Gland Plate Installation Instructions FSA 3 3 FSB & FSC 2 4 4 Ground (Earth) 2 1 5 1 O 22.8 mm 5 nd u ro G FSB FSC Clamp (not included) CAUTION 1. Bonding between conduit connections is not automatic and must be provided as a part of the installation. 2. The Earth bonding conductor must be equal or greater in cross-section to the power supply cable. 3. GROUNDING (EARTH) must be made at points shown in illustration above. Wire Size and Terminal Torques - Field Wiring Connectors Metric NPT PG O 18.8 mm M16x1.5 3 11 O 22.8 mm M25x1.5 1/2 Inch - 16 16 O 28.0 mm M25x1.5 3/4 Inch 16 /8 Inch Frame Size A B C Tightening Torque (Nm) Tightening Torque (lbf.in) 1.1 1.5 2.25 10 13.3 Recommended Minimum 2 Cable Cross Section (mm ) 20 1 1.5 2.5 2.5 6 10 Recommended Minimum Cable Cross Section (AWG) 17 AWG 16 AWG 14 AWG Maximum Cable Cross Section (AWG) 14 AWG 10 AWG 8 AWG Maximum Cable Cross 2 Section (mm ) O22.8 mm O18.8 mm O22.8 mm O28.0 mm O18.8 mm O28.0 mm Clip (not included)