4−line filters
for converters and power electronics
520/300 V ac, 50/60 Hz, 8...200 A, 50 °C
Ordering code: B84144A0008...A0200R120
Date: 2009−01−16
Version: 09
EPCOS AG 2008. Reproduction, publication and dissemination of this publication, enclosures
hereto and the information contained therein without EPCOS’ prior express consent is prohibited.
4−line filters B84144A0008...A0200R120
for converters and power electronics
Construction
4−line filter
Metal case
Features
Easy to install
Compact design
Design complies with IEC 60939
cULus, ENEC approval
Optimized for long motor cable
and operation under full load
Applications
Frequency converters for motor drives, e.g.
elevators
pumps
traction systems
conveyor systems
HVAC systems (heating, ventilation and air conditioning)
Power supplies
Terminals
Line side: finger−safe terminal blocks
Load side: finger−safe terminal blocks
Marking
Marking on component:
manufacturers logo, ordering code, rated voltage, rated current,
rated temperature, climatic category, date code
Minimum marking on packaging: maufacturers logo, ordering code,
date code, quantity
1) To IEC 60529:2001
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
Typical circuit diagram
LINE LOAD
L1
N
L3
L2
L1’
N’
L3’
L2’
Technical data and measuring conditions
Rated voltage UR520/300 V AC
Rated frequency fR50/60 Hz
Test voltage line to line for 2 s Utest 2240 V DC
Test voltage line to case for 2 s Utest 2720 V DC
Rated temperature TR50 °C
Overload capability (thermal)
for 3 min per hour or
for 30 s per hour 1.5 x IR
2.5 x IR
Climatic category (IEC 60068−1) 25/100/21
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
Characteristics and ordering codes
IRTerminal
cross
section
Ileak 2) Rtyp Approx.
weight Ordering code Approvals
A mm2mA mkg
8 4 <3,5 13,6 1,55 B84144A0008R120 x x x
16 4 <3,5 7,5 1,6 B84144A0016R120 x x x
25 4 <3,5 3,9 1,7 B84144A0025R120 x x x
36 10 <3,5 2,7 2,15 B84144A0036R120 x x x
50 10 <3,5 1,3 2,2 B84144A0050R120 x x x
66 16 <3,5 1,1 3,6 B84144A0066R120 x x x
90 25 <3,5 0,76 5,1 B84144A0090R120 x x x
120 50 <3,5 0,47 9,5 B84144A0120R120 x x x
150 95 <3,5 0,32 11,7 B84144A0150R120 x x x
200 95 <3,5 0,23 12,5 B84144A0200R120 x x x
X = approval granted
2) 3 phase operation in TN network; maximum voltage = UR; frequency = 50 Hz without harmonics; tolerance of capacitors −20%/ 0%; worst
case positioning of the components; unbalance 2% according EN 50160:2000.
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
Dimensional drawings
60
200
80
650,3
6,5
238
2250,5
80
12
45
PE M5x19
Tightening torque 2 ± 0,1 Nm
Terminals 4mm2
Tightening torque of screw 0,65 − 0,8Nm
All dimensions in mm!
2
B84144A0008R120
B84144A0016R120
B84144A0025R120
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
60
2
230
90
750,3
272
2570,5
6,5
90
12
45
Terminals 10mm2
Tightening torque of screw 1,2 − 1,5Nm
PE M6x24
Tightening torque 3 ± 0,15 Nm
B84144A0036R120
B84144A0050R120
All dimensions in mm!
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
80
10
(2)
32,3260
100
850,3
290
2750,5
100
32,3
6,5
64,520,3
11
40
41 12
Terminals Phoenix HDFK16
Tightening torque of screw 2 − 2,3Nm
PE M6x24
Tightening torque 3 ± 0,15 Nm
All dimensions in mm!
B84144A0066R120
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
100
130
1150,3
(2)
280
2650,5
6,5
38,5
250
(93,1)
130
20
20 (48,5) (10,2)
Terminals Phoenix HDFK25
Tightening torque of screw 4 − 4,5Nm
PE M8x29
Tightening torque 6 ± 0,3 Nm
All dimensions in mm!
B84144A0090R120
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
130
(2)
130
1150,3
2650,5
280
(43)
6,5
130
96,8
20
20 (54) (20)
Terminals Phoenix HDFK50
Tightening torque of screw 6 − 8Nm
PE M10x39
Tightening torque 10 ± 1 Nm
250
All dimensions in mm!
B84144A0120R120
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
280
130
100,7
(2)
(50,5)
(250)
160
1450,5
2650,5
6,5
160
115 13,5
17
80
Terminals Phoenix HDFK95
Tightening torque of screw 15 − 20Nm
PE M10x39
Tightening torque 10 ± 1 Nm
All dimensions in mm!
B84144A0150R120
B84144A0200R120
Please read and Cautions and warnings and
Important notes at the end of this document.
   

