Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (05.05.03) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Type: Dupline®
H4-Housing
Combined module
Interface type
DC supply
Lucky Goldstar master
Plug and play: Automatic communication with specific
PLC/Controllers
Built-in normal Dupline®Channel Generator
128 I/O’s and DC power supply on 3 wires
RS232/RS422/RS485 port for interfacing to control
system
Split-I/O mode selectable (128 inputs and 128 outputs)
LED-indications for supply, Dupline®carrier and Com-
port Tx
Galvanically isolated Com-port supplied by internal
DC/DC converter
Product Description Ordering Key
G 3496 0001 is designed as
a cost-effective Plug & Play
solution for interfacing
Dupline®I/O’s to a Lucky
Goldstar PLC. It performs
three functions: Dupline®
channel generator, power
supply synchronization (en-
ables 3-wire system with
supply) and RS232/RS422/
RS485 interface.
Type Selection
Supply PLC Interface type Ordering no.
20-30 VDC Lucky Goldstar K-serie G 3496 0001 700
G 3496 0001 700
Input/Output Specifications
Dupline®Plug & Play Master Module
Interface for Lucky Goldstar PLC
Power output
Output voltage 20-30 VDC (pulsating)
Output current < 3.0 A @ 50ºC
Short circuit protection 4 A quick acting fuse
Output voltage drop < 1.0 V
Dupline®carrier
Output voltage 8.2 V (pulsating)
Current < 60 mA
Short circuit protection Yes
Scan time
128 channels 132.2 ms
64 channels 69.8 ms
Communication port
Standard RS232/RS422/RS485
Split I/O mode Yes, selectable
Normal Dupline mode Yes, selectable
Connection 9 pole female Sub-D
Dielectric voltage
Com-port Dupline®1 kVAC (rms)
Protocol LG Serial Communication
Standard
Baud rate 19200
Data bits 8
Start bit 1
Stop bit 1
Parity None
Flow-control None
Type G 3496 0001
Input/Output Specifications (Cont.)
Pin assignment
2-wire RS 485
S/R Data line + (B) Pin 3
S/R Data line - (A) Pin 8
GND Pin 5
4-wire RS 485/RS 422
R Data line + (B) Pin 3
R Data line - (A) Pin 8
S Data line + (B) Pin 2
S Data line - (A) Pin 7
Direction Pin 4
(Connect to GND pin 5
when using 4-wire commu-
nication)
RS 232
TX Pin 1
RX Pin 9
GND Pin 5
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Operational voltage (Vin) 20-30 VDC
Reverse polarity protection None
Current consumption < 150 mA + Power load
Power dissipation < 5 W
Transient protection voltage 800 V
Dielectric voltage
Supply - Dupline®None
Supply - com-port 1 kVAC (rms)
Power ON delay 2 s
Indication for
Com-port Tx LED, red
Supply ON LED, green
Dupline®carrier LED, yellow
Environment
Pollution degree 3 (IEC 60664)
Operating temperature to +50°C (+32° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Du line
®
Fieldbus Installationbus
2Specifications are subject to change without notice (30.08.00)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Mode of Operation
The Dupline
®
Master Module
(DMM) controls a 3-wire bus
with signal, DC-power and
common GND. The DMM is
connected to a standard DC-
supply, which it synchronizes
with the Dupline
®
carrier signal
before it is output to supply.
The synchronization is neces-
sary in order to enable the
Dupline
®
and DC-supply to
share the GND-wire.
The Dupline
®
Master Module is
a Dupline
®
Channel Generator
with the function of a master.
This means that the 128
Dupline
®
I/O’s will be read/writ-
ten by the DMM and then sent
to the PLC.
The DMM can run in two dif-
ferent modes – Normal mode
and split I/O mode. In Normal
mode, Dupline
®
operates as a
peer-to-peer system, where
the channel generator auto-
matically establishes a con-
nection between Dupline
®
inputs and Dupline
®
outputs
which are coded to the same
Dupline
®
address. If e.g. an
input coded for B5 is activat-
ed, the output(s) coded for B5
will also be activated.
Consequently, a Dupline
®
-out-
put can either be activated
through the output-data
received on DMM or by an
active Dupline
®
input coded
for the same Dupline
®
-
address. In “Split I/O” mode,
the channel generator treats
the Dupline
®
inputs and
Dupline
®
outputs indepen-
dently. If e.g. an input coded
for B5 is activated, the DMM
will make the information avail-
able for the PLC (like in normal
mode), but it will not automati-
cally activate the Dupline
®
out-
put(s) coded to B5. The
Dupline
®
outputs are con-
trolled exclusively through the
output data received from the
PLC. In this mode, up to 128
Dupline
®
inputs and 128
Dupline
®
outputs are available,
since an input and an output
coded to the same Dupline
®
address can operate indepen-
dently.
G 3496 0001
General Specifications
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions H4-Housing
Material (see Technical information)
Weight 100 g
Dip-Switch Setting
Sw.4 On: Split I/O Channel Generator Mode
(See “Mode of Operation”)
Off: Normal Dupline
®
Monostable Channel
Generator Mode
Sw.5 On: 64 Dupline
®
channels
Off: 128 Dupline
®
channels
Installation Hints
No TX-LED
Hardware fault Check the wiring.
No Dupline
®
Carrier-LED
Short circuit Short circuit between the
two Dupline
®
wires.
Pin Assignment
1
9
8
7
6
5
4
3
2
Only for G 2196 0001
Wiring Diagram
1234
21 22 27 28
Supply in
20-30 V DC
24
23
678
5
26
25
+-
Power out
GND
Dupline Signal
RS 232
RS 485
3W
Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (30.08.00) 3
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Memory Mapping
Dupline®Lucky Goldstar Dupline®Lucky Goldstar
Channel Channel
Read Write Read Write
A1 M000 M080 E1 M020 M100
A2 M001 M081 F1 M028 M108
A3 M002 M082 G1 M030 M110
A4 M003 M083 H1 M038 M118
A5 M004 M084 I1 M040 M120
A6 M005 M085 J1 M048 M128
A7 M006 M086 K1 M050 M130
A8 M007 M087 L1 M058 M138
B1 M008 M088 M1 M060 M140
B8 M00F M08F N1 M068 M148
C1 M010 M090 O1 M070 M150
D1 M018 M098 P1 M078 M158
Table of the memory mapping
Accessories
Cable for Communication port RS485-CAB
Additional Information
Scope of supply
1 x Master Module G3496 0001 700
G 3496 0001