black
11 BEZEL COLOR / STYLE8
Color without Rockerguard with Rockerguard
White A1
Black B2
Gray G7
7 TERMINAL 9
1Push-On 0.250 Tab (Q.C.)
2Screw 8-32 w/upturned lugs
3Screw 8-32 (Bus Type)
A11 Push-In Stud
P12 Printed Circuit Board
Notes:
1 One actuator is located in the center of each multi-pole breaker.
2 One Auxiliary Switch is supplied per breaker. Auxiliary Switch option limited to Series Trip &
Switch Only circuits, and is not available in single pole illuminated breakers, or with Back
Connected Screw or Push-in Stud terminals.
3 Mates with AMP .058" diameter pin receptacles: 60983-1 (gold plated) & 60983-1 (tin plated).
4 For neon bulb applications at 120VAC @ 47K, 1/4 WATT and for 250VAC applications @
150K, 1/4 WATT, external resistors must be supplied by customer.
5 For LED (DC or rectified AC) applications, LED is mounted in the center of the rocker actua-
tor with electrical characteristics as follows: 100 millicandela at 20mA; Maximum power dis-
sipation = 75mW at 25°C; Maximum forward current = 25mA; Typical forward voltage =
2.1V at 20mA; Typical reverse current = 100uA at 3V. Customer supplies the proper exter-
nal resistor limiting current to these values.
6 On Visi-Rocker breakers, Visi portion of rocker cannot be the same color as the bezel.
7 Rocker color for LED’s and green neon lamp must be clear, smoke gray, white translucent
or match color of LED or neon lamp.
8 Other colors available. Consult factory.
9 TUV Certified to 25 amps. UL Recognized, CSA Accepted and UL489A Listed to 30 amps.
Screw Terminals recommended above 20 amps.
10 UL489A Listed must have ON-OFF or Dual legends. TUV Certified approvals must have
I - O or Dual legends.
11 Terminal code A available with circuit codes A & B only.
12 Printed circuit board available with UL recognized approval only.
13 Auxiliary switch (flat Q.C.) available with UL recognized approvals only.
www.carlingtech.com 25
M-Series Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
www.carlingtech.com26
M-Series Handle – Form & Fit Drawings
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ± 0.20 [.51] unless otherwise specified.
www.carlingtech.com 27
M-Series Handle – PC Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
www.carlingtech.com28
M-Series Pushbutton – Circuit & Ter minal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
www.carlingtech.com 29
M-Series Pushbutton – Form & Fit Drawings
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ± 0.20 [.51] unless otherwise specified.
3 Available with Push-Pull or Push-to-Reset Actuators.
www.carlingtech.com30
M-Series Push-Pull – PC Terminal Drawings
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
www.carlingtech.com 31
M-Series Rocker – Circuit & Ter minal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 Schematic shown represents current trip circuit.
www.carlingtech.com32
M-Series Rocker – Form & Fit Drawings
Notes:
1 Dimensions apply to all variations shown. Notice that circuit breaker line & load terminal orientation on indicate OFF is opposite of indicate ON.
2 I-O, ON-OFF or dual legends available for vertical or horizontal mounting. For pole orientation with horizontal legend, rotate front view clockwise 90°.
3 All dimensions are in inches [millimeters].
4 Tolerance ± 0.20 [.51] unless otherwise specified.
www.carlingtech.com 33
M-Series Rocker – Supplementary Diagrams