PST AND PST...-R ELECTRONIC PRESSURE SWITCHES
EN0B-0346GE51 R0609
7
OVERVIEW OF ADJUSTABLE PARAMETERS
LCD display shows parameters adjustable in
activity / situation symbols digital values / text basic mode expert mode
Current Pressure Is Displayed1
current pressure , unit digital value - -
SP [RP] of OUT1 OUT1 - - -
SP [RP] of OUT2 OUT2 - - -
AOUT (pressure betw. ZERO & FSO) AOUT - - -
pressure is rising - - -
pressure is dropping - - -
warning WARN digital value NO NO
Parameterizing Output 1 [Output 2]
SP , OUT1 [OUT2], SP digital value YES NO
RP , OUT1 [OUT2], RP digital value YES NO
first limit of window (WIN) , OUT1 [OUT2], SP digital value YES NO
second limit of window (WIN) , OUT1 [OUT2], RP digital value YES NO
Configuring Output 1 [Output 2]
max. pressure monitor (SP>RP) EXPERT, SP, RP, OUT1 [OUT2] NO YES
min. pressure monitor (SP<RP) EXPERT, SP, RP, OUT1 [OUT2] NO YES
window monitor (WIN) EXPERT, WIN OUT1 [OUT2] NO YES
output 2 as WARN EXPERT, WARN OUT2 NO YES
N-C low-side output 1 [2], OC2 EXPERT, , ZERO FCT1 [FCT2] NO YES
N-O low-side output 1 [2], OC2 EXPERT, , ZERO FCT1 [FCT2] NO YES
N-C high-side output 1 [2], OC2 EXPERT, , FSO FCT1 [FCT2] NO YES
N-O high-side output 1 [2], OC2 EXPERT, , FSO FCT1 [FCT2] NO YES
output 1 [2] as "push-pull" EXPERT, , ZERO, FSO FCT1 [FCT2] NO YES
output 1 [2] as inverted "push-pull" EXPERT, , ZERO, FSO FCT1 [FCT2] NO YES
Parameterizing the Analog Output
first limit (ZERO) of range , AOUT, ZERO digital value YES NO
second limit (FSO) of range , AOUT, FSO digital value YES NO
Configuring the Analog Output
0...10 V voltage-controlled output EXPERT, AOUT FCTV NO YES
10...0 V voltage-controlled output EXPERT, AOUT, INV FCTV NO YES
4...20 mA current-control output EXPERT, AOUT FCTA NO YES
20...4 mA current-control output EXPERT, AOUT, INV FCTA NO YES
Configuring the Relay
relay coupled with output 1 EXPERT, OUT1 REL NO YES
relay coupled with output 2 EXPERT, OUT2 REL NO YES
relay configured as alarm output EXPERT, WARN REL NO YES
Configuring Unit
unit EXPERT, Pa / bar / psi UNIT NO YES
Parameterizing Filter
attenuation , ATT, % digital value or OFF YES NO
Locking / Unlocking Device Using a Code
unlocked (code = 0000) - EXP YES NO
locked (code ≠ 0000) - CODE, digital value YES NO
Changing Code
device is locked EXPERT LOCK NO YES
device is unlocked EXPERT CODE NO YES
1The same symbols appearing in the expert mode are also visible in the user mode, where they indicate the current configuration of the given
output. Exceptions: If an output has been configured to act as a max. / min. monitor, in the user mode, and appear instead of and .
2Open-Collector