Description
The Bussmann™ series CUBEFuse™ holder is a
finger-safe modular system of single-pole 30, 60,
100, 200, 225 and 400 amp holders. All holders
dovetailed together to create the desired number
of poles for the application, including mixed amp
ratings between the 30, 60 and 100 amp holders.
The 200, 225 and 400 amp holders require
installing lugs to make conductor connections.
These are listed on page 3.
The CUBEFuse holder is available as the 600 V
UL® Listed version utilizing the time-delay Low-
Peak™ CUBEFuse (TCF up to 400 A) or fast-acting
CUBEFuse (FCF up to 100 A), or the 690 V UL
Recognized version utilizing the fast-acting wind
CUBEFuse (WCF up to 100 A).
Ratings
• Volts
• 600 Vac / 300 Vdc (UL Listed)
• 690 Vac (UL Recognized up to 100 A)
• Amps
• 30, 60, 100, 200, 225, 400 A
• SCCR
• 300 kA RMS Sym. (30, 60, 100 A UL Listed)
• 200 kA RMS Sym. (200, 225, 400 A UL
Listed)
• 200 kA RMS Sym. (CSA® Certified 100 A and
below)
• 100 kA DC (UL Listed and CSA Certified 100
A and below)
• 50 kA RMS Sym. (UL Recognized)
Agency information
• 600 V UL Listed, Guide IZLT, File E14853
• 690 V UL Recognized, Guide IZLT2, File E14853
• CSA Certified, Class 6225-01, File 47235, cURus
component Certified (30, 60 and 100 A holders)
• CE (100 A and below)
• RoHS compliant
Mounting
• 35 mm DIN-Rail/panel (Up to 100 A)
• Panel mount (200 to 400 A)
Operating and storage temperature range
• -40°C to 80°C (-40°F to 176°F)
Catalog no.
Max holder
amps
Fuse amp
range
600 V UL Listed
TCFH30N 30 1-30
TCFH60N 60 1-60
TCFH100N 100 1-100
TCFH200N 200 110-200
TCFH225N 225 110-225
TCFH400N 400 110-400
690 V UL Recognized
TCFH30NW 30 1-30
TCFH60NW 60 1-60
TCFH100NW 100 1-100
Features
• Finger-safe construction for enhanced safety*
• Amp rating rejection helps prevent overfusing
by rejecting higher fuse amp ratings
• Smallest installed fuse and holder footprint of
any Class J or R installation
• All holders dovetail together to create the
required number of poles, mixed 30, 60 and 100
A holders dovetail together
• 30, 60 and 100 A holders have dual wire rated
box lug terminals for wiring ease
• 200, 225 and 400 A holders available with
a variety of lugs and terminal shrouds for
application flexibility
• Up to 300 kA SCCR withstands high fault
currents
* 200, 225 and 400 A holders require installed shrouds.
Technical Data 9007 Effective March 2019
Supersedes February 2019
BUSSMANN
SERIES
2
Technical Data 9007
Effective March 2019
UL Class CF CUBEFuse holders
Eaton.com/bussmannseries
30, 60 and 100 A CUBEFuse holder fuse applications
Holder
catalog no. Volts
CUBEFuse type and amp range
TCF and TCF_RN FCF_RN WCF_RN
TCFH30N
600
1-30 1-30
TCFH60N 1-60 1-60
TCFH100N 1-100 1-100
TCFH30NW
690
1-30
TCFH60NW 1-60
TCFH100NW 1-100
Conductor ratings and torque for 30, 60 and 100 A holders
Ratings are for 75°C Cu AWG solid/stranded conductors. Torque is in
N•m (lb-in).
Terminal
wire
rating
Holder catalog no.
TCFH30N /
TCFH30NW
TCFH60N /
TCFH60NW
TCFH100N /
TCFH100NW
Single 8-10; 2.8 (25),
12-18; 2.6 (20)
10-14; 2.6 (20),
4-8; 3.9 (35)
10-18; 2.6 (20)**,
1-8; 4.5 (40)†
Dual 10-18; 2.8 (25)* 10-18; 2.6 (20),
6-8; 3.9 (35) 6; 5.1 (45)
* 10-18 AWG stranded, 14-18 AWG solid
** Solid and stranded
† Stranded
Carton quantity and weight
Amp rating Qty. Weight per carton lb (kg)
30 12 2.42 (1.10)
60 12 2.57 (1.17)
100 61.38 (0.63)
All 30, 60 and 100 A CUBEFuse holders
dovetail together to create the desired
number of poles. Each holder accepts
CUBEFuse amp ratings up to its rating.
E.g., the 60 amp holder will accept a
CUBEFuse from 1 to 60 A.
