https://www.phoenixcontact.com/us/products/2906853
04/13/2017Page2/6
Surge protection device-TTC-6-TVSD-D-60DC-PT-I-2906853
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20 (with end cover)
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C3
Nominal voltage UN60 V DC
Maximum continuous voltage UC75 V DC
Rated current 10 A (60°C)
Operating effective current IC at UC≤ 5 µA
Nominal discharge current In (8/20) µs (core-GND) 60 A
Voltage protection level Up (core-GND) ≤ 110 V (C3 - 12 A)
Response time tA (core-earth) ≤ 1 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 1.2 MHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system typ. 4 MHz
Capacity (Core-GND) 0.6 nF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (conductor-GND) C3 - 12 A
Connection data
Connection method Push-in connection
Connection method IN Push-in connection
Connection method OUT Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012