G
B
DELTA profil Pushbutton single UP 241 5WG1 241-2AB_1
UP 242 5WG1 242-2AB_1
Pushbutton
double UP 243 5WG1 243-2AB_1
UP 244 5WG1 244-2AB_1
Pushbutton
quadruple UP 245 5WG1 245-2AB_1
UP 246 5WG1 246-2AB_1
DELTA style Pushbutton single UP 285 5WG1 285-2AB_1
Pushbutton
double UP 286 5WG1 286-2AB_1
Pushbutton
quadruple UP 287 5WG1 287-2AB_1
As at: March 2008
Operating and mounting instructions
Products
Pushbutton single
Pushbutton double
Pushbutton quadruple
DELTA profil: cut-out frames ordered separately from the DELTA ranges
Frame
DELTA style: frames ordered separately from the DELTA ranges
Bus coupling unit bus coupling unit UP 110 or UP 114 ordered separately
Diagram 1: Mounting the pushbutton
C1 Bus coupling unit
C2 Frame
C3 Fixing screws *)
C4 Basic pushbutton module *)
C5 Rockers *)
C6 Mounting rack *)
C7 Recess *)
*) Scope of supply
Product and functional description
There is an upper and a lower operating field on the push-
buttons. In the middle of the pushbutton there is a note
panel in which pictograms can be inserted. This panel also
contains display elements (LEDs) for orientation lighting and
also for status indication. Opposing rockers are combined to
form a pair e.g. for defined switching, dimming, controlling
shutters and blinds.
It is also possible to carry out the switching functions ON and
OFF e.g. via a pushbutton “UP”.
Using an application program, the flush-mounted pushbut-
tons give commands via the flush-mounted bus coupler for
example to actuators for defined switching on/off, for dim-
ming lamps, raising/lowering shutters or for louvre adjust-
ment or other parameterisable functional units.
The device pushbutton is placed together with the relevant
DELTA frame on the flush-mounted bus coupler and can only
function in combination with the bus coupler UP and an ap-
propriate application program, i.e. the pushbutton (with bus
coupler UP) consist of the device (hardware) and the applica-
tion program (software).
The bus coupler UP and the relevant frame are not supplied
with the device but must be ordered separately.
Using the ETS program the application programs can be se-
lected and the specific parameters and addresses can be as-
signed.
Additional Informations
http://www.siemens.com/gamma
Technical data
Power supply
via the flush-mounted bus coupler
Operating elements
1, 2 or 4 pairs of rockers, idle in the middle position
Display elements
per pair of pushbuttons 1 LED red for status indication
e.g. quadruple pushbutton = 4 LEDs red
1 LED red for orientation light
Connections
10-pole plug connector (PEI): for connection to the flush-
mounted bus coupler
Mechanical data
Dimensions:
- DELTA profil (L x W x D ): 65 x 65 x 11 mm
- DELTA style (L x W x D ): 68 x 68 x 14 mm
Weight: approx. 40 g
Electrical safety
Type of protection (according to EN 60529): IP 20
Environmental conditions
Ambient operating temperature: - 5 ... + 45 °C
Storage temperature: - 25 ... + 70 °C
Relative humidity (not condensing): 5 % to 93 %
Markings
KNX / EIB
Please turn over !
C5
C6
C5
C1
C2
C5
C7
C5
C5
C7
C3
C4
C7
C4
C3
C4
C3
C6
C5
C6
Location and function of the operating and display
elements
A1
A2
A3
A4
A5
Pushbutton single
A1
A2
A3
A4
A5
Pushbutton double
A1
A2
A3
A4
A5
Pushbutton quadruple
Diagram 2: Location of display and operating elements
A1 Upper operating field
A2 LEDs for status indication
A3 LED as an orientation light
A4 Lower operating field
A5 Cover for pictograms
Mounting
The device can be used for permanent interior installa-
tions, in dry rooms and for insertion in flush-type boxes.
V DANGER
JJJJJJJJJJJJJJJJJJJJJJJJJJ
The device may only be installed and commissioned by an
authorised electrician.
The device may not be inserted in the same box as 230 V
devices.
The device may be used in switch sockets, if VDE
approved devices have been used.
The prevailing safety and accident regulations must be
observed.
The device may not be opened.
For planning and construction of electric installations, the
relevant guidelines, regulations and standards of the re-
spective country are to be considered.
General description
The pushbutton is placed together with the relevant frame
on the flush-mounted bus coupler.
The flush-mounted bus coupler (C1) is connected in the
flush-type box and fixed in position (refer to the installation
instructions for the bus coupler).
Mounting sequence
Place the basic pushbutton module (C4, diagram 3) with
the relevant frame (C2) on the flush-mounted bus coupler
(C1) and press the one strongly upon the other.
Using fixing screws:
If the fixing screws (C3) are used first of all the rockers
(C5) have to be lifted out altogether. This can be achieved
by inserting the screwdriver between the frame in the re-
cess (C7) and applying leverage (diagram 4).
Important: The pushbutton module (C4, diagram 3) and
the rockers (C5) together with the frame (C2)
must be held down / pressed down.
Screw down the fixing screws (C3).
The rockers (C5) have to be orientated properly and
clicked upon the mounting rack (C6).
C5
C5
C3
C6
C7
C4
C2
C1
C5
C5
C3
C6
C7
C4
C5
C5
C3
C6
C7
C4
Diagram 3: mounting sequence
Drawing for mounting the fixing screws (C3)
Pushbutton single
Pushbutton double / pushbutton quadruple
Holding down as shown with pushbutton single
Diagram 4: Lifting out the rockers
Inserting pictograms
Lift out the pictogram cover (A5) with the screwdriver by
applying leverage, during this hold down the pushbutton
module (C4).
DELTA profil
Insert the screwdriver into the slot (A2) until it reaches
the stop and then wiggle it.
Diagram 5: Lifting out the pictogram cover
Lay the pictograms onto the foundation.
Snap on the pictogram cover (A5) again.
DELTA style
1) Insert the screwdriver between the frame and the
pushbutton module
2) Swivel the screwdriver towards the wall.
Diagram 6: Lifting out the pictogram cover
retaining tongue
pictogram
pictogram X)
foundation
X)
foundation
Diagram 7: inserting the pictograms
Snap on the pictogram cover (A5) again.
Dismantling
Without fixing screws
Remove the pushbutton (C4) completely together with
the frame (C2) from the flush-mounted bus coupler (C1):
a) with the mere hand
b) with a screwdriver beneath the frame / wall
a) b)
Diagram 8: Dismantling
With fixing screws
Remove the rockers as described at „Mounting / Using
fixing screws“.
Screw out the fixing screws (C3).
Snap on the rockers (C5) again.
Remove the whole pushbutton module (C4) as described
at „ Without fixing screws “.
General Notes
The operating instructions must be handed over
to the client.
Any faulty device should be returned to the local
Siemens office.
If you have further questions concerning the product
please contact our technical support:
! +49 (180) 5050-222
! +49 (180) 5050-223
" www.siemens.com/automation/support-request
251523.41.11
DS04
1) 2)
1) 2)
C7