General
User interface Graphical LCD with blue backlight and text in
English, French, German, Russian and Spanish
LEDs Four status-indicating LEDs
Topology True online, double-conversion
Diagnostics Full system self-test
UPS bypass Automatic bypass
Dimensions See models table
Rail kit Included with all rackmount units
Electrical input
Nominal voltage 240V
Voltage range 240V: 160–276 Vac (with load PF of 0.7)
Frequency 50/60 Hz
Frequency range 45–65 Hz
Electrical output
Power factor 0.9
On utility voltage ±3% of nominal
regulation
On battery voltage ±3% of nominal
regulation
Efficiency >93% high-efficiency mode; >90% online mode (700VA - 3000VA)
>98% high-efficiency mode; >94% online mode (6000VA)
Frequency regulation ±3% Hz online
Technical specifications
Communications
Serial port RS-232 standard, for interface to power
management software
USB port HID standard
Relay output Common alarm standard
Communications slot Optional communication slots (BD Slot)
Optional communication ConnectUPS Web/SNMP card
cards AS400/Relay card
Cables USB and serial cable
included Input power cable
2 x 10Amp IEC to IEC output cable (rack models only)
Environmental
Safety markings 240V: CE, GS
EMC markings 240V: CE (per IEC/EN62040-2: Emissions, Category
C1; Immunity, Category C2)
Audible noise <50 dB
Ambient operating 0˚C to +40˚C
Storage temperature -20˚C to +40˚C with batteries and
-25˚C to +55˚C without batteries
Relative humidity 5–90% non-condensing
© 2010 Eaton Corporation
All Rights Reserved
044PQ
Note: 1. Height dimensions include feet on tower models, allow up to 150mm to depth for cable connections, accessories & ventilation.
2. For longer battery runtimes refer to battery chart.
TOWER AND RACK MODELS
Rating Input Dimensions Weight Runtime
Catalogue number Description (VA/Watts) connection Output receptacles H x W x D, in mm kg (100/50% load)
9130 Tower Models: 240V, 50/60 Hz1
PW9130G700T-XLAU PW9130 700VA AUS TOWER 700/630 C14 (4) Aust 10A 250 x 160 x 355 13 5/14
PW9130G1000T-XLAU PW9130 1000VA AUS TOWER 1000/900 C14 (4) Aust 10A 250 x 160 x 383 15 6/19
PW9130G1500T-XLAU PW9130 1500VA AUS TOWER 1500/1350 C14 (4) Aust 10A 250 x 160 x 435 19 5/14
PW9130G2000T-XLAU PW9130 2000VA AUS TOWER 2000/1800 C14 (1) C13, (5) Aust 10A 345 x 214 x 410 35 11/27
PW9130G3000T-XLAU PW9130 3000VA AUS TOWER 3000/2700 C20 (1) C19, (5) Aust 15A 345 x 214 x 410 35 6/15
PW9130G6000T-XLAU PW9130 6000VA AUS TOWER 6000/5400 Hardwire Hardwire 574 x 244 x 542 75.5 6/19
9130 Tower Extended Battery Modules1,2
PW9130N1000T-EBM PW9130 1000 EBM TOWER NA NA NA 250 x 160 x 383 19 -
PW9130N1500T-EBM PW9130 1500 EBM TOWER NA NA NA 250 x 160 x 435 25 -
PW9130N3000T-EBM PW9130 2000/3000 EBM TOWER NA NA NA 345 x 214 x 410 50 -
PW9130N6000T-EBM PW9130 6000 EBM TOWER NA NA NA 574 x 244 x 542 111 -
9130 Rack Models: 240V, 50/60 Hz1
PW9130G1000R-XL2UAU PW9130 1000VA AUS RACK 1000/900 C14 (4) C13, (2) Aust 10A 86.5 x 438 x 450 23 6/19
PW9130G1500R-XL2UAU PW9130 1500VA AUS RACK 1500/1350 C14 (4) C13, (2) Aust 10A 86.5 x 438 x 450 25 5/14
PW9130G2000R-XL2UAU PW9130 2000VA AUS RACK 2000/1800 C14 (4) C13, (4) Aust 10A 86.5 x 438 x 600 31 6/16
PW9130G3000R-XL2UAU PW9130 3000VA AUS RACK 3000/2700 C20 (4) C13, (1) C19, (3) 86.5 x 438 x 600 31 3/9
9130 Rack Extended Battery Modules
1,2
PW9130N1000R-EBM2U PW9130 1000 EBM RACK NA NA NA 86.5 x 438 x 438 29 -
PW9130N1500R-EBM2U PW9130 1500 EBM RACK NA NA NA 86.5 x 438 x 438 29 -
PW9130N3000R-EBM2U PW9130 2000/3000 EBM RACK NA NA NA 86.5 x 438 x 600 38 -
Eaton Industries Pty. Ltd.
Electrical Sector
Head Office:
10 Kent Road Mascot,
NSW 2020 Australia
1300 UPS UPS (1300 877 877)
www.eaton.com/powerquality