4−line filters B84144A0008...A0200R120
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84144A0025R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84144A0036R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84144A0016R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84144A0008R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
Please read and Cautions and warnings and
Important notes at the end of this document.
  

4−line filters B84144A0008...A0200R120
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84144A0090R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84144A0120R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84144A0066R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84144A0050R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
Please read and Cautions and warnings and
Important notes at the end of this document.
   

4−line filters B84144A0008...A0200R120
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84144A0200R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84144A0150R120
f
104105106107108
Hz
dB
0
20
40
60
80
100
Please read and Cautions and warnings and
Important notes at the end of this document.
   

4−line filters B84144A0008...A0200R120
for converters and power electronics
Caution and warnings
Please note the advices in our data book “EMC Filters” (latest edition); attention should
be paid to the chapter “General safety notes”.
It shall be ensured that only qualified persons (electricity specialists) are engaged on work
such as planning, assembly, installation, operation, repair and maintenance. They must
be provided with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge.
Dangerous voltages can continue to exist at the filter terminals for longer than five min-
utes even after the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is
installed and the last to be disconnected. Depending on the magnitude of the leakage cur-
rents, the particular specifications for making the protective−earth connection must be ob-
served.
Impermissible overloading of the EMC filter, such as with circuits able to cause reso-
nances, impermissible voltages at higher frequencies etc. can lead to bodily injury and
death as well as cause substantial material damages (e.g. destruction of the filter hous-
ing).
EMC filters must be protected in the application against impermissible exceeding of the
rated currents by overcurrent protective.
In case of leakage currents > 3.5 mA you shall mount the PE conductor stationary with
the required cross section before beginning of operation and save it against disconnect-
ing. For leakage currents IL 4) < 10 mA the PE conductor must have a KU value 3) of 4.5;
for leakage currents IL 10 mA the PE conductor must have a KU value of 6.
3) The KU value (symbol KU) is a classification parameter of safety−referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
A value of KU = 4.5 with respect to interruptions is attained:
− with a permanently connected protective earth circuit 1.5 mm2
− with a protective earth circuit 2.5 mm2 connected via shroud connectors (IEC 60309−2).
KU = 6 with respect to interruptions is achieved for fixed−connection lines 10 mm2 where the type of connection and line layout corre-
spond to the requirements for PEN conductors as specified in relevant standards.
4) IL = leakage current let−go
Please read and Cautions and warnings and
Important notes at the end of this document.
   

4−line filters B84144A0008...A0200R120
for converters and power electronics
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products
for certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned.
We nevertheless expressly point out that such statement cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar
with them than the customers themselves. For these reasons, it is always ultimately incum-
bent on the customer to check and decide whether an EPCOS product with the properties
described in the product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or
failure before end of their usual service life time cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in
which the malfunction or failure of a passive electronic component could endanger human
life or health (e.g. in accident prevention or life−saving systems), it must therefore be en-
sured by means of suitable design of the customer application or other action taken by the
customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is
sustained by third parties in the event of malfunction or failure of a passive electronic compo-
nent.
3. The warnings, cautions and product−specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions
(e.g. because they are classed as hazardous). Useful information on this will be found in
our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any
more detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in
this publication may change from time to time. The same is true of the corresponding
product specifications. Please check therefore to what extent product descriptions and spec-
ifications contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Conse-
quently, we cannot guarantee that all products named in this publication will always be avail-
able. The aforementioned does not apply in the case of individual agreements deviating from
the foregoing for customer−specific products.
6. Unless otherwise agreed in individual contracts, all orders subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu−X, CeraDiode, CSSP, CTVS, DSSP, MiniBlue, MKK,
MLSC, MotorCAP, PCC, PhaseCap, PhaseMod, SIFERRIT, SIFI, SIKOREL, SilverCap,
SIMDAD, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are
trademarks registered or pending in Europe and in other countries. Further information
will be found on the Internet at www.epcos.com/trademarks.
1
Please read and Cautions and warnings and
Important notes at the end of this document.
   

Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
EPCOS:
B84144A120R120 B84144A150R120 B84144A25R120 B84144A36R120 B84144A90R120 B84144A8R120
B84144A0050R120 B84144A0200R120