EMC filters
Series/Type: B84776*A000
Date: November 2012
© EPCOS AG 2012. Reproduction, publication and dissemination of this publication, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
1) To IEC 60529
Power line filters for 1-phase systems
Rated voltage 250 V AC/DC
Rated current 1 A to 10 A
Construction
2-line filter with IEC connector, fuse holder and switch
Appliance connector according to IEC/EN 60320-1
Fuse holder for 2 fuses 5×20 mm
Metal case
2-pole rocker switch
Versions
Standard version (B84776A*)
Medical version with low leakage current (B84776M*)
Features
Easy to install
Compact design
Cost optimized construction
Degree of protection from front side IP 401)
UL and cUL approval obtained
ENEC 10 approval is pending
Applications
Switched-mode power supplies for
industrial electronics
telecom systems
data systems
DC applications
Measuring instruments
Medical engineering
Terminals
Line side: IEC inlet C14 according to IEC/EN 60320-1
Load side: Tab connectors 6.3 ×0.8 mm
Marking
Marking on component:
Manufacturer's logo, ordering code, rated voltage, rated
current, rated temperature, climatic category, date code
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
2-line filters B84776*A000
IEC inlet filters
Page 2 of 10Please read Cautions and warnings and
Important notes at the end of this document.
Typical circuit diagram of B84776A*A000 (standard version)
Typical circuit diagram of B84776M*A000(medical version)
2-line filters B84776*A000
IEC inlet filters
Page 3 of 10Please read Cautions and warnings and
Important notes at the end of this document.
1) Calculation according draft proposal IEC 609391 Ed. 3 (20081029), annex A, ”Calculation of leakage current” at 50 Hz. In practice
are up to double values to be expected due to the insulation resistance values of the used ceramic capacitors. For the medical version
results computationally the value 0. In practice are values 1 ... 2 µA to be expected due to the insulation resistance values of the used
materials.
Technical data and measuring conditions of B84776*A000
Rated voltage VR250 V DC/AC
Rated frequency fR50/60 Hz
Test voltage line to line for 2 s Vtest 760 V AC
Test voltage line to case for 2 s (B84776A*) Vtest 2000 V AC
Test voltage line to case for 2 s (B84776M*) Vtest 2500 V AC
Rated temperature TR40 °C
Climatic category (IEC 60068-1) 25/085/21
Rocker switch Rating 10 A HP) / 250 V AC
Inrush current 82 A
Electrical life time
ON OFF
10000 cycles
Mechanical life time
ON OFF
50000 cycles
Characteristics and ordering codes of B84776*A000
VR= 250 V AC/DC
IR
A
CR
X2
µF
CR
Y2
pF
LR
mH
Ileak1)
mA
Rbleed
M
Approx.
weight
g
Ordering code Approvals
×= approval is granted
P = approval is pending
1 1 ×0.22 2 ×2200 2 ×7.6 0.173 1 90 B84776A0001A000 P × ×
1×0.22 2×7.6 0 1 90 B84776M0001A000 P × ×
2 1 ×0.22 2 ×2200 2 ×2.0 0.173 1 90 B84776A0002A000 P × ×
1×0.22 2×2.0 0 1 90 B84776M0002A000 P × ×
4 1 ×0.22 2 ×2200 2 ×1.0 0.173 1 90 B84776A0004A000 P × ×
1×0.22 2×1.0 0 1 90 B84776M0004A000 P × ×
6 1 ×0.22 2 ×2200 2 ×0.46 0.173 1 90 B84776A0006A000 P × ×
1×0.22 2×0.46 0 1 90 B84776M0006A000 P × ×
10 1 ×0.22 2 ×2200 2 ×0.33 0.173 1 130 B84776A0010A000 P × ×
1×0.22 2×0.33 0 1 130 B84776M0010A000 P × ×
2-line filters B84776*A000
IEC inlet filters
Page 4 of 10Please read Cautions and warnings and
Important notes at the end of this document.
Dimensional drawing
Dimensions in mm
ISO 2768-cl
2-line filters B84776*A000
IEC inlet filters
Page 5 of 10Please read Cautions and warnings and
Important notes at the end of this document.
Insertion loss (typical values at Z = 50 )
Filter for 1 A Filter for 2 A
Filter for 4 A Filter for 6 A
2-line filters B84776*A000
IEC inlet filters
Page 6 of 10Please read Cautions and warnings and
Important notes at the end of this document.
Insertion loss (typical values at Z = 50 )
Filter for 10 A
2-line filters B84776*A000
IEC inlet filters
Page 7 of 10Please read Cautions and warnings and
Important notes at the end of this document.
Insertion loss (typical values at Z = 50 )
Filter for 1 A Filter for 2 A
Filter for 4 A Filter for 6 A
2-line filters B84776*A000
IEC inlet filters
Page 8 of 10Please read Cautions and warnings and
Important notes at the end of this document.
Insertion loss (typical values at Z = 50 )
Filter for 10 A
2-line filters B84776*A000
IEC inlet filters
Page 9 of 10Please read Cautions and warnings and
Important notes at the end of this document.
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical re-
quirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar
with them than the customers themselves. For these reasons, it is always ultimately incum-
bent on the customer to check and decide whether an EPCOS product with the properties de-
scribed in the product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or
failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in
which the malfunction or failure of an electronic component could endanger human life or
health (e.g. in accident prevention or lifesaving systems), it must therefore be ensured by
means of suitable design of the customer application or other action taken by the customer
(e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by
third parties in the event of malfunction or failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Ma-
terial Data Sheets on the Internet (www.epcos.com/material). Should you have any more de-
tailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order. We also
reserve the right to discontinue production and delivery of products. Consequently, we
cannot guarantee that all products named in this publication will always be available. The
aforementioned does not apply in the case of individual agreements deviating from the fore-
going for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current ver-
sion of the "General Terms of Delivery for Products and Services in the Electrical In-
dustry" published by the German Electrical and Electronics Industry Association
(ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CeraLink, CSMP, CSSP, CTVS,
DeltaCap, DigiSiMic, DSSP, FilterCap, FormFit, MiniBlue, MiniCell, MKD, MKK, MLSC,
MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap, SIFERRIT, SIFI, SIKOREL,
SilverCap, SIMDAD, SiMic, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse,
WindCap are trademarks registered or pending in Europe and in other countries. Further
information will be found on the Internet at www.epcos.com/trademarks.
Important notes
Page 10 of 10