Amps H I J K L M
Max
height
with
fuse
30 2.3 (58) 0.76 (19) 1.36 (34) 0.15 (4) 2.36 (60)
60 2.6 (66) 1.03 (26) 1.60 (41) 0.17 (4) 2.73 (69)
100 2.91 (74) 1.05 (27) 2.01 (51) 0.15 (4) 0.80 (20) 2.51 (64) 3.27 (83)
Dimensions — in (mm)
Recommended Bussmann series fuses
Type Amp range Data sheet
600 volt UL Listed
Time-delay indicating Low-Peak™ 6-100 A 9000
Time-delay non-indicating Low-Peak 1-100 A
Fast-acting non-indicating 1-100 A 2147
690 volt UL Recognized
Fast-acting wind power 1-100 A 9009
3
Technical Data 9007
Effective March 2019
UL Class CF CUBEFuse holders
Eaton.com/bussmannseries
200, 225 and 400 A CUBEFuse holder fuse applications
Holder catalog no. Volts CUBEFuse amp range
TCFH200N
600 Vac/300 Vdc
110-200
TCFH225N 110-225
TCFH400N 110-400*
* Achieving 400 A continuous current requires three ganged holders
and installed lug catalog number CCP2-L4B-3 to permit the necessary
copper conductor size.
Available lug kits
For complete installation, the 200, 225 and 400 A CUBEFuse holders
require lugs. The table below contains the information necessary for
ordering the desired lug kit for the application.
Accessories
Catalog no.
Holder
amps Description
CCP2-TS2-3
200/225
3-pole terminal shroud
CCP2-PB2 Phase barriers (pack of 2)
CCP2-CWK2 1/4” QC terminals. Use with CCP2-L2-1A,
CCP2-MW2-3 and CCP2-MW2-6 lugs (pack of 12)
CCP2-TS6-3 400 3-pole terminal shroud
CCP2-PB6 Phase barriers (pack of 2)
Recommended Bussmann series fuses
Type Amp range Data sheet
Time-delay indicating Low-Peak 110-400 A 9000
Time-delay non-indicating Low-Peak
Available lugs, conductor ratings and terminal torques
Catalog no. Description
Lugs per
cat. no.
Wire range
AWG (mm2)
Wire type/
temp.
Conductor
torque N•m
(lb-in)
Lug mounting screw
torque N•m (lb-in)
200/225 A holders
CCP2-L2-1 Stainless steel lug 1350-4 (185-25) Cu 75°C 20.3 (180) 0.9 (8)
CCP2-L2-1A Aluminum lug* 1350-4 (185-25) Cu/Al 75°C 28.2 (250) 13.5 (120)
CCP2-MW2-3 3-port multi-wire terminal with shroud*† 32-14 (35-2.5) Cu/Al 75°C 7.9 (70) 10.8 (95)
CCP2-MW2-6 6-port multi-wire terminal with shroud*† 36-14 (16-2.5) Cu/Al 75°C 2.8 (25) 10.8 (95)
* These lugs also accept 1/4” quick connect control wire terminals. Order catalog number CCP2-CWK2 (package of 12 terminals).
400 A holders
CCP2-L4-1 Stainless steel lug 1500-3 (240-35) Cu 75°C 42.0 (375)
22.0 (200)
CCP2-L4-1A Aluminum lug 1500-3 (240-35) Cu/Al 75°C 42.0 (375)
CCP2-L4B-3 Stainless steel lug kit with shroud† 3750-500 (400-240) Cu 75°C 57.0 (500)
CCP2-L4B-3A Aluminum lug kit with shroud† 3750-500 (400-240) Cu/Al 75°C 62.0 (550)
CCP2-L6-3 2-port stainless steel lug kit with shroud 3(2) 500-2 (240-35) Cu 75°C 42.0 (375)
CCP2-L6-3A 2-port aluminum lug kit with shroud 3(2) 500-2 (240-35) Cu/Al 75°C 42.0 (375)
CCP2-MW6-6 6-port multi-wire terminal with shroud† 31/0-14 (50-2.5) Cu/Al 75°C
10-14 = 3.9 (35)
8 = 4.5 (40)
4-6 = 5.0 (45
1/0-2 = 5.6 (50)
This is a lug kit with three lugs and a shroud for installation on three ganged CUBEFuse holders.
Carton quantity
Catalog no. Description Qty.
200/225 A holders
TCFH200N 1-pole 200 A holder 1
TCFH225N 1-pole 225 A holder 1
CCP2-L2-1 Stainless steel lug 1
CCP2-L2-1A Aluminum lug 1
CCP2-MW2-3 3-port multi-wire terminal with shroud 3
CCP2-MW2-6 6-port multi-wire terminal with shroud 3
CCP2-CWK2 1/4” quick connect control wire terminals 12
CCP2-TS2-3 3-pole terminal shroud 1
CCP2-PB2 Phase barriers (pack of 2) 2
400 A holders
TCFH400N 1-pole 400 A holder 1
CCP2-L4-1 Stainless steel lug 1
CCP2-L4-1A Aluminum lug 1
CCP2-L4B-3 Aluminum lug kit with shroud 3
CCP2-L4B-3A Aluminum lug kit with shroud 3
CCP2-MW6-6 6-port multi-wire terminal with shroud 3
CCP2-TS6-3 3-pole terminal shroud 1
CCP2-PB6 Phase barriers (pack of 2) 2
Lug
Terminal shroud
All 200, 225 and 400 amp holders
require installing lugs. Only
three ganged holders can accept
terminal shrouds. See table below.
4
Technical Data 9007
Effective March 2019
UL Class CF CUBEFuse holders
Eaton.com/bussmannseries
167.7
(6.6)
27.5
(1.1)
43.66
(1.7)
2xØ 4.2 (0.2)
33.4
(1.3)
400 A holder
276.0
(10.9)
99.6
(3.9)
139.2
(5.5)
3-pole ganged 400 A holder with installed shroud
40.7
(1.6)
25.3
(1.0)
34.9
(1.4)
23.9
(0.9)
124.5
(4.9)
2xØ 4.2 (0.2)
Dimensions — mm (in)
200/225 A holder
87.6
(3.4)
282.6
(11.1)
104.8
4.1)
108.1
(4.2)
3-pole ganged 200 A holder with installed shroud
5
Technical Data 9007
Effective March 2019
UL Class CF CUBEFuse holders
Eaton.com/bussmannseries
Ordering a complete 200/225 A holder installation
For a complete installation, select from the following required and optional components, and accessories.
Catalog no.
Holders Amps Poles
Required
TCFH200N 200
1
Order required quantity for installation
TCFH225N 225
And
Lug kits Description
CCP2-L2-1 Stainless steel lug, 75° Cu only, 350 kcmil-4, 1 per pack
CCP2-L2-1A Aluminum lug, 75°C Cu/Al, 350 kcmil-4, 1 per pack
CCP2-MW2-3 3-port multi-wire lug, 75°C Cu/Al, 2-14, 3 per pack, includes terminal shroud
CCP2-MW2-6 6-port multi-wire lug, 75°C Cu/Al, 6-14, 3 per pack, includes terminal shroud
And
Accessories
Terminal shrouds Description
CCP2-TS2-3 3-pole terminal shroud with phase shields, 1 per pack
Phase barriers Description
CCP2-PB2 Phase barriers, 2 per pack
And
Control terminals Description
CCP2-CWK2 1/4” quick-connect control wire terminals - mounts on installed lug (cannot be used
with lug CCP2-L2-1), 12 per pack
UL Class CF CUBEFuse holdersTechnical Data 9007
Effective March 2019
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help
the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue
or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this
bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Eaton, Bussmann, CUBEFuse, and Low-Peak
are valuable trademarks of Eaton in the US
and other countries. You are not permitted to
use the Eaton trademarks without prior writ-
ten consent of Eaton.
CSA is a registered trademark of the Canadian
Standards Group
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2019 Eaton
All Rights Reserved
Printed in USA
Publication No. 9007 – BU-SB18087
March 2019
For Eatons Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Follow us on social media to get the
latest product and support information.
Ordering a complete 400 A holder installation
For a complete installation, select from the following required and optional components, and accessories.
Catalog no.
Holder Amps Poles
Required
TCFH400N 400 1
Order required quantity for installation
And
Lug kits Description
CCP2-L4-1 Stainless steel lug, 75° Cu only, 500 kcmil-3, 1 per pack
CCP2-L4-1A Aluminum lug, 75° Cu only, 500 kcmil-3, 1 per pack
CCP2-L4B-3 Stainless steel lug, 75° Cu only, 750-500 kcmil, 3 per pack, includes terminal shroud
CCP2-L4B-3A Aluminum lug, 75°C Cu/Al, 750-500 kcmil, 3 per pack, includes terminal shroud
CCP2-L6-3 2-port stainless steel lug, 75° Cu only, 500 kcmil-2, 3 per pack, includes terminal shroud
CCP2-L6-3A 2-port aluminum lug, 75° Cu only, 500 kcmil-2, 3 per pack, includes terminal shroud
CCP2-MW6-6 6-port multi-wire lug, 75°C Cu/Al, 1/0-14, 3 per pack, includes terminal shroud
And
Accessories
Terminal
shrouds Description
CCP2-TS6-3 3-pole terminal shroud with phase shields, 1 per pack
Phase barriers Description
CCP2-PB6 Phase barriers, 2 per pack
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Eaton:
TCFH100N TCFH30N TCFH60N TCFH225N TCFH